BIS type names (India): slik leser du kabeltypenavnene

Hvert navn i BIS type names (India) står for en hel kabeltype: A2XY har for eksempel sin egen konstruksjon, standard og egne merkedata. Dekoderen kjenner 18 typer i dette systemet. Nedenfor: hvordan navnene er bygd opp, hver type med sine merkedata og kildene tabellen nevner.

Slik er et navn bygd opp

Typetabellen deler hvert navn opp i deler og angir hva hver del betyr. Noen navn tatt fra hverandre:

A2XY

AAluminiumsleder
2XIsolasjon av tverrbundet polyetylen (PEX)
YPVC-ytterkappe

A2XY: aluminium conductors, XLPE insulation, inner sheath, unarmoured, PVC outer sheath (IS 7098-1, up to 1100 V)

2XY

2XIsolasjon av tverrbundet polyetylen (PEX)
YPVC-ytterkappe

2XY: copper conductors, XLPE insulation, inner sheath, unarmoured, PVC outer sheath (IS 7098-1, up to 1100 V)

A2XFY

AAluminiumsleder
2XIsolasjon av tverrbundet polyetylen (PEX)
FFlat galvanisert ståltrådarmering (bånd)
YPVC-ytterkappe

A2XFY: aluminium conductors, XLPE insulation, inner sheath, galvanised steel strip (formed wire) armour, PVC outer sheath (IS 7098-1, up to 1100 V)

2XWY

2XIsolasjon av tverrbundet polyetylen (PEX)
WRund ståltrådarmering
YPVC-ytterkappe

2XWY: copper conductors, XLPE insulation, inner sheath, unarmoured, PVC outer sheath (IS 7098-1, up to 1100 V)

Alle deler som brukes i navnene

DelBetydningBrukes i
YPVC-ytterkappeAYFY AYWY YFY YWY A2XFY A2XWY 2XFY 2XWY A2XY 2XY
2XIsolasjon av tverrbundet polyetylen (PEX)A2XFY A2XWY 2XFY 2XWY A2XY 2XY
AAluminiumslederAYFY AYWY A2XFY A2XWY A2XY
YPVC-isolasjonAYFY AYWY YFY YWY
FFlat galvanisert ståltrådarmering (bånd)AYFY YFY A2XFY 2XFY
WRund ståltrådarmeringAYWY YWY A2XWY 2XWY
FRFlammehemmendeFRLS FR WIRE
PVCPVC-isolasjonFR WIRE IS 1554-2
SCHalvledende lag og skjerm over hver lederHT XLPE IS 1554-2
CUKobberbåndskjermHT XLPE IS 1554-2
ARMArmeringHT XLPE IS 1554-2
PVCPVC-ytterkappeHT XLPE IS 1554-2
LSPVC med lav røykutvikling og lavt halogeninnholdFRLS
HFFRHalogenfri, flammehemmende blandingHFFR WIRE
FLEXIBLEFleksibel leder (klasse 5)MULTICORE FLEXIBLE
HTHT-kabel (high tension) med PEX-isolasjon (XLPE) etter IS 7098-2, for 3,3 kV opp til 33 kV (høyspenning), hver leder skjermetHT XLPE
XLPEIsolasjon av tverrbundet polyetylen (PEX)HT XLPE

Alle typer i BIS type names (India)

TypeBeskrivelseMerkedata
FRLSFRLS / FR-LSH house wire: one copper conductor, flame-retardant PVC insulation with reduced smoke and acid gas emissionUp to and including 1100 V; -15 to +70 C (RR Kabel, Polycab)
FR WIREFR house wire: one copper conductor, flame-retardant PVC insulation1100 V AC (Polycab ETIRA FR)
HFFR WIREHFFR house wire: one flexible copper conductor, halogen-free flame-retardant insulationUp to and including 1100 V; -15 to +70 C, 160 C short circuit (RR Kabel LS0H-FR)
MULTICORE FLEXIBLEMulticore flexible cable: class 5 copper cores in PVC under a PVC sheath, in the general purpose, FR or FR-LSH grade (IS 694 Tables 6, 7 and 9)1100 V (IS 694 Amendment No. 3, 2015)
AYFYAYFY: aluminium conductors, PVC insulation, inner sheath, galvanised steel strip (formed wire) armour, PVC outer sheath (IS 1554-1, up to 1100 V)Up to and including 1100 V a.c.; d.c. up to and including 1500 V to earth; 70 C (Type A PVC) or 85 C (Type C, marked HR 85), 160 C short circuit
AYWYAYWY: aluminium conductors, PVC insulation, inner sheath, galvanised round steel wire armour, PVC outer sheath (IS 1554-1, up to 1100 V)Up to and including 1100 V a.c.; d.c. up to and including 1500 V to earth; 70 C (Type A PVC) or 85 C (Type C, marked HR 85), 160 C short circuit
YFYYFY: copper conductors, PVC insulation, inner sheath, galvanised steel strip (formed wire) armour, PVC outer sheath (IS 1554-1, up to 1100 V)Up to and including 1100 V a.c.; d.c. up to and including 1500 V to earth; 70 C (Type A PVC) or 85 C (Type C, marked HR 85), 160 C short circuit
YWYYWY: copper conductors, PVC insulation, inner sheath, galvanised round steel wire armour, PVC outer sheath (IS 1554-1, up to 1100 V)Up to and including 1100 V a.c.; d.c. up to and including 1500 V to earth; 70 C (Type A PVC) or 85 C (Type C, marked HR 85), 160 C short circuit
A2XFYA2XFY: aluminium conductors, XLPE insulation, inner sheath, galvanised steel strip (formed wire) armour, PVC outer sheath (IS 7098-1, up to 1100 V)Up to and including 1100 V a.c.; d.c. up to and including 1500 V; 90 C normal, 250 C short circuit
A2XWYA2XWY: aluminium conductors, XLPE insulation, inner sheath, galvanised round steel wire armour, PVC outer sheath (IS 7098-1, up to 1100 V)Up to and including 1100 V a.c.; d.c. up to and including 1500 V; 90 C normal, 250 C short circuit
2XFY2XFY: copper conductors, XLPE insulation, inner sheath, unarmoured, PVC outer sheath (IS 7098-1, up to 1100 V)Up to and including 1100 V a.c.; d.c. up to and including 1500 V; 90 C normal, 250 C short circuit
2XWY2XWY: copper conductors, XLPE insulation, inner sheath, unarmoured, PVC outer sheath (IS 7098-1, up to 1100 V)Up to and including 1100 V a.c.; d.c. up to and including 1500 V; 90 C normal, 250 C short circuit
A2XYA2XY: aluminium conductors, XLPE insulation, inner sheath, unarmoured, PVC outer sheath (IS 7098-1, up to 1100 V)Up to and including 1100 V a.c.; d.c. up to and including 1500 V; 90 C normal, 250 C short circuit
2XY2XY: copper conductors, XLPE insulation, inner sheath, unarmoured, PVC outer sheath (IS 7098-1, up to 1100 V)Up to and including 1100 V a.c.; d.c. up to and including 1500 V; 90 C normal, 250 C short circuit
IS 1554-1IS 1554-1: PVC-insulated, PVC-sheathed power cable up to and including 1.1 kV (the letter name, AYFY or AYWY, says the metal and the armour)Up to and including 1100 V a.c.; d.c. up to and including 1500 V to earth; 70 C (Type A PVC) or 85 C (Type C, marked HR 85), 160 C short circuit
IS 7098-1IS 7098-1: XLPE-insulated, PVC-sheathed power cable up to and including 1.1 kV (the letter name, A2XFY or A2XWY, says the metal and the armour)Up to and including 1100 V a.c.; d.c. up to and including 1500 V; 90 C normal, 250 C short circuit
HT XLPEHT XLPE: XLPE-insulated cable for 3.3 kV up to 33 kV, each core with a conductor screen, XLPE insulation, an insulation screen and copper tape; PVC fillers and inner sheath, steel round wire or flat strip armour, PVC outer sheathEarthed 1.9/3.3, 3.8/6.6, 6.35/11, 12.7/22, 19/33 kV, unearthed 3.3/3.3 and 11/11 kV; 90 C normal, 250 C short circuit (BIS catalogue); RR Kabel sells 6.35/11 kV (E)
IS 1554-2HT PVC: PVC-insulated heavy duty cable for 3.3 kV up to 11 kV; at 6.35/11 kV each core with a conductor screen, PVC insulation, an insulation screen and a metallic screen; PVC fillers and inner sheath, steel round wire or formed wire (strip) armour, PVC outer sheath1.9/3.3, 3.3/3.3, 3.8/6.6 and 6.35/11 kV; 70 C normal, 160 C short circuit

Vanlige spørsmål

Hva er kabelen A2XY?

A2XY: aluminium conductors, XLPE insulation, inner sheath, unarmoured, PVC outer sheath (IS 7098-1, up to 1100 V). Merkedata: Up to and including 1100 V a.c.; d.c. up to and including 1500 V; 90 C normal, 250 C short circuit. Standard: IS 7098 (Part 1):2025, cable code cl. 18.3. Navnet leses: A (Aluminiumsleder) + 2X (Isolasjon av tverrbundet polyetylen (PEX)) + Y (PVC-ytterkappe).

Hva er kabelen 2XY?

2XY: copper conductors, XLPE insulation, inner sheath, unarmoured, PVC outer sheath (IS 7098-1, up to 1100 V). Merkedata: Up to and including 1100 V a.c.; d.c. up to and including 1500 V; 90 C normal, 250 C short circuit. Standard: IS 7098 (Part 1):2025, cable code cl. 18.3. Navnet leses: 2X (Isolasjon av tverrbundet polyetylen (PEX)) + Y (PVC-ytterkappe).

Hva er forskjellen mellom A2XY og 2XY?

A2XY: aluminium conductors, XLPE insulation, inner sheath, unarmoured, PVC outer sheath (IS 7098-1, up to 1100 V), Up to and including 1100 V a.c.; d.c. up to and including 1500 V; 90 C normal, 250 C short circuit. 2XY: copper conductors, XLPE insulation, inner sheath, unarmoured, PVC outer sheath (IS 7098-1, up to 1100 V), Up to and including 1100 V a.c.; d.c. up to and including 1500 V; 90 C normal, 250 C short circuit. Navnene skiller seg i: A2XY: A (Aluminiumsleder).

BIS type names (India): hva betyr Y i et kabelnavn?

Y har mer enn én betydning, avhengig av typen: PVC-ytterkappe (AYFY, AYWY, YFY, YWY +6); PVC-isolasjon (AYFY, AYWY, YFY, YWY).

Hva er kabelen A2XFY?

A2XFY: aluminium conductors, XLPE insulation, inner sheath, galvanised steel strip (formed wire) armour, PVC outer sheath (IS 7098-1, up to 1100 V). Merkedata: Up to and including 1100 V a.c.; d.c. up to and including 1500 V; 90 C normal, 250 C short circuit. Standard: IS 7098 (Part 1):2025, cable code cl. 18.3. Navnet leses: A (Aluminiumsleder) + 2X (Isolasjon av tverrbundet polyetylen (PEX)) + F (Flat galvanisert ståltrådarmering (bånd)) + Y (PVC-ytterkappe).

Hva er kabelen 2XWY?

2XWY: copper conductors, XLPE insulation, inner sheath, unarmoured, PVC outer sheath (IS 7098-1, up to 1100 V). Merkedata: Up to and including 1100 V a.c.; d.c. up to and including 1500 V; 90 C normal, 250 C short circuit. Standard: IS 7098 (Part 1):2025, cable code cl. 18.3. Navnet leses: 2X (Isolasjon av tverrbundet polyetylen (PEX)) + W (Rund ståltrådarmering) + Y (PVC-ytterkappe).

Typetabellens kilder

Standarder som nevnes i tabellen

  • IS 694:2010 (cable code cl. 13)
  • insulation IS 5831
  • conductor IS 8130
  • flammability IEC 60332-1 (Polycab)
  • IS 17048:2018 (cable code cl. 7)
  • IS 694:2010 + Amd 3:2015, Tables 6, 7 and 9
  • insulation and sheath IS 5831
  • IS 1554 (Part 1):1988 (reaffirmed 2020), cable code cl. 17.3
  • IS 7098 (Part 1):2025, cable code cl. 18.3
  • IS 1554 (Part 1):1988 (reaffirmed 2020)
  • IS 7098 (Part 1):2025
  • IS 7098-2:2011
  • IS 1554 (Part 2):1988 (reaffirmed 2020)