MC-HL dimensions

Nominal calculation, not one manufacturer's datasheet. The conductors are NEC Chapter 9 Table 8; the XHHW-2 walls, the grounds and the jacket are the values the makers print, and the corrugated sheath is a radial band fitted to four makers' diameters, because UL 1569 and UL 2225 were not read and no maker prints the sheath's wall. Check the datasheet before you specify or order.

Each row is one MC-HL size in copper at 600 V: the conductor from NEC Table 8, the walls as the makers catalogue them. Open a row for every layer and its source. What MC-HL means, letter by letter.

North American building wire, 600 V (AWG / kcmil) · 13 sizes

SizeRatingInsulation mmOverall diameter mmWeight (approximate) kg/km
3C 10 AWG600 V0.7618.0440
3C 8 AWG600 V1.1421.3600
3C 6 AWG600 V1.1423.3820
3C 4 AWG600 V1.1425.81,090
3C 2 AWG600 V1.1430.01,580
3C 1/0 AWG600 V1.4036.72,300
3C 4/0 AWG600 V1.4045.44,150
3C 250 kcmil600 V1.6549.04,840
3C 500 kcmil600 V1.6563.59,000
3C 750 kcmil600 V2.0377.413,290
4C 2 AWG600 V1.1433.61,970
4C 4/0 AWG600 V1.4050.55,250
4C 500 kcmil600 V1.6572.011,570

Who makes or stocks this cable?