RH5Z1-2OL
RH5Z1-2OL is a UNE (Spain: UNE 21123 / UNE 20434) cable designation: RH = Cross-Linked Polyethylene (XLPE); 5 = Aluminium Tape Screen (H5, After RH Or DH: XLPE Or EPR Insulation With The Screen; HD 620 S3 10-E2); Z1 = Low Smoke Zero Halogen Compound; 2OL = Double Layer Longitudinal Water Barrier (On Conductor + Under Jacket).
1 coding system recognises this code
Standard, worked reading and related types
Worked reading of RH5Z1-2OL:
RH5Z1-2OL: RH = Cross-Linked Polyethylene (XLPE); 5 = Aluminium Tape Screen (H5, After RH Or DH: XLPE Or EPR Insulation With The Screen; HD 620 S3 10-E2); Z1 = Low Smoke Zero Halogen Compound; 2OL = Double Layer Longitudinal Water Barrier (On Conductor + Under Jacket)
UNE (Spain: UNE 21123 / UNE 20434)
| Symbol | Meaning |
|---|---|
RH | Cross-Linked Polyethylene (XLPE) |
5 | Aluminium Tape Screen (H5, After RH Or DH: XLPE Or EPR Insulation With The Screen; HD 620 S3 10-E2) |
Z1 | Low Smoke Zero Halogen Compound |
2OL | Double Layer Longitudinal Water Barrier (On Conductor + Under Jacket) |
How to read a UNE (Spain: UNE 21123 / UNE 20434) cable code
A UNE (Spain: UNE 21123 / UNE 20434) designation (Spain) is a row of letter groups, and each group stands for one part of the cable: conductor, insulation, screen, armour, sheath, or the standard it follows. The decoder knows 56 symbols for this system.
What does RH mean in a UNE (Spain: UNE 21123 / UNE 20434) cable code? RH means Cross-Linked Polyethylene (XLPE).
What does 5 mean in a UNE (Spain: UNE 21123 / UNE 20434) cable code? 5 means Aluminium Tape Screen (H5, After RH Or DH: XLPE Or EPR Insulation With The Screen; HD 620 S3 10-E2).
What does Z1 mean in a UNE (Spain: UNE 21123 / UNE 20434) cable code? Z1 means Low Smoke Zero Halogen Compound.
What does 2OL mean in a UNE (Spain: UNE 21123 / UNE 20434) cable code? 2OL means Double Layer Longitudinal Water Barrier (On Conductor + Under Jacket).
Fire behaviour (EU CPR)
Halogen-free compound (Z1). Under the CPR this shows in the additional classes: acidity a1 to a3 (EN 60754-2) and smoke s1 to s3 (EN 50399; s1a and s1b add the 3 m cube test EN 61034-2). The main class, Aca to Fca, depends on the whole construction.
Typically targeted, as declared by makers for this kind of construction in the examples this site checked (not the class of this cable):
B2ca-s1a,d0,a11-CXKH-R-J, Kablo VrchlabíCca-s1b,d1,a1FG16(O)M16, Nexans (La Triveneta Cavi)B2ca-s1a,d1,a1FG18(O)M16, Nexans (La Triveneta Cavi)DcaFXQJ, Nexans NorwayCca-s1b,d1,a1H07Z1-K, Nexans SpainB2ca-s1,d2,a1AXQJ-RMF, Prysmian Sweden (12/20 kV)B2ca-s1a,d1,a1RZ1-K (AS), Top CableCca-s1b,d1,a1RZ1FZ1-K (AS), Top Cable
Listed as sources, alphabetically by maker. No maker pays to appear here.
A CPR class is declared by the maker in its Declaration of Performance and printed on the sheath (EN 50575 cl 7). This decoder does not assign one. What the CPR classes mean →
Sources: EN 13501-6 draft and FprEN 50575:2014 final draft (drafts, not the published texts); IEC 60332-3-24:2000+A1:2008; EN 13501-3 draft A2.
Work with RH5Z1-2OL
Who makes or stocks this cable?
Makers and stockists of this cable family appear here as sponsors for your region, each marked "Sponsored"; a listing never changes what this page says about the cable.