P1MeKrvaslqwd
P1MeKrvaslqwd is a NEN / KEMA type names (Netherlands) cable designation: P1 = P1: PP-TPE insulation (polypropylene thermoplastic elastomer; HD 620 S3 12-J Appendix D, NEN 3207 key); MeK = Polyethylene (PE) Sheathed Cable; rv = With Radial Field (Individually Screened Cores, MV); as = With Earthing Screen; lqwd = Longitudinally And Quasi-Radially Water-Tight; P1MeKrvaslqwd = P1MeKrvaslqwd: three-core unarmoured medium-voltage cable, solid aluminium, PP-TPE insulation, common copper wire screen, quasi radially and longitudinally watertight, red PE sheath (HD 620 S3 12-J A.3). 10 and 20 kV underground systems; 6/10 kV 3,4 mm and 12/20 kV 5,5 mm insulation (Table A.3) (HD 620 S3 12-J); PP-TPE insulation, 90 C conductor (HD 620 S3 Part 1 2.1.1). HD 620 S3:2023 section 12-J, Appendix A.3 (p. 12-J-42) code designation and Appendix D NEN 3207 key (p. 12-J-47). seen: standard.
1 coding system recognises this code
NEN / KEMA type names (Netherlands)
| Symbol | Meaning |
|---|---|
P1 | P1: PP-TPE insulation (polypropylene thermoplastic elastomer; HD 620 S3 12-J Appendix D, NEN 3207 key) |
MeK | Polyethylene (PE) Sheathed Cable |
rv | With Radial Field (Individually Screened Cores, MV) |
as | With Earthing Screen |
lqwd | Longitudinally And Quasi-Radially Water-Tight |
P1MeKrvaslqwd | P1MeKrvaslqwd: three-core unarmoured medium-voltage cable, solid aluminium, PP-TPE insulation, common copper wire screen, quasi radially and longitudinally watertight, red PE sheath (HD 620 S3 12-J A.3). 10 and 20 kV underground systems; 6/10 kV 3,4 mm and 12/20 kV 5,5 mm insulation (Table A.3) (HD 620 S3 12-J); PP-TPE insulation, 90 C conductor (HD 620 S3 Part 1 2.1.1). HD 620 S3:2023 section 12-J, Appendix A.3 (p. 12-J-42) code designation and Appendix D NEN 3207 key (p. 12-J-47). seen: standard |
What is P1MeKrvaslqwd cable?
P1MeKrvaslqwd: three-core unarmoured medium-voltage cable, solid aluminium, PP-TPE insulation, common copper wire screen, quasi radially and longitudinally watertight, red PE sheath (HD 620 S3 12-J A.3). Rating: 10 and 20 kV underground systems; 6/10 kV 3,4 mm and 12/20 kV 5,5 mm insulation (Table A.3) (HD 620 S3 12-J); PP-TPE insulation, 90 C conductor (HD 620 S3 Part 1 2.1.1). Standard: HD 620 S3:2023 section 12-J, Appendix A.3 (p. 12-J-42) code designation and Appendix D NEN 3207 key (p. 12-J-47). seen: standard.
Appendix A.3: aluminium round solid; semiconducting swellable tape on each core and over the laid-up cores; non-hygroscopic fillers; copper wires and a copper tape counter spiral (35 mm² for 95 to 240 mm², Table A.3); swellable tape; red PE sheath 3,2 mm. The insulation is drawn without a material: the site has no PP-TPE material yet.
Documents and pages the readings were taken from
- HD 620 S3:2023 12-J Appendix A.3, p. 12-J-42; Appendix D, p. 12-J-47; Part 1 Table 2.1.1, PP-TPE
NEN / KEMA type names (Netherlands): how to read the cable type names
Fire behaviour (EU CPR)
PE sheath (MeK).
Typically targeted, as declared by makers for this kind of construction in the examples this site checked (not the class of this cable):
FcaYMeKrvaslqwd, TKFFcaNA2XS(F)2Y, Waskönig+Walter
Listed as sources, alphabetically by maker. No maker pays to appear here.
A CPR class is declared by the maker in its Declaration of Performance and printed on the sheath (EN 50575 cl 7). This decoder does not assign one. What the CPR classes mean →
Sources: EN 13501-6 draft and FprEN 50575:2014 final draft (drafts, not the published texts); IEC 60332-3-24:2000+A1:2008; EN 13501-3 draft A2.
Work with P1MeKrvaslqwd
Who makes or stocks this cable?
Makers and stockists of this cable family appear here as sponsors for your region, each marked "Sponsored"; a listing never changes what this page says about the cable.