KYJY is a China (GB / JB/T / MT cable model codes) cable designation: K = Control Cable; YJ = Cross-Linked Polyethylene (XLPE); Y = Polyethylene (PE) Or Polyolefin.
1 coding system recognises this code
Standard, worked reading and related types
Standards behind these values: IEC 60502-1:2004 (edition 2.0): Power cables with extruded insulation and their accessories for rated voltages from 1 kV (Um = 1,2 kV) up to 30 kV (Um = 36 kV) - Part 1: Cables for rated voltages of 1 kV (Um = 1,2 kV) and 3 kV (Um = 3,6 kV); IEC 60228:2023 (edition 4.0): Conductors of insulated cables. How the values are sourced
Worked reading of KYJY 4x1.5 450/750 V:
KYJY: K = Control Cable; YJ = Cross-Linked Polyethylene (XLPE); Y = Polyethylene (PE) Or Polyolefin4x1.5 450/750 V: 4 cores, each copper 1.5 mm²; rated voltage 0.45/0.75 kV
Related cable types: YJY
China (GB / JB/T / MT cable model codes)
| Symbol | Meaning |
|---|---|
K | Control Cable |
YJ | Cross-Linked Polyethylene (XLPE) |
Y | Polyethylene (PE) Or Polyolefin |
How to read a China (GB / JB/T / MT cable model codes) cable code
How to read a China (GB / JB/T / MT cable model codes) cable code
A China (GB / JB/T / MT cable model codes) designation (China) is a row of letter groups, and each group stands for one part of the cable: conductor, insulation, screen, armour, sheath, or the standard it follows. The decoder knows 137 symbols for this system.
What does K mean in a China (GB / JB/T / MT cable model codes) cable code? K means Control Cable.
What does YJ mean in a China (GB / JB/T / MT cable model codes) cable code? YJ means Cross-Linked Polyethylene (XLPE).
What does Y mean in a China (GB / JB/T / MT cable model codes) cable code? Y means Polyethylene (PE) Or Polyolefin.
Fire behaviour (EU CPR)
PE sheath (Y).
Typically targeted, as declared by makers for this kind of construction in the examples this site checked (not the class of this cable):
FcaYMeKrvaslqwd, TKFFcaNA2XS(F)2Y, Waskönig+Walter
Listed as sources, alphabetically by maker. No maker pays to appear here.
A CPR class is declared by the maker in its Declaration of Performance and printed on the sheath (EN 50575 cl 7). This decoder does not assign one. What the CPR classes mean →
Sources: EN 13501-6 draft and FprEN 50575:2014 final draft (drafts, not the published texts); IEC 60332-3-24:2000+A1:2008; EN 13501-3 draft A2.
KYJY as the cable designer builds it, 4x1.5 450/750 V
Overall diameter 8.6 mm, about 100 kg/km. Nominal values from the standard's tables for this size, computed, not a maker's data.
| Layer | Material | Thickness, mm | Over the layer, mm |
|---|---|---|---|
| Insulation | XLPE | 0.60 | 2.6 |
| Filler | PP | 6.2 | |
| Sheath | PE | 1.2 | 8.6 |
KYJY on a drum
The smallest drum that passes every check, for 8.6 mm and about 100 kg/km as the cable designer builds it. Drums as their makers print them; lengths are estimates: whole layers wound nested (each turn in the groove of the layer below), wound diameter 1.05 × OD, 50 mm freeboard under the flange rim. Cable makers' own tables print less, as they count aligned layers.
| Length | Drum size (its makers) | Layers | Gross weight |
|---|---|---|---|
| 500 m | KTG 5 (500 mm flange), plastic KTG drums (Europe), Bayka, KTG | 14 of 15 | 53–54 kg |
| 1,000 m | KTG 7 (710 mm flange), wood KTG drums (Europe), Bayka, KTG | 16 of 16 | 125–128 kg |
Barrel at least 15 × OD = 130 mm for a cable of this kind (Low voltage, multi-core): KTG table, the cable's datasheet wins. A load rating is the drum maker's own. A steel drum whose maker prints none is checked against the DIN 46391-4 guide load instead: 28 kN per m³ of gross winding volume.
Other lengths, drums and weights: the cable drum calculator
Load it on a truck: 1000 m on its drum in the loading planner
Laying, sizes and datasheet: KYJY