YAXC7Z1-R
YAXC7Z1-R is a TS 621 / TSE (Turkey) cable designation: Y = Underground Heavy-Duty Cable For Fixed Installation (Y Cable Family, TS 212); A = Aluminium Conductor; X = Cross-Linked Polyethylene (XLPE) Insulation; C7 = Copper Screen (Wire Or Tape); Also Used For The Concentric Conductor (YVC7V; Z1 = Halogen-Free Flame-Retardant Compound; -R = Round Stranded Conductor (Class 2).
2 coding systems recognise this code
Standard, worked reading and related types
Worked reading of YAXC7Z1-R:
YAXC7Z1-R: Y = Underground Heavy-Duty Cable For Fixed Installation (Y Cable Family, TS 212); A = Aluminium Conductor; X = Cross-Linked Polyethylene (XLPE) Insulation; C7 = Copper Screen (Wire Or Tape); Also Used For The Concentric Conductor (YVC7V; Z1 = Halogen-Free Flame-Retardant Compound; -R = Round Stranded Conductor (Class 2)
Related cable types: YAXC7V-R · YXC7(Q)Z1-R · YXC7Z1
TS 621 / TSE (Turkey)
| Symbol | Meaning |
|---|---|
Y | Underground Heavy-Duty Cable For Fixed Installation (Y Cable Family, TS 212) |
A | Aluminium Conductor |
X | Cross-Linked Polyethylene (XLPE) Insulation |
C7 | Copper Screen (Wire Or Tape); Also Used For The Concentric Conductor (YVC7V |
Z1 | Halogen-Free Flame-Retardant Compound |
-R | Round Stranded Conductor (Class 2) |
HAR: HD 361 harmonised designation (CENELEC)
| Symbol | Meaning |
|---|---|
Y | Turkish TS Type For Medium And Heavy Operating Conditions (e.g. YXC7V-R) |
A | Concentric Aluminium Conductor |
X | Cross-Linked Polyethylene (XLPE) |
C7 | Copper Screen Of Tape, Round Or Profile-Wires Over Twisted Cores |
Z1 | Thermoplastic Polyolefin Compound, Low Smoke And Non-Corrosive Gases (LSZH) |
-R | Multi-Wire, Round-Section, Class 2 |
How to read a HAR: HD 361 harmonised designation (CENELEC) cable code
How to read a TS 621 / TSE (Turkey) cable code
A TS 621 / TSE (Turkey) designation (Turkey) is a row of letter groups, and each group stands for one part of the cable: conductor, insulation, screen, armour, sheath, or the standard it follows. The decoder knows 41 symbols for this system.
What does y mean in a TS 621 / TSE (Turkey) cable code? y means Flat Conductor; or Underground Heavy-Duty Cable For Fixed Installation (Y Cable Family, TS 212).
What does A mean in a TS 621 / TSE (Turkey) cable code? A means Aluminium Conductor.
What does X mean in a TS 621 / TSE (Turkey) cable code? X means Cross-Linked Polyethylene (XLPE) Insulation.
What does C7 mean in a TS 621 / TSE (Turkey) cable code? C7 means Copper Screen (Wire Or Tape); Also Used For The Concentric Conductor (YVC7V = NYCY).
What does Z1 mean in a TS 621 / TSE (Turkey) cable code? Z1 means Halogen-Free Flame-Retardant Compound.
What does -R mean in a TS 621 / TSE (Turkey) cable code? -R means Round Stranded Conductor (Class 2).
Fire behaviour (EU CPR)
Halogen-free compound (Z1). Under the CPR this shows in the additional classes: acidity a1 to a3 (EN 60754-2) and smoke s1 to s3 (EN 50399; s1a and s1b add the 3 m cube test EN 61034-2). The main class, Aca to Fca, depends on the whole construction.
Typically targeted, as declared by makers for this kind of construction in the examples this site checked (not the class of this cable):
B2ca-s1a,d0,a11-CXKH-R-J, Kablo VrchlabíCca-s1b,d1,a1FG16(O)M16, Nexans (La Triveneta Cavi)B2ca-s1a,d1,a1FG18(O)M16, Nexans (La Triveneta Cavi)DcaFXQJ, Nexans NorwayCca-s1b,d1,a1H07Z1-K, Nexans SpainB2ca-s1,d2,a1AXQJ-RMF, Prysmian Sweden (12/20 kV)B2ca-s1a,d1,a1RZ1-K (AS), Top CableCca-s1b,d1,a1RZ1FZ1-K (AS), Top Cable
Listed as sources, alphabetically by maker. No maker pays to appear here.
Flame retardant (Z1). The single-cable test behind class Eca is EN 60332-1-2 (the flame stops within 425 mm). Bunched cables are tested by IEC 60332-3-24 category C (1.5 l/m, 20 min, char at most 2.5 m), which is not a CPR class test; the CPR ladder test for B1ca to Dca is EN 50399.
A CPR class is declared by the maker in its Declaration of Performance and printed on the sheath (EN 50575 cl 7). This decoder does not assign one. What the CPR classes mean →
Sources: EN 13501-6 draft and FprEN 50575:2014 final draft (drafts, not the published texts); IEC 60332-3-24:2000+A1:2008; EN 13501-3 draft A2.
Work with YAXC7Z1-R
Who makes or stocks this cable?
Makers and stockists of this cable family appear here as sponsors for your region, each marked "Sponsored"; a listing never changes what this page says about the cable.