MICC
MICC is a Mineral insulated cables (MICC, IEC 60702-1 grades) cable designation: MICC = Mineral insulated copper cable (MICC, MIMS): solid copper conductors in compressed magnesium oxide inside a seamless or welded copper sheath, bare or with an LSZH covering; fire survival wiring; MICC = MICC: mineral insulated copper sheathed cable (light duty 500 V or heavy duty 750 V). light duty 500 V, heavy duty 750 V; copper sheath 70 C covered or exposed to touch, 105 C bare and out of reach (IEC 60364-5-52:2009 Table 52.1). IEC 60702-1 / BS EN 60702-1 (as the makers cite it; not held here).
1 coding system recognises this code
Mineral insulated cables (MICC, IEC 60702-1 grades)
| Symbol | Meaning |
|---|---|
MICC | Mineral insulated copper cable (MICC, MIMS): solid copper conductors in compressed magnesium oxide inside a seamless or welded copper sheath, bare or with an LSZH covering; fire survival wiring |
MICC | MICC: mineral insulated copper sheathed cable (light duty 500 V or heavy duty 750 V). light duty 500 V, heavy duty 750 V; copper sheath 70 C covered or exposed to touch, 105 C bare and out of reach (IEC 60364-5-52:2009 Table 52.1). IEC 60702-1 / BS EN 60702-1 (as the makers cite it; not held here) |
What is MICC cable?
MICC: mineral insulated copper sheathed cable (light duty 500 V or heavy duty 750 V). Rating: light duty 500 V, heavy duty 750 V; copper sheath 70 C covered or exposed to touch, 105 C bare and out of reach (IEC 60364-5-52:2009 Table 52.1). Standard: IEC 60702-1 / BS EN 60702-1 (as the makers cite it; not held here).
Values and references from three makers that agree; the designer builds every reference.
Documents and pages the readings were taken from
- Wrexham Mineral Cables, Wrexham Mineral Cables catalogue, Standard Conductor Cable tables, pp. 20 to 21: https://electricaldirect-assets.s3.amazonaws.com/product-documentation/technical/835702.pdf [seen: manufacturer]
- nVent Pyrotenax, nVent Pyrotenax MI Wiring Cable System brochure, Pyro MI Cable System Data, p. 10: https://www.topazfiresystems.com/images/special-systems/micc/MICC%20Cable.pdf [seen: manufacturer]
- KME Italy, KME Italy MICO mineral insulated cables brochure, Cable technical data, p. 10: https://www.kme.com/fileadmin/DOWNLOADCENTER/COPPER%20DIVISON/6._Mineral_Insulated_Cables/Mineral_Insulated_Cables_Manuals_KME_Italy_Spa/Brochure_KME_Italy_MICO_Mineral_Insultated_Cables.pdf [seen: manufacturer]
Mineral insulated cables (MICC, IEC 60702-1 grades): how to read the cable type names
Fire behaviour (EU CPR)
Halogen-free compound (MICC). Under the CPR this shows in the additional classes: acidity a1 to a3 (EN 60754-2) and smoke s1 to s3 (EN 50399; s1a and s1b add the 3 m cube test EN 61034-2). The main class, Aca to Fca, depends on the whole construction.
Typically targeted, as declared by makers for this kind of construction in the examples this site checked (not the class of this cable):
B2ca-s1a,d0,a11-CXKH-R-J, Kablo VrchlabíCca-s1b,d1,a1FG16(O)M16, Nexans (La Triveneta Cavi)B2ca-s1a,d1,a1FG18(O)M16, Nexans (La Triveneta Cavi)DcaFXQJ, Nexans NorwayCca-s1b,d1,a1H07Z1-K, Nexans SpainB2ca-s1,d2,a1AXQJ-RMF, Prysmian Sweden (12/20 kV)B2ca-s1a,d1,a1RZ1-K (AS), Top CableCca-s1b,d1,a1RZ1FZ1-K (AS), Top Cable
Listed as sources, alphabetically by maker. No maker pays to appear here.
A CPR class is declared by the maker in its Declaration of Performance and printed on the sheath (EN 50575 cl 7). This decoder does not assign one. What the CPR classes mean →
Sources: EN 13501-6 draft and FprEN 50575:2014 final draft (drafts, not the published texts); IEC 60332-3-24:2000+A1:2008; EN 13501-3 draft A2.
MICC as the cable designer builds it, 2x1.5 300/500 V
Overall diameter 5.7 mm, about 130 kg/km. Nominal values from the standard's tables for this size, computed, not a maker's data.
| Layer | Material | Thickness, mm | Over the layer, mm |
|---|---|---|---|
| Insulation | Compressed magnesium oxide (MgO) | 0.52 | 2.4 |
| Metal sheath (lead or smooth aluminium) | Copper | 0.43 | 5.7 |
MICC on a drum
The smallest drum that passes every check, for 5.7 mm and about 130 kg/km as the cable designer builds it. Drums as their makers print them; lengths are estimates: whole layers wound nested (each turn in the groove of the layer below), wound diameter 1.05 × OD, 50 mm freeboard under the flange rim. Cable makers' own tables print less, as they count aligned layers.
| Length | Drum size (its makers) | Layers | Gross weight |
|---|---|---|---|
| 500 m | KTG 3 (390 mm flange), plastic KTG drums (Europe), KTG | 13 of 15 | 67 kg |
| 1,000 m | KTG 5 (500 mm flange), wood KTG drums (Europe), Meinhart Kabel | 19 of 23 | 138 kg |
Barrel at least 15 × OD = 85 mm for a cable of this kind (Low voltage, multi-core): KTG table, the cable's datasheet wins. A load rating is the drum maker's own.
Other lengths, drums and weights: the cable drum calculator
Load it on a truck: 1000 m on its drum in the loading planner
Laying, sizes and datasheet: MICC
Selling this cable? Open it in the designer and get a datasheet with your logo (Pro). Open the cable designer · See Pro
Work with MICC
Who makes or stocks this cable?
Makers and stockists of this cable family appear here as sponsors for your region, each marked "Sponsored"; a listing never changes what this page says about the cable.
Related cables
More Mineral insulated cables (MICC, IEC 60702-1 grades) designations