IS 1554-2

IS 1554-2 is a BIS type names (India) cable designation: SC = Semiconducting Layer And Screen Over Each Core; PVC = PVC insulation; CU = Copper Tape Screen; ARM = Armour; PVC = PVC outer sheath; IS 1554-2 = HT PVC: PVC-insulated heavy duty cable for 3.3 kV up to 11 kV; at 6.35/11 kV each core with a conductor screen, PVC insulation, an insulation screen and a metallic screen; PVC fillers and inner sheath, steel round wire or formed wire (strip) armour, PVC outer sheath. 1.9/3.3, 3.3/3.3, 3.8/6.6 and 6.35/11 kV; 70 C normal, 160 C short circuit. IS 1554 (Part 2):1988 (reaffirmed 2020).

1 coding system recognises this code

BIS type names (India)

SymbolMeaning
SCSemiconducting Layer And Screen Over Each Core
PVCPVC insulation
CUCopper Tape Screen
ARMArmour
PVCPVC outer sheath
IS 1554-2HT PVC: PVC-insulated heavy duty cable for 3.3 kV up to 11 kV; at 6.35/11 kV each core with a conductor screen, PVC insulation, an insulation screen and a metallic screen; PVC fillers and inner sheath, steel round wire or formed wire (strip) armour, PVC outer sheath. 1.9/3.3, 3.3/3.3, 3.8/6.6 and 6.35/11 kV; 70 C normal, 160 C short circuit. IS 1554 (Part 2):1988 (reaffirmed 2020)

Fire behaviour (EU CPR)

A CPR class is declared by the maker in its Declaration of Performance and printed on the sheath (EN 50575 cl 7). This decoder does not assign one. What the CPR classes mean →

Sources: EN 13501-6 draft and FprEN 50575:2014 final draft (drafts, not the published texts); IEC 60332-3-24:2000+A1:2008; EN 13501-3 draft A2.

IS 1554-2 as the cable designer builds it, 3x185 6.35/11 kV

Overall diameter 72.6 mm, about 12,300 kg/km. Nominal values from the standard's tables for this size, computed, not a maker's data.

LayerMaterialThickness, mmOver the layer, mm
Conductor screen (semicon)Semiconducting0.6017.3
InsulationPVC4.225.7
Insulation screen (semicon)Semiconducting0.8027.3
Tape screenCopper0.2027.7
FillerPP59.6
Inner covering / beddingPVC0.7061.0
Wire armourSteel61 × 3.1567.3
SheathPVC2.772.6

IS 1554-2 on a drum

The smallest drum that passes every check, for 72.6 mm and about 12,300 kg/km as the cable designer builds it. Drums as their makers print them; lengths are estimates within a few per cent of the cable makers' own tables: whole layers, wound diameter 1.05 × OD, 76 mm freeboard under the flange rim.

LengthDrum size (its makers)LayersGross weight
500 mKTG 28 (2800 mm flange), wood KTG drums (Europe), Bayka, KTG5 of 57,325–7,390 kg
1,000 mNo single drum in KTG drums (Europe) takes it: the drum calculator splits it over several.

Barrel at least 20 × OD = 1,453 mm for a cable of this kind (Medium voltage, multi-core): KTG table, the cable's datasheet wins. A load rating is the drum maker's own.

Other lengths, drums and weights: the cable drum calculator

Load it on a truck: 1000 m on its drum in the loading planner

Laying, sizes and datasheet: IS 1554-2

IS 1554-2 belongs to the family Medium voltage cables: the lowest laying temperature, bending radius, pulling, depth, drum handling and the test after laying, every rule with its sources. Laying and handling guide: Medium voltage cables

Terms on this page: conductor screen · insulation screen · metallic screen · oversheath (outer sheath)

Selling this cable? Open it in the designer and get a datasheet with your logo (Pro). Open the cable designer · See Pro

Work with IS 1554-2

Related cables