JE-LiHCH

JE-LiHCH is a VDE telecom, signal and fibre cables (DIN VDE 0815, 0816, 0813, 0888) cable designation: J = Installation Cable; E = For Industrial Electronics; Li = Stranded Conductor, Flexible (Litzenleiter To VDE 0812); H = Low Smoke Zero Halogen Compound; C = Copper Screen As Braid; H = Low Smoke Zero Halogen Compound.

1 coding system recognises this code

VDE telecom, signal and fibre cables (DIN VDE 0815, 0816, 0813, 0888)

SymbolMeaning
JInstallation Cable
EFor Industrial Electronics
LiStranded Conductor, Flexible (Litzenleiter To VDE 0812)
HLow Smoke Zero Halogen Compound
CCopper Screen As Braid
HLow Smoke Zero Halogen Compound

How to read a VDE telecom, signal and fibre cables (DIN VDE 0815, 0816, 0813, 0888) cable code

Fire behaviour (EU CPR)

A CPR class is declared by the maker in its Declaration of Performance and printed on the sheath (EN 50575 cl 7). This decoder does not assign one. What the CPR classes mean →

Sources: EN 13501-6 draft and FprEN 50575:2014 final draft (drafts, not the published texts); IEC 60332-3-24:2000+A1:2008; EN 13501-3 draft A2.

JE-LiHCH as the cable designer builds it, JE-LiHCH

Overall diameter 7.4 mm, about 80 kg/km. Nominal values from the standard's tables for this size, computed, not a maker's data.

LayerMaterialThickness, mmOver the layer, mm
InsulationHalogen-free (LSZH)0.451.8
Separation tapePolyester0.054.4
Braid (copper wires)Copper0.204.8
SheathHalogen-free (LSZH)1.37.4

JE-LiHCH on a drum

The smallest drum that passes every check, for 7.4 mm and about 80 kg/km as the cable designer builds it. Drums as their makers print them; lengths are estimates within a few per cent of the cable makers' own tables: whole layers, wound diameter 1.05 × OD, 50 mm freeboard under the flange rim.

LengthDrum size (its makers)LayersGross weight
500 mKTG 5 (500 mm flange), plastic KTG drums (Europe), Bayka, KTG13 of 1543–44 kg
1,000 mKTG 7 (710 mm flange), wood KTG drums (Europe), Bayka, KTG14 of 16105–108 kg

Barrel at least 20 × OD = 149 mm for a cable of this kind (Telecom, data and control cable): KTG table, the cable's datasheet wins. A load rating is the drum maker's own.

Other lengths, drums and weights: the cable drum calculator

Load it on a truck: 1000 m on its drum in the loading planner

Laying, sizes and datasheet: JE-LiHCH

JE-LiHCH belongs to the family Control and instrument cables: the lowest laying temperature, bending radius, pulling, depth, drum handling and the test after laying, every rule with its sources. Laying and handling guide: Control and instrument cables

Selling this cable? Open it in the designer and get a datasheet with your logo (Pro). Open the cable designer · See Pro

Work with JE-LiHCH

Related cables

More VDE telecom, signal and fibre cables (DIN VDE 0815, 0816, 0813, 0888) designations