WDZ-BY
WDZ-BY is a China (GB / JB/T / MT cable model codes) cable designation: WD = Low Smoke Zero Halogen Cable; Z = Flame Retardant; B = Fixed Cable; Y = Polyethylene (PE) Or Polyolefin.
1 coding system recognises this code
Standard, worked reading and related types
Worked reading of WDZ-BY:
WDZ-BY: WD = Low Smoke Zero Halogen Cable; Z = Flame Retardant; B = Fixed Cable; Y = Polyethylene (PE) Or Polyolefin
China (GB / JB/T / MT cable model codes)
| Symbol | Meaning |
|---|---|
WD | Low Smoke Zero Halogen Cable |
Z | Flame Retardant |
B | Fixed Cable |
Y | Polyethylene (PE) Or Polyolefin |
How to read a China (GB / JB/T / MT cable model codes) cable code
How to read a China (GB / JB/T / MT cable model codes) cable code
A China (GB / JB/T / MT cable model codes) designation (China) is a row of letter groups, and each group stands for one part of the cable: conductor, insulation, screen, armour, sheath, or the standard it follows. The decoder knows 137 symbols for this system.
What does WD mean in a China (GB / JB/T / MT cable model codes) cable code? WD means Low Smoke Zero Halogen Cable.
What does Z mean in a China (GB / JB/T / MT cable model codes) cable code? Z means Flame Retardant; or Small Cross Sections; or Oil-Impregnated Paper Insulation.
What does B mean in a China (GB / JB/T / MT cable model codes) cable code? B means Fixed Cable; or Polypropylene (PP); or Flat Type.
What does Y mean in a China (GB / JB/T / MT cable model codes) cable code? Y means Polyethylene (PE) Or Polyolefin.
Fire behaviour (EU CPR)
Halogen-free compound (WD). Under the CPR this shows in the additional classes: acidity a1 to a3 (EN 60754-2) and smoke s1 to s3 (EN 50399; s1a and s1b add the 3 m cube test EN 61034-2). The main class, Aca to Fca, depends on the whole construction.
Typically targeted, as declared by makers for this kind of construction in the examples this site checked (not the class of this cable):
B2ca-s1a,d0,a11-CXKH-R-J, Kablo VrchlabíCca-s1b,d1,a1FG16(O)M16, Nexans (La Triveneta Cavi)B2ca-s1a,d1,a1FG18(O)M16, Nexans (La Triveneta Cavi)DcaFXQJ, Nexans NorwayCca-s1b,d1,a1H07Z1-K, Nexans SpainB2ca-s1,d2,a1AXQJ-RMF, Prysmian Sweden (12/20 kV)B2ca-s1a,d1,a1RZ1-K (AS), Top CableCca-s1b,d1,a1RZ1FZ1-K (AS), Top Cable
Listed as sources, alphabetically by maker. No maker pays to appear here.
Flame retardant (Z). The single-cable test behind class Eca is EN 60332-1-2 (the flame stops within 425 mm). Bunched cables are tested by IEC 60332-3-24 category C (1.5 l/m, 20 min, char at most 2.5 m), which is not a CPR class test; the CPR ladder test for B1ca to Dca is EN 50399.
A CPR class is declared by the maker in its Declaration of Performance and printed on the sheath (EN 50575 cl 7). This decoder does not assign one. What the CPR classes mean →
Sources: EN 13501-6 draft and FprEN 50575:2014 final draft (drafts, not the published texts); IEC 60332-3-24:2000+A1:2008; EN 13501-3 draft A2.
Work with WDZ-BY
Who makes or stocks this cable?
Makers and stockists of this cable family appear here as sponsors for your region, each marked "Sponsored"; a listing never changes what this page says about the cable.