ВВГ
ВВГ is a GOST (Russia) cable designation: В = PVC insulation (also reduced-fire-hazard PVC); В = PVC outer sheath; Г = No armour (a bare cable); not the "flexible" Г of the installation wires ПуГВ; ВВГ = ВВГ: unarmoured copper power cable, PVC insulation and PVC sheath, single laying, 0,66 kV (closest VDE: NYY-J / NYY-O, derived by construction). 0,66 kV (0,6/1 kV on some sheets). GOST 31996-2012; TU 3521-010-00214468-2011 (radel.ru sheet).
1 coding system recognises this code
Standard, worked reading and related types
Standards behind these values: IEC 60502-1:2004 (edition 2.0): Power cables with extruded insulation and their accessories for rated voltages from 1 kV (Um = 1,2 kV) up to 30 kV (Um = 36 kV) - Part 1: Cables for rated voltages of 1 kV (Um = 1,2 kV) and 3 kV (Um = 3,6 kV); IEC 60228:2023 (edition 4.0): Conductors of insulated cables. How the values are sourced
Worked reading of ВВГ 1x16 0.6/1 kV:
ВВГ: В = PVC insulation (also reduced-fire-hazard PVC); В = PVC outer sheath; Г = No armour (a bare cable); not the "flexible" Г of the installation wires ПуГВ; ВВГ = ВВГ: unarmoured copper power cable, PVC insulation and PVC sheath, single laying, 0,66 kV (closest VDE: NYY-J / NYY-O, derived by construction). 0,66 kV (0,6/1 kV on some sheets). GOST 31996-2012; TU 3521-010-00214468-2011 (radel.ru sheet)1x16 0.6/1 kV: one core, copper 16 mm²; rated voltage 0.6/1 kV
GOST (Russia)
| Symbol | Meaning |
|---|---|
В | PVC insulation (also reduced-fire-hazard PVC) |
В | PVC outer sheath |
Г | No armour (a bare cable); not the "flexible" Г of the installation wires ПуГВ |
ВВГ | ВВГ: unarmoured copper power cable, PVC insulation and PVC sheath, single laying, 0,66 kV (closest VDE: NYY-J / NYY-O, derived by construction). 0,66 kV (0,6/1 kV on some sheets). GOST 31996-2012; TU 3521-010-00214468-2011 (radel.ru sheet) |
What is ВВГ cable?
ВВГ: unarmoured copper power cable, PVC insulation and PVC sheath, single laying, 0,66 kV (closest VDE: NYY-J / NYY-O, derived by construction). Rating: 0,66 kV (0,6/1 kV on some sheets). Standard: GOST 31996-2012; TU 3521-010-00214468-2011 (radel.ru sheet).
The VDE pairing is derived from the construction, not stated by the radel.ru sheet. No fire index: single laying only. Cu core solid 1,5 to 50 mm2, stranded 16 mm2 and up; up to 16 mm2 there is no inner sheath. Mark order (GOST 31996-2012 cl. 4.3): conductor (А = aluminium, none = copper), insulation, sheath, armour or no-armour letter, then screen, flat -П, fire index, climatic suffix. The full order line adds the size with conductor letters, the N / PE tag and the voltage: 3х2,5ок(N,PE)-0,66. A cable without a (PE) or (N,PE) tag has no green-yellow core (3 cores = grey, brown, black; 4 = grey, brown, black, blue; GOST 31996 Table 4). The Latin spellings are expected transliterations (ВВГ = VVG, Пв = Pv, Шв = Shv, Э = E): seen only as URL slugs, not read from a page. The standard itself mixes scripts (нг(A) with a Latin A, 35oc(N), РЕ with Cyrillic letters).
Documents and pages the readings were taken from
Fire behaviour (EU CPR)
PVC sheath (В).
Typically targeted, as declared by makers for this kind of construction in the examples this site checked (not the class of this cable):
EcaN1XV-R, Ahlsell (seller)Cca-s3,d1,a3FG16OR16, Nexans (La Triveneta Cavi)EcaU1000 R2V, Nexans (La Triveneta Cavi)EcaN2XSY, Waskönig+Walter (10 kV datasheet)
Listed as sources, alphabetically by maker. No maker pays to appear here.
A CPR class is declared by the maker in its Declaration of Performance and printed on the sheath (EN 50575 cl 7). This decoder does not assign one. What the CPR classes mean →
Sources: EN 13501-6 draft and FprEN 50575:2014 final draft (drafts, not the published texts); IEC 60332-3-24:2000+A1:2008; EN 13501-3 draft A2.
ВВГ: equivalents in other countries
Shown for 1x16 0.6/1 kV. Each country's rules are applied to this build, keeping the conductor, section, cores, voltage, screen, armour and sheath.
| Country | Standard | Name in that country | Verdict | Differences |
|---|---|---|---|---|
| Germany | HD 603 3-G (DIN VDE 0276-603) | NYY 1x16 RM 0,6/1 kV | Close | Sheath 1.4 → 1.8 mm; Overall diameter 9.7 → 10.5 mm; this cable as built misses 2 of its rules |
| India | IS 1554 (Part 1) | YY 1x16 1100 V (the code letters of IS 1554 (Part 1):1988 cl. 17.3) | Close | rated 0.635/1.1 kV (same Um 1.2 kV); routine voltage test 3 kV a.c., 5 min (this cable 3.5 kV; IS 1554 (Part 1) cl. 16.2, IS 7098 (Part 1) cl. 17.2.1, IEC 60502-1 Table 11); Sheath 1.4 → 1.8 mm; Overall diameter 9.7 → 10.5 mm; this cable as built misses 1 of its rules |
Nominal values computed by each standard's rules, not manufacturer data. This is not a statement that two cables are interchangeable: the buyer's specification and the maker's type test decide.
ВВГ as the cable designer builds it, 1x16 0.6/1 kV
Overall diameter 9.7 mm, about 220 kg/km. Nominal values from the standard's tables for this size, computed, not a maker's data.
| Layer | Material | Thickness, mm | Over the layer, mm |
|---|---|---|---|
| Insulation | PVC | 1.0 | 6.9 |
| Sheath | PVC | 1.4 | 9.7 |
ВВГ on a drum
The smallest drum that passes every check, for 9.7 mm and about 220 kg/km as the cable designer builds it. Drums as their makers print them; lengths are estimates: whole layers wound nested (each turn in the groove of the layer below), wound diameter 1.05 × OD, 50 mm freeboard under the flange rim. Cable makers' own tables print less, as they count aligned layers.
| Length | Drum size (its makers) | Layers | Gross weight |
|---|---|---|---|
| 500 m | KTG 6 (600 mm flange), plywood KTG drums (Europe), Bayka | 12 of 14 | 117 kg |
| 1,000 m | KTG 8 (800 mm flange), wood KTG drums (Europe), Bayka, KTG | 16 of 16 | 251–255 kg |
Barrel at least 20 × OD = 194 mm for a cable of this kind (Low voltage, single core): KTG table, the cable's datasheet wins. A load rating is the drum maker's own. A steel drum whose maker prints none is checked against the DIN 46391-4 guide load instead: 28 kN per m³ of gross winding volume.
Other lengths, drums and weights: the cable drum calculator
Load it on a truck: 1000 m on its drum in the loading planner
Laying, sizes and datasheet: ВВГ
ВВГ belongs to the family LV PVC power cables: the lowest laying temperature, bending radius, pulling, depth, drum handling and the test after laying, every rule with its sources. Laying and handling guide: LV PVC power cables
Terms on this page: oversheath (outer sheath)
Selling this cable? Open it in the designer and get a datasheet with your logo (Pro). Open the cable designer · See Pro