ELOT type names (Greece): how to read the cable type names

Each name in ELOT type names (Greece) stands for a whole cable type: E1VV-R, for example, comes with its own construction, standard and rating. The decoder knows 8 types of this system. Below: how the names are built, every type with its rating, and the sources the table names.

How a name is built

The type table splits each name into parts and records what each part means. A few names taken apart:

E1VV-R

EE: Greek standard, ELOT ('Ελληνικό πρότυπο')
11: rated voltage 0,6/1 kV ('1 = 1 kV'), not the HD 361 100/100 V
VPVC insulation
VPVC sheath
-RRound Stranded Conductor (Class 2)

E1VV-R: PVC-insulated, PVC-sheathed 0,6/1 kV power cable (Greek standard name of NYY), round stranded conductor (class 2)

J1VV-R

JJ: made to IEC ('Κατά IEC'), the Greek counterpart of the E name
11: rated voltage 0,6/1 kV ('1 = 1 kV'), not the HD 361 100/100 V
VPVC insulation
VPVC sheath
-RRound Stranded Conductor (Class 2)

J1VV-R: PVC-insulated, PVC-sheathed 0,6/1 kV power cable (IEC name of NYY), round stranded conductor (class 2)

J1VV-U

JJ: made to IEC ('Κατά IEC'), the Greek counterpart of the E name
11: rated voltage 0,6/1 kV ('1 = 1 kV'), not the HD 361 100/100 V
VPVC insulation
VPVC sheath
-URound Solid Conductor (Class 1)

J1VV-U: PVC-insulated, PVC-sheathed 0,6/1 kV power cable (IEC name of NYY), round solid conductor (class 1)

J1VV-S

JJ: made to IEC ('Κατά IEC'), the Greek counterpart of the E name
11: rated voltage 0,6/1 kV ('1 = 1 kV'), not the HD 361 100/100 V
VPVC insulation
VPVC sheath
-SSector Stranded Conductor

J1VV-S: PVC-insulated, PVC-sheathed 0,6/1 kV power cable (IEC name of NYY), sector stranded conductor

Every part used in the names

PartMeaningUsed in
VPVC insulationJ1VV-U J1VV-R J1VV-S E1VV-U E1VV-R E1VV-S A05VV-U A05VV-R
VPVC sheathJ1VV-U J1VV-R J1VV-S E1VV-U E1VV-R E1VV-S A05VV-U A05VV-R
11: rated voltage 0,6/1 kV ('1 = 1 kV'), not the HD 361 100/100 VJ1VV-U J1VV-R J1VV-S E1VV-U E1VV-R E1VV-S
JJ: made to IEC ('Κατά IEC'), the Greek counterpart of the E nameJ1VV-U J1VV-R J1VV-S
-URound Solid Conductor (Class 1)J1VV-U E1VV-U A05VV-U
-RRound Stranded Conductor (Class 2)J1VV-R E1VV-R A05VV-R
EE: Greek standard, ELOT ('Ελληνικό πρότυπο')E1VV-U E1VV-R E1VV-S
-SSector Stranded ConductorJ1VV-S E1VV-S
AA: a recognised national type (HD 361), in Greece the successor of NYMA05VV-U A05VV-R
05300/500 VA05VV-U A05VV-R

Every type in ELOT type names (Greece)

TypeDescriptionRating
J1VV-UJ1VV-U: PVC-insulated, PVC-sheathed 0,6/1 kV power cable (IEC name of NYY), round solid conductor (class 1)0,6/1 kV
J1VV-RJ1VV-R: PVC-insulated, PVC-sheathed 0,6/1 kV power cable (IEC name of NYY), round stranded conductor (class 2)0,6/1 kV
J1VV-SJ1VV-S: PVC-insulated, PVC-sheathed 0,6/1 kV power cable (IEC name of NYY), sector stranded conductor0,6/1 kV
E1VV-UE1VV-U: PVC-insulated, PVC-sheathed 0,6/1 kV power cable (Greek standard name of NYY), round solid conductor (class 1)0,6/1 kV
E1VV-RE1VV-R: PVC-insulated, PVC-sheathed 0,6/1 kV power cable (Greek standard name of NYY), round stranded conductor (class 2)0,6/1 kV
E1VV-SE1VV-S: PVC-insulated, PVC-sheathed 0,6/1 kV power cable (Greek standard name of NYY), sector stranded conductor0,6/1 kV
A05VV-UA05VV-U: PVC-insulated, PVC-sheathed installation cable, 300/500 V (the Greek national type that replaced NYM)300/500 V
A05VV-RA05VV-R: PVC-insulated, PVC-sheathed installation cable, 300/500 V (the Greek national type that replaced NYM)300/500 V

Common questions

What is E1VV-R cable?

E1VV-R: PVC-insulated, PVC-sheathed 0,6/1 kV power cable (Greek standard name of NYY), round stranded conductor (class 2). Rating: 0,6/1 kV. Standard: IEC 60502-1 (J) / ELOT (E); TEE Table 1.3.1. The name reads: E (E: Greek standard, ELOT ('Ελληνικό πρότυπο')) + 1 (1: rated voltage 0,6/1 kV ('1 = 1 kV'), not the HD 361 100/100 V) + V (PVC insulation) + V (PVC sheath) + -R (Round Stranded Conductor (Class 2)).

What is J1VV-R cable?

J1VV-R: PVC-insulated, PVC-sheathed 0,6/1 kV power cable (IEC name of NYY), round stranded conductor (class 2). Rating: 0,6/1 kV. Standard: IEC 60502-1 (J) / ELOT (E); TEE Table 1.3.1. The name reads: J (J: made to IEC ('Κατά IEC'), the Greek counterpart of the E name) + 1 (1: rated voltage 0,6/1 kV ('1 = 1 kV'), not the HD 361 100/100 V) + V (PVC insulation) + V (PVC sheath) + -R (Round Stranded Conductor (Class 2)).

What is the difference between E1VV-R and J1VV-R?

E1VV-R: PVC-insulated, PVC-sheathed 0,6/1 kV power cable (Greek standard name of NYY), round stranded conductor (class 2), 0,6/1 kV. J1VV-R: PVC-insulated, PVC-sheathed 0,6/1 kV power cable (IEC name of NYY), round stranded conductor (class 2), 0,6/1 kV. The names differ in: E1VV-R: E (E: Greek standard, ELOT ('Ελληνικό πρότυπο')); J1VV-R: J (J: made to IEC ('Κατά IEC'), the Greek counterpart of the E name).

ELOT type names (Greece): what does V mean in a cable name?

V has more than one meaning, depending on the type: PVC insulation (J1VV-U, J1VV-R, J1VV-S, E1VV-U +4); PVC sheath (J1VV-U, J1VV-R, J1VV-S, E1VV-U +4).

What is J1VV-U cable?

J1VV-U: PVC-insulated, PVC-sheathed 0,6/1 kV power cable (IEC name of NYY), round solid conductor (class 1). Rating: 0,6/1 kV. Standard: IEC 60502-1 (J) / ELOT (E); TEE Table 1.3.1. The name reads: J (J: made to IEC ('Κατά IEC'), the Greek counterpart of the E name) + 1 (1: rated voltage 0,6/1 kV ('1 = 1 kV'), not the HD 361 100/100 V) + V (PVC insulation) + V (PVC sheath) + -U (Round Solid Conductor (Class 1)).

What is J1VV-S cable?

J1VV-S: PVC-insulated, PVC-sheathed 0,6/1 kV power cable (IEC name of NYY), sector stranded conductor. Rating: 0,6/1 kV. Standard: IEC 60502-1 (J) / ELOT (E); TEE Table 1.3.1. The name reads: J (J: made to IEC ('Κατά IEC'), the Greek counterpart of the E name) + 1 (1: rated voltage 0,6/1 kV ('1 = 1 kV'), not the HD 361 100/100 V) + V (PVC insulation) + V (PVC sheath) + -S (Sector Stranded Conductor).

Sources the type table names

Standards named in the table

  • IEC 60502-1 (J) / ELOT (E)
  • TEE Table 1.3.1
  • ELOT 563 (HD 21.3), as the TEE guide and the Greek ministry specification cite it

Documents and pages the readings were taken from

Taken from the type table of this site, with the sources named above. Check the manufacturer's datasheet before you specify a cable.

Every type in ELOT type names (Greece) · Decode your own designation