HT XLPE

HT XLPE is a BIS type names (India) cable designation: HT = High tension (HT) XLPE cable of IS 7098-2, for 3.3 kV up to 33 kV, each core screened; SC = Semiconducting Layer And Screen Over Each Core; XLPE = Cross-linked polyethylene (XLPE) insulation; CU = Copper Tape Screen; ARM = Armour; PVC = PVC outer sheath; HT XLPE = HT XLPE: XLPE-insulated cable for 3.3 kV up to 33 kV, each core with a conductor screen, XLPE insulation, an insulation screen and copper tape; PVC fillers and inner sheath, steel round wire or flat strip armour, PVC outer sheath. Earthed 1.9/3.3, 3.8/6.6, 6.35/11, 12.7/22, 19/33 kV, unearthed 3.3/3.3 and 11/11 kV; 90 C normal, 250 C short circuit (BIS catalogue); RR Kabel sells 6.35/11 kV (E). IS 7098-2:2011.

2 coding systems recognise this code

BIS type names (India)

SymbolMeaning
HTHigh tension (HT) XLPE cable of IS 7098-2, for 3.3 kV up to 33 kV, each core screened
SCSemiconducting Layer And Screen Over Each Core
XLPECross-linked polyethylene (XLPE) insulation
CUCopper Tape Screen
ARMArmour
PVCPVC outer sheath
HT XLPEHT XLPE: XLPE-insulated cable for 3.3 kV up to 33 kV, each core with a conductor screen, XLPE insulation, an insulation screen and copper tape; PVC fillers and inner sheath, steel round wire or flat strip armour, PVC outer sheath. Earthed 1.9/3.3, 3.8/6.6, 6.35/11, 12.7/22, 19/33 kV, unearthed 3.3/3.3 and 11/11 kV; 90 C normal, 250 C short circuit (BIS catalogue); RR Kabel sells 6.35/11 kV (E). IS 7098-2:2011

China (GB / JB/T / MT cable model codes)

SymbolMeaning
HCommunication Cable
TCopper Conductor
XNatural Or Styrene-Butadiene Rubber
LAluminium Conductor
PCopper Screen As Braid
ELow Smoke Zero Halogen Compound

How to read a China (GB / JB/T / MT cable model codes) cable code

Fire behaviour (EU CPR)

A CPR class is declared by the maker in its Declaration of Performance and printed on the sheath (EN 50575 cl 7). This decoder does not assign one. What the CPR classes mean →

Sources: EN 13501-6 draft and FprEN 50575:2014 final draft (drafts, not the published texts); IEC 60332-3-24:2000+A1:2008; EN 13501-3 draft A2.

HT XLPE as the cable designer builds it, 3x185 6.35/11 kV

Overall diameter 69.7 mm, about 11,430 kg/km. Nominal values from the standard's tables for this size, computed, not a maker's data.

LayerMaterialThickness, mmOver the layer, mm
Conductor screen (semicon)Semiconducting0.6017.3
InsulationXLPE3.624.5
Insulation screen (semicon)Semiconducting0.8026.1
Tape screenCopper0.2026.5
FillerPP57.0
Inner covering / beddingPVC0.7058.4
Wire armourSteel59 × 3.1564.7
SheathPVC2.569.7

HT XLPE on a drum

The smallest drum that passes every check, for 69.7 mm and about 11,430 kg/km as the cable designer builds it. Drums as their makers print them; lengths are estimates within a few per cent of the cable makers' own tables: whole layers, wound diameter 1.05 × OD, 73 mm freeboard under the flange rim.

LengthDrum size (its makers)LayersGross weight
500 mKTG 28 (2800 mm flange), wood KTG drums (Europe), Bayka, KTG5 of 56,890–6,955 kg
1,000 mNo single drum in KTG drums (Europe) takes it: the drum calculator splits it over several.

Barrel at least 20 × OD = 1,395 mm for a cable of this kind (Medium voltage, multi-core): KTG table, the cable's datasheet wins. A load rating is the drum maker's own.

Other lengths, drums and weights: the cable drum calculator

Load it on a truck: 1000 m on its drum in the loading planner

Laying, sizes and datasheet: HT XLPE

HT XLPE belongs to the family Medium voltage cables: the lowest laying temperature, bending radius, pulling, depth, drum handling and the test after laying, every rule with its sources. Laying and handling guide: Medium voltage cables

Terms on this page: conductor screen · insulation screen · oversheath (outer sheath)