E1VV-R
E1VV-R is a ELOT type names (Greece) cable designation: E = E: Greek standard, ELOT ('Ελληνικό πρότυπο'); 1 = 1: rated voltage 0,6/1 kV ('1 = 1 kV'), not the HD 361 100/100 V; V = PVC insulation; V = PVC sheath; -R = Round Stranded Conductor (Class 2); E1VV-R = E1VV-R: PVC-insulated, PVC-sheathed 0,6/1 kV power cable (Greek standard name of NYY), round stranded conductor (class 2). 0,6/1 kV. IEC 60502-1 (J) / ELOT (E); TEE Table 1.3.1.
1 coding system recognises this code
ELOT type names (Greece)
| Symbol | Meaning |
|---|---|
E | E: Greek standard, ELOT ('Ελληνικό πρότυπο') |
1 | 1: rated voltage 0,6/1 kV ('1 = 1 kV'), not the HD 361 100/100 V |
V | PVC insulation |
V | PVC sheath |
-R | Round Stranded Conductor (Class 2) |
E1VV-R | E1VV-R: PVC-insulated, PVC-sheathed 0,6/1 kV power cable (Greek standard name of NYY), round stranded conductor (class 2). 0,6/1 kV. IEC 60502-1 (J) / ELOT (E); TEE Table 1.3.1 |
Fire behaviour (EU CPR)
PVC sheath (V).
Typically targeted, as declared by makers for this kind of construction in the examples this site checked (not the class of this cable):
EcaN1XV-R, Ahlsell (seller)Cca-s3,d1,a3FG16OR16, Nexans (La Triveneta Cavi)EcaU1000 R2V, Nexans (La Triveneta Cavi)EcaN2XSY, Waskönig+Walter (10 kV datasheet)
Listed as sources, alphabetically by maker. No maker pays to appear here.
A CPR class is declared by the maker in its Declaration of Performance and printed on the sheath (EN 50575 cl 7). This decoder does not assign one. What the CPR classes mean →
Sources: EN 13501-6 draft and FprEN 50575:2014 final draft (drafts, not the published texts); IEC 60332-3-24:2000+A1:2008; EN 13501-3 draft A2.
E1VV-R as the cable designer builds it, 1x16 0.6/1 kV
Overall diameter 9.7 mm, about 220 kg/km. Nominal values from the standard's tables for this size, computed, not a maker's data.
| Layer | Material | Thickness, mm | Over the layer, mm |
|---|---|---|---|
| Insulation | PVC | 1.0 | 6.9 |
| Sheath | PVC | 1.4 | 9.7 |
E1VV-R on a drum
The smallest drum that passes every check, for 9.7 mm and about 220 kg/km as the cable designer builds it. Drums as their makers print them; lengths are estimates within a few per cent of the cable makers' own tables: whole layers, wound diameter 1.05 × OD, 50 mm freeboard under the flange rim.
| Length | Drum size (its makers) | Layers | Gross weight |
|---|---|---|---|
| 500 m | KTG 6 (600 mm flange), plywood KTG drums (Europe), Bayka | 12 of 12 | 117 kg |
| 1,000 m | KTG 9 (900 mm flange), wood KTG drums (Europe), Bayka, KTG | 11 of 17 | 267–271 kg |
Barrel at least 20 × OD = 194 mm for a cable of this kind (Low voltage, single core): KTG table, the cable's datasheet wins. A load rating is the drum maker's own.
Other lengths, drums and weights: the cable drum calculator
Load it on a truck: 1000 m on its drum in the loading planner
Laying, sizes and datasheet: E1VV-R
E1VV-R belongs to the family LV PVC power cables: the lowest laying temperature, bending radius, pulling, depth, drum handling and the test after laying, every rule with its sources. Laying and handling guide: LV PVC power cables
Selling this cable? Open it in the designer and get a datasheet with your logo (Pro). Open the cable designer · See Pro