RE4M1
RE4M1 is a CEI-UNEL 35011 (Italy) cable designation: R = Multi-Wire, Round-Section, Class 2; E4 = Cross-Linked Polyethylene (XLPE) Compound, 85 °C; M1 = Low Smoke Zero Halogen Compound (Thermoplastic).
1 coding system recognises this code
Standard, worked reading and related types
Worked reading of RE4M1:
RE4M1: R = Multi-Wire, Round-Section, Class 2; E4 = Cross-Linked Polyethylene (XLPE) Compound, 85 °C; M1 = Low Smoke Zero Halogen Compound (Thermoplastic)
CEI-UNEL 35011 (Italy)
| Symbol | Meaning |
|---|---|
R | Multi-Wire, Round-Section, Class 2 |
E4 | Cross-Linked Polyethylene (XLPE) Compound, 85 °C |
M1 | Low Smoke Zero Halogen Compound (Thermoplastic) |
How to read a CEI-UNEL 35011 (Italy) cable code
A CEI-UNEL 35011 (Italy) designation (Italy) is a row of letter groups, and each group stands for one part of the cable: conductor, insulation, screen, armour, sheath, or the standard it follows. The decoder knows 85 symbols for this system.
What does R mean in a CEI-UNEL 35011 (Italy) cable code? R means Multi-Wire, Round-Section, Class 2; or PVC Compound (TI1/TI2 Quality, 70 °C).
What does E4 mean in a CEI-UNEL 35011 (Italy) cable code? E4 means Cross-Linked Polyethylene (XLPE) Compound, 85 °C.
What does M1 mean in a CEI-UNEL 35011 (Italy) cable code? M1 means Low Smoke Zero Halogen Compound (Thermoplastic).
Fire behaviour (EU CPR)
Halogen-free compound (M1). Under the CPR this shows in the additional classes: acidity a1 to a3 (EN 60754-2) and smoke s1 to s3 (EN 50399; s1a and s1b add the 3 m cube test EN 61034-2). The main class, Aca to Fca, depends on the whole construction.
Typically targeted, as declared by makers for this kind of construction in the examples this site checked (not the class of this cable):
B2ca-s1a,d0,a11-CXKH-R-J, Kablo VrchlabíCca-s1b,d1,a1FG16(O)M16, Nexans (La Triveneta Cavi)B2ca-s1a,d1,a1FG18(O)M16, Nexans (La Triveneta Cavi)DcaFXQJ, Nexans NorwayCca-s1b,d1,a1H07Z1-K, Nexans SpainB2ca-s1,d2,a1AXQJ-RMF, Prysmian Sweden (12/20 kV)B2ca-s1a,d1,a1RZ1-K (AS), Top CableCca-s1b,d1,a1RZ1FZ1-K (AS), Top Cable
Listed as sources, alphabetically by maker. No maker pays to appear here.
A CPR class is declared by the maker in its Declaration of Performance and printed on the sheath (EN 50575 cl 7). This decoder does not assign one. What the CPR classes mean →
Sources: EN 13501-6 draft and FprEN 50575:2014 final draft (drafts, not the published texts); IEC 60332-3-24:2000+A1:2008; EN 13501-3 draft A2.
Work with RE4M1
Who makes or stocks this cable?
Makers and stockists of this cable family appear here as sponsors for your region, each marked "Sponsored"; a listing never changes what this page says about the cable.