PP 00
PP 00 is a JUS / SRPS / HRN N.C0.006 type names (former Yugoslavia) cable designation: P = PVC insulation; P = PVC sheath; 00 = 00: no mechanical protection, no armour (HRN N.C0.006); PP 00 = PP 00: PVC-insulated, PVC-sheathed power cable, 0,6/1 kV (NYY, NAYY; GOST ВВГ, АВВГ); aluminium conductors: PP 00-A. 0,6/1 kV, test voltage 3,5 kV (Novkabel). SRPS N.C5.220.
1 coding system recognises this code
JUS / SRPS / HRN N.C0.006 type names (former Yugoslavia)
| Symbol | Meaning |
|---|---|
P | PVC insulation |
P | PVC sheath |
00 | 00: no mechanical protection, no armour (HRN N.C0.006) |
PP 00 | PP 00: PVC-insulated, PVC-sheathed power cable, 0,6/1 kV (NYY, NAYY; GOST ВВГ, АВВГ); aluminium conductors: PP 00-A. 0,6/1 kV, test voltage 3,5 kV (Novkabel). SRPS N.C5.220 |
What is PP 00 cable?
PP 00: PVC-insulated, PVC-sheathed power cable, 0,6/1 kV (NYY, NAYY; GOST ВВГ, АВВГ); aluminium conductors: PP 00-A. Rating: 0,6/1 kV, test voltage 3,5 kV (Novkabel). Standard: SRPS N.C5.220.
Novkabel pdf p.7: 'PP 00, PP 00-A', NYY, NAYY; GOST ВВГ, АВВГ; construction: conductor class 1 or 2 to SRPS N.C0.015, PVC insulation, filling of non-hygroscopic rubber or thermoplastic compound, black PVC sheath. Split p.11: 'PP00-A, 4 x 50/SV mm2 0,6/1 kV', alternatively 'NAYY- 4x50 SM'. Shops print PP00-Y for NYY-J ('Kabel EYY-J (PP00-Y) 4x16 RE', Schrack). Letters per the Split university text, Tablica 1.3 'Nacin oznacavanja energetskih kabela' (HRN N.C0.006 against HD 603 S1 / HD 620 S1): P = PVC insulation or sheath (HD Y), X = XLPE (2X), Y = green-yellow protective conductor (HD J), H = semiconducting layers round the insulation, E = PE sheath (2Y), Eh = semiconducting PE sheath, 00 = no mechanical protection, 44 = round steel wire armour, 49 = watertight electrical protection (S(F)), 91 = outer protective covering, A = aluminium; OJ / OV / SJ / SV = round solid / round stranded / sector solid / sector stranded conductor (RE / RM / SE / SM). The other two-digit codes are read off the Novkabel catalogue, which prints each SRPS name beside its VDE / HD and GOST twin.
Documents and pages the readings were taken from
- Novkabel AD, 'Cables and Wires' catalogue, pdf p.7
- oss.unist.hr
- kabeltrade.si
- elteh.net
- schrack.hr
- elektromaterijal.hr
JUS / SRPS / HRN N.C0.006 type names (former Yugoslavia): how to read the cable type names
Fire behaviour (EU CPR)
PVC sheath (P, PP 00).
Typically targeted, as declared by makers for this kind of construction in the examples this site checked (not the class of this cable):
EcaN1XV-R, Ahlsell (seller)Cca-s3,d1,a3FG16OR16, Nexans (La Triveneta Cavi)EcaU1000 R2V, Nexans (La Triveneta Cavi)EcaN2XSY, Waskönig+Walter (10 kV datasheet)
Listed as sources, alphabetically by maker. No maker pays to appear here.
A CPR class is declared by the maker in its Declaration of Performance and printed on the sheath (EN 50575 cl 7). This decoder does not assign one. What the CPR classes mean →
Sources: EN 13501-6 draft and FprEN 50575:2014 final draft (drafts, not the published texts); IEC 60332-3-24:2000+A1:2008; EN 13501-3 draft A2.
Work with PP 00
Who makes or stocks this cable?
Makers and stockists of this cable family appear here as sponsors for your region, each marked "Sponsored"; a listing never changes what this page says about the cable.
Related cables
More JUS / SRPS / HRN N.C0.006 type names (former Yugoslavia) designations