ВВГ

ВВГ is a GOST (Russia) cable designation: В = PVC insulation (also reduced-fire-hazard PVC); В = PVC outer sheath; Г = No armour (a bare cable); not the "flexible" Г of the installation wires ПуГВ; ВВГ = ВВГ: unarmoured copper power cable, PVC insulation and PVC sheath, single laying, 0,66 kV (closest VDE: NYY-J / NYY-O, derived by construction). 0,66 kV (0,6/1 kV on some sheets). GOST 31996-2012; TU 3521-010-00214468-2011 (radel.ru sheet).

1 coding system recognises this code

Standard, worked reading and related types

Standards behind these values: IEC 60502-1:2004 (edition 2.0): Power cables with extruded insulation and their accessories for rated voltages from 1 kV (Um = 1,2 kV) up to 30 kV (Um = 36 kV) - Part 1: Cables for rated voltages of 1 kV (Um = 1,2 kV) and 3 kV (Um = 3,6 kV); IEC 60228:2023 (edition 4.0): Conductors of insulated cables. How the values are sourced

Worked reading of ВВГ 1x16 0.6/1 kV:

  • ВВГ: В = PVC insulation (also reduced-fire-hazard PVC); В = PVC outer sheath; Г = No armour (a bare cable); not the "flexible" Г of the installation wires ПуГВ; ВВГ = ВВГ: unarmoured copper power cable, PVC insulation and PVC sheath, single laying, 0,66 kV (closest VDE: NYY-J / NYY-O, derived by construction). 0,66 kV (0,6/1 kV on some sheets). GOST 31996-2012; TU 3521-010-00214468-2011 (radel.ru sheet)
  • 1x16 0.6/1 kV: one core, copper 16 mm²; rated voltage 0.6/1 kV

Related cable types: АВВГ · ВВГЗ · ВВГ-П

GOST (Russia)

SymbolMeaning
ВPVC insulation (also reduced-fire-hazard PVC)
ВPVC outer sheath
ГNo armour (a bare cable); not the "flexible" Г of the installation wires ПуГВ
ВВГВВГ: unarmoured copper power cable, PVC insulation and PVC sheath, single laying, 0,66 kV (closest VDE: NYY-J / NYY-O, derived by construction). 0,66 kV (0,6/1 kV on some sheets). GOST 31996-2012; TU 3521-010-00214468-2011 (radel.ru sheet)

What is ВВГ cable?

ВВГ: unarmoured copper power cable, PVC insulation and PVC sheath, single laying, 0,66 kV (closest VDE: NYY-J / NYY-O, derived by construction). Rating: 0,66 kV (0,6/1 kV on some sheets). Standard: GOST 31996-2012; TU 3521-010-00214468-2011 (radel.ru sheet).

The VDE pairing is derived from the construction, not stated by the radel.ru sheet. No fire index: single laying only. Cu core solid 1,5 to 50 mm2, stranded 16 mm2 and up; up to 16 mm2 there is no inner sheath. Mark order (GOST 31996-2012 cl. 4.3): conductor (А = aluminium, none = copper), insulation, sheath, armour or no-armour letter, then screen, flat -П, fire index, climatic suffix. The full order line adds the size with conductor letters, the N / PE tag and the voltage: 3х2,5ок(N,PE)-0,66. A cable without a (PE) or (N,PE) tag has no green-yellow core (3 cores = grey, brown, black; 4 = grey, brown, black, blue; GOST 31996 Table 4). The Latin spellings are expected transliterations (ВВГ = VVG, Пв = Pv, Шв = Shv, Э = E): seen only as URL slugs, not read from a page. The standard itself mixes scripts (нг(A) with a Latin A, 35oc(N), РЕ with Cyrillic letters).

Documents and pages the readings were taken from

GOST (Russia): how to read the cable type names

Fire behaviour (EU CPR)

A CPR class is declared by the maker in its Declaration of Performance and printed on the sheath (EN 50575 cl 7). This decoder does not assign one. What the CPR classes mean →

Sources: EN 13501-6 draft and FprEN 50575:2014 final draft (drafts, not the published texts); IEC 60332-3-24:2000+A1:2008; EN 13501-3 draft A2.

ВВГ: equivalents in other countries

Shown for 1x16 0.6/1 kV. Each country's rules are applied to this build, keeping the conductor, section, cores, voltage, screen, armour and sheath.

CountryStandardName in that countryVerdictDifferences
GermanyHD 603 3-G (DIN VDE 0276-603)NYY 1x16 RM 0,6/1 kVCloseSheath 1.4 → 1.8 mm; Overall diameter 9.7 → 10.5 mm; this cable as built misses 2 of its rules
IndiaIS 1554 (Part 1)YY 1x16 1100 V (the code letters of IS 1554 (Part 1):1988 cl. 17.3)Closerated 0.635/1.1 kV (same Um 1.2 kV); routine voltage test 3 kV a.c., 5 min (this cable 3.5 kV; IS 1554 (Part 1) cl. 16.2, IS 7098 (Part 1) cl. 17.2.1, IEC 60502-1 Table 11); Sheath 1.4 → 1.8 mm; Overall diameter 9.7 → 10.5 mm; this cable as built misses 1 of its rules

Nominal values computed by each standard's rules, not manufacturer data. This is not a statement that two cables are interchangeable: the buyer's specification and the maker's type test decide.

ВВГ as the cable designer builds it, 1x16 0.6/1 kV

Overall diameter 9.7 mm, about 220 kg/km. Nominal values from the standard's tables for this size, computed, not a maker's data.

LayerMaterialThickness, mmOver the layer, mm
InsulationPVC1.06.9
SheathPVC1.49.7

ВВГ on a drum

The smallest drum that passes every check, for 9.7 mm and about 220 kg/km as the cable designer builds it. Drums as their makers print them; lengths are estimates: whole layers wound nested (each turn in the groove of the layer below), wound diameter 1.05 × OD, 50 mm freeboard under the flange rim. Cable makers' own tables print less, as they count aligned layers.

LengthDrum size (its makers)LayersGross weight
500 mKTG 6 (600 mm flange), plywood KTG drums (Europe), Bayka12 of 14117 kg
1,000 mKTG 8 (800 mm flange), wood KTG drums (Europe), Bayka, KTG16 of 16251–255 kg

Barrel at least 20 × OD = 194 mm for a cable of this kind (Low voltage, single core): KTG table, the cable's datasheet wins. A load rating is the drum maker's own. A steel drum whose maker prints none is checked against the DIN 46391-4 guide load instead: 28 kN per m³ of gross winding volume.

Other lengths, drums and weights: the cable drum calculator

Load it on a truck: 1000 m on its drum in the loading planner

Laying, sizes and datasheet: ВВГ

Current rating and voltage drop: One circuit, C: cable on a wall, 30 °C air: about 76 A. At that current over 100 m, three-phase 400 V, cos φ 0.9: a voltage drop of about 4.2 %. Sources: IEC 60364-5-52:2009, Table B.52.4, p. 43; IEC 60228:2023 Table 4, p. 13; IEC 60228:2023 Annex B, p. 18; IEC 60364-5-52:2009 (ed. 3.0) Annex G (informative), pp. 74 to 75 (read in the standard text) Cable size calculator: smallest section for a load, every factor shown · Voltage drop calculator: IEC 60364-5-52 method and limits

ВВГ belongs to the family LV PVC power cables: the lowest laying temperature, bending radius, pulling, depth, drum handling and the test after laying, every rule with its sources. Laying and handling guide: LV PVC power cables

Terms on this page: oversheath (outer sheath)