UF-B 10/3 W/G 600 V

Nominal calculation, not one manufacturer's datasheet. The conductors are NEC Chapter 9 Table 8; the insulation, nylon and jacket walls and the ground are the values the makers print, and the web of jacket between the conductors is fitted to three makers' widths, because UL 493 was not read. Check the datasheet before you specify or order.

By NEC Table 8 and the makers' walls, UF-B 10/3 W/G 600 V comes to about 19.5 × 5.8 mm (width × thickness) and a weight of about 310 kg/km.

Open this cable in the designer Change any layer, see it in 3D and to scale, and download it.

This size as a PDF datasheet under your brand, with Pro. See Pro

Request a quote for this cable Sent to makers of this cable family, free.

Main dimensions

ConductorCopper 10 AWG (5.3 mm²), Ø 2.6 mmNEC 2026 Chapter 9 Table 8: Class B concentric or solid diameter
InsulationPVC 0.51 mmUF-B conductor PVC insulation: 15 mil to 12 AWG, 20 at 10 AWG, 30 at 8 and 6 (Service Wire; Southwire and Cerrowire the same sums; UL 493 not read)
Diameter over insulation3.6 mm
Core diameter3.8 mm
Width × thickness19.5 × 5.8 mm
Weight (approximate)310 kg/km

Layer by layer (inside out)

#LayerMaterialThickness mmØ over mmSourceHow firmly
1InsulationPVC0.513.6 (on each core)UF-B conductor PVC insulation: 15 mil to 12 AWG, 20 at 10 AWG, 30 at 8 and 6 (Service Wire; Southwire and Cerrowire the same sums; UL 493 not read)maker catalogue value, standard text not read
2Nylon jacket (polyamide)Nylon (PA)0.103.8 (on each core)UF-B conductor nylon jacket: 4 mil to 10 AWG, 5 at 8 and 6 (Service Wire; UL 493 not read)maker catalogue value, standard text not read
3SheathPVC1.025.8UF-B gray PVC jacket, solid between the conductors: 40 mil to 10 AWG, 48 at 8, 55 at 6; the makers print 30 / 45 mil minimums, the values are fitted to five makers' thicknessesmaker catalogue value, standard text not read

UF-B is the UL 493 underground feeder cable of NEC Article 340: copper conductors in PVC and nylon and a bare ground, laid apart in a row in a solid gray PVC jacket that fills between them, no paper. Every size is flat, three conductors too. Its ampacity is that of 60 °C conductors (NEC 340.80). Checked against Southwire, Cerrowire and Service Wire: research/designer-americas/nm-b.md in the site repository.

Materials in this cable: Copper, PVC

Weight, by part

Conductors190 kg/km
Metal screens and armour0 kg/km
Insulation, semicon, tapes, fillers and sheaths120 kg/km
Total310 kg/km

Each layer's cross-section times its density; stranded conductors, laid-up cores and helical wires count 2 % longer than the cable. Densities: copper 8.89 and aluminium 2.703 g/cm³ (the values of IEC 60028 and IEC 60889); XLPE 0.92, PE 0.94, PVC 1.45, semicon 1.12, steel 7.85 g/cm³ (usual compound values).