LX1AV

LX1AV is a NP 665 (Portugal) cable designation: L = L: aluminium conductor, class 2 (stranded); X = Cross-linked polyethylene (XLPE) insulation; 1A = 1A: armour of aluminium tapes (the Spanish UNE letters FA); V = PVC sheath; LX1AV = LX1AV: aluminium tape armoured 0,6/1 kV power cable, stranded aluminium conductors, XLPE insulation, PVC sheath. 0,6/1 kV. NP 665 designation; IEC 60502-1 (E-REDES DMA-C33-200/N).

1 coding system recognises this code

NP 665 (Portugal)

SymbolMeaning
LL: aluminium conductor, class 2 (stranded)
XCross-linked polyethylene (XLPE) insulation
1A1A: armour of aluminium tapes (the Spanish UNE letters FA)
VPVC sheath
LX1AVLX1AV: aluminium tape armoured 0,6/1 kV power cable, stranded aluminium conductors, XLPE insulation, PVC sheath. 0,6/1 kV. NP 665 designation; IEC 60502-1 (E-REDES DMA-C33-200/N)

Fire behaviour (EU CPR)

A CPR class is declared by the maker in its Declaration of Performance and printed on the sheath (EN 50575 cl 7). This decoder does not assign one. What the CPR classes mean →

Sources: EN 13501-6 draft and FprEN 50575:2014 final draft (drafts, not the published texts); IEC 60332-3-24:2000+A1:2008; EN 13501-3 draft A2.

LX1AV as the cable designer builds it, 4x16 0.6/1 kV

Overall diameter 24.0 mm, about 750 kg/km. Nominal values from the standard's tables for this size, computed, not a maker's data.

LayerMaterialThickness, mmOver the layer, mm
InsulationXLPE0.706.3
FillerPP15.2
Inner covering / beddingPVC1.017.2
SheathPVC1.219.6
Tape armourSteel0.4020.4
SheathPVC1.824.0

LX1AV on a drum

The smallest drum that passes every check, for 24 mm and about 750 kg/km as the cable designer builds it. Drums as their makers print them; lengths are estimates within a few per cent of the cable makers' own tables: whole layers, wound diameter 1.05 × OD, 50 mm freeboard under the flange rim.

LengthDrum size (its makers)LayersGross weight
500 mKTG 12 (1250 mm flange), wood KTG drums (Europe), Bayka, KTG8 of 10519–540 kg
1,000 mKTG 16 (1600 mm flange), wood KTG drums (Europe), Bayka, KTG10 of 131,026–1,059 kg

Barrel at least 15 × OD = 360 mm for a cable of this kind (Low voltage, multi-core): KTG table, the cable's datasheet wins. A load rating is the drum maker's own.

Other lengths, drums and weights: the cable drum calculator

Load it on a truck: 1000 m on its drum in the loading planner

Laying, sizes and datasheet: LX1AV

LX1AV belongs to the family LV armoured cables: the lowest laying temperature, bending radius, pulling, depth, drum handling and the test after laying, every rule with its sources. Laying and handling guide: LV armoured cables

Selling this cable? Open it in the designer and get a datasheet with your logo (Pro). Open the cable designer · See Pro

Work with LX1AV

Related cables

More NP 665 (Portugal) designations