H07Z-K
H07Z-K is a HAR: HD 361 harmonised designation (CENELEC) cable designation: H = Harmonized Standard; 07 = 450/750 V; Z = Cross-Linked Polyolefin Compound, Low Smoke And Non-Corrosive Gases (Halogen-Free); -K = Fine-Wired For Fixed Installations-Class 5.
1 coding system recognises this code
Standard, worked reading and related types
Standards behind these values: IEC 60228:2023 (edition 4.0): Conductors of insulated cables. How the values are sourced
Worked reading of H07Z-K 1x1.5 450/750 V:
H07Z-K: H = Harmonized Standard; 07 = 450/750 V; Z = Cross-Linked Polyolefin Compound, Low Smoke And Non-Corrosive Gases (Halogen-Free); -K = Fine-Wired For Fixed Installations-Class 51x1.5 450/750 V: one core, copper 1.5 mm²; rated voltage 0.45/0.75 kV
HAR: HD 361 harmonised designation (CENELEC)
| Symbol | Meaning |
|---|---|
H | Harmonized Standard |
07 | 450/750 V |
Z | Cross-Linked Polyolefin Compound, Low Smoke And Non-Corrosive Gases (Halogen-Free) |
-K | Fine-Wired For Fixed Installations-Class 5 |
How to read a HAR: HD 361 harmonised designation (CENELEC) cable code
How to read a HAR: HD 361 harmonised designation (CENELEC) cable code
A HAR: HD 361 harmonised designation (CENELEC) designation (Europe (CENELEC)) is a row of letter groups, and each group stands for one part of the cable: conductor, insulation, screen, armour, sheath, or the standard it follows. The decoder knows 129 symbols for this system.
What does H mean in a HAR: HD 361 harmonised designation (CENELEC) cable code? H means Harmonized Standard; or Flat Divisible (Separable) Cable Or Cord.
What does Z mean in a HAR: HD 361 harmonised designation (CENELEC) cable code? Z means Cross-Linked Polyolefin Compound, Low Smoke And Non-Corrosive Gases (Halogen-Free).
What does -K mean in a HAR: HD 361 harmonised designation (CENELEC) cable code? -K means Fine-Wired For Fixed Installations-Class 5.
Fire behaviour (EU CPR)
Halogen-free compound (Z). Under the CPR this shows in the additional classes: acidity a1 to a3 (EN 60754-2) and smoke s1 to s3 (EN 50399; s1a and s1b add the 3 m cube test EN 61034-2). The main class, Aca to Fca, depends on the whole construction.
Typically targeted, as declared by makers for this kind of construction in the examples this site checked (not the class of this cable):
B2ca-s1a,d0,a11-CXKH-R-J, Kablo VrchlabíCca-s1b,d1,a1FG16(O)M16, Nexans (La Triveneta Cavi)B2ca-s1a,d1,a1FG18(O)M16, Nexans (La Triveneta Cavi)DcaFXQJ, Nexans NorwayCca-s1b,d1,a1H07Z1-K, Nexans SpainB2ca-s1,d2,a1AXQJ-RMF, Prysmian Sweden (12/20 kV)B2ca-s1a,d1,a1RZ1-K (AS), Top CableCca-s1b,d1,a1RZ1FZ1-K (AS), Top Cable
Listed as sources, alphabetically by maker. No maker pays to appear here.
A CPR class is declared by the maker in its Declaration of Performance and printed on the sheath (EN 50575 cl 7). This decoder does not assign one. What the CPR classes mean →
Sources: EN 13501-6 draft and FprEN 50575:2014 final draft (drafts, not the published texts); IEC 60332-3-24:2000+A1:2008; EN 13501-3 draft A2.
H07Z-K: equivalents in other countries
Shown for 1x1.5 450/750 V. Each country's rules are applied to this build, keeping the conductor, section, cores, voltage, screen, armour and sheath.
| Country | Standard | Name in that country | Verdict | Differences |
|---|---|---|---|---|
| Europe | EN 50525-3-31 | H07Z1-K 1x1,5 450/750 V | Equivalent | every value the same |
Nominal values computed by each standard's rules, not manufacturer data. This is not a statement that two cables are interchangeable: the buyer's specification and the maker's type test decide.
H07Z-K as the cable designer builds it, 1x1.5 450/750 V
Overall diameter 2.9 mm, about 20 kg/km. Nominal values from the standard's tables for this size, computed, not a maker's data.
| Layer | Material | Thickness, mm | Over the layer, mm |
|---|---|---|---|
| Insulation | Halogen-free (LSZH) | 0.70 | 2.9 |
H07Z-K on a drum
The smallest drum that passes every check, for 2.9 mm and about 20 kg/km as the cable designer builds it. Drums as their makers print them; lengths are estimates: whole layers wound nested (each turn in the groove of the layer below), wound diameter 1.05 × OD, 50 mm freeboard under the flange rim. Cable makers' own tables print less, as they count aligned layers.
| Length | Drum size (its makers) | Layers | Gross weight |
|---|---|---|---|
| 500 m | KTG 3 (390 mm flange), plastic KTG drums (Europe), KTG | 9 of 30 | 12 kg |
| 1,000 m | KTG 3 (390 mm flange), plastic KTG drums (Europe), KTG | 15 of 30 | 22 kg |
Barrel at least 12 × OD = 35 mm for a cable of this kind (Flexible cable (class 5 or 6 conductor)): KTG table, the cable's datasheet wins. A load rating is the drum maker's own. A steel drum whose maker prints none is checked against the DIN 46391-4 guide load instead: 28 kN per m³ of gross winding volume.
Other lengths, drums and weights: the cable drum calculator
Load it on a truck: 1000 m on its drum in the loading planner
Laying, sizes and datasheet: H07Z-K
Selling this cable? Open it in the designer and get a datasheet with your logo (Pro). Open the cable designer · See Pro
Work with H07Z-K
Who makes or stocks this cable?
Makers and stockists of this cable family appear here as sponsors for your region, each marked "Sponsored"; a listing never changes what this page says about the cable.
Related cables
More HAR: HD 361 harmonised designation (CENELEC) designations