FG7OR

FG7OR is a CEI-UNEL 35011 (Italy) cable designation: F = Fine-Wired In Flexible Cables-Class 5; G7 = Hard Grade Ethylene-Propylene Rubber (HEPR); O = Round Cable Laid Up Cores; R = PVC Compound (TI1/TI2 Quality, 70 °C).

1 coding system recognises this code

Standard, worked reading and related types

Standards behind these values: IEC 60502-1:2004 (edition 2.0): Power cables with extruded insulation and their accessories for rated voltages from 1 kV (Um = 1,2 kV) up to 30 kV (Um = 36 kV) - Part 1: Cables for rated voltages of 1 kV (Um = 1,2 kV) and 3 kV (Um = 3,6 kV); IEC 60228:2023 (edition 4.0): Conductors of insulated cables. How the values are sourced

Worked reading of FG7OR 1x16 0.6/1 kV:

  • FG7OR: F = Fine-Wired In Flexible Cables-Class 5; G7 = Hard Grade Ethylene-Propylene Rubber (HEPR); O = Round Cable Laid Up Cores; R = PVC Compound (TI1/TI2 Quality, 70 °C)
  • 1x16 0.6/1 kV: one core, copper 16 mm²; rated voltage 0.6/1 kV

CEI-UNEL 35011 (Italy)

SymbolMeaning
FFine-Wired In Flexible Cables-Class 5
G7Hard Grade Ethylene-Propylene Rubber (HEPR)
ORound Cable Laid Up Cores
RPVC Compound (TI1/TI2 Quality, 70 °C)

How to read a CEI-UNEL 35011 (Italy) cable code

How to read a CEI-UNEL 35011 (Italy) cable code

A CEI-UNEL 35011 (Italy) designation (Italy) is a row of letter groups, and each group stands for one part of the cable: conductor, insulation, screen, armour, sheath, or the standard it follows. The decoder knows 85 symbols for this system.

What does F mean in a CEI-UNEL 35011 (Italy) cable code? F means Fine-Wired In Flexible Cables-Class 5; or Round Steel Wire.

What does G7 mean in a CEI-UNEL 35011 (Italy) cable code? G7 means Hard Grade Ethylene-Propylene Rubber (HEPR).

What does O mean in a CEI-UNEL 35011 (Italy) cable code? O means Round Cable Laid Up Cores.

What does R mean in a CEI-UNEL 35011 (Italy) cable code? R means Multi-Wire, Round-Section, Class 2; or PVC Compound (TI1/TI2 Quality, 70 °C).

Fire behaviour (EU CPR)

A CPR class is declared by the maker in its Declaration of Performance and printed on the sheath (EN 50575 cl 7). This decoder does not assign one. What the CPR classes mean →

Sources: EN 13501-6 draft and FprEN 50575:2014 final draft (drafts, not the published texts); IEC 60332-3-24:2000+A1:2008; EN 13501-3 draft A2.

FG7OR as the cable designer builds it, 1x16 0.6/1 kV

Overall diameter 9.3 mm, about 210 kg/km. Nominal values from the standard's tables for this size, computed, not a maker's data.

LayerMaterialThickness, mmOver the layer, mm
InsulationHEPR0.706.5
SheathPVC1.49.3

FG7OR on a drum

The smallest drum that passes every check, for 9.3 mm and about 210 kg/km as the cable designer builds it. Drums as their makers print them; lengths are estimates: whole layers wound nested (each turn in the groove of the layer below), wound diameter 1.05 × OD, 50 mm freeboard under the flange rim. Cable makers' own tables print less, as they count aligned layers.

LengthDrum size (its makers)LayersGross weight
500 mKTG 6 (600 mm flange), plywood KTG drums (Europe), Bayka12 of 14112 kg
1,000 mKTG 8 (800 mm flange), wood KTG drums (Europe), Bayka, KTG16 of 17241–245 kg

Barrel at least 12 × OD = 112 mm for a cable of this kind (Flexible cable (class 5 or 6 conductor)): KTG table, the cable's datasheet wins. A load rating is the drum maker's own. A steel drum whose maker prints none is checked against the DIN 46391-4 guide load instead: 28 kN per m³ of gross winding volume.

Other lengths, drums and weights: the cable drum calculator

Load it on a truck: 1000 m on its drum in the loading planner

Laying, sizes and datasheet: FG7OR

Current rating and voltage drop: One circuit, C: cable on a wall, 30 °C air: about 96 A. At that current over 100 m, three-phase 400 V, cos φ 0.9: a voltage drop of about 5.9 %. Sources: IEC 60364-5-52:2009, Table B.52.5, p. 44; IEC 60228:2023 Table 5, p. 14; IEC 60228:2023 Annex B, p. 18; IEC 60364-5-52:2009 (ed. 3.0) Annex G (informative), pp. 74 to 75 (read in the standard text) Cable size calculator: smallest section for a load, every factor shown · Voltage drop calculator: IEC 60364-5-52 method and limits

Selling this cable? Open it in the designer and get a datasheet with your logo (Pro). Open the cable designer · See Pro

Work with FG7OR

Who makes or stocks this cable?

Makers and stockists of this cable family appear here as sponsors for your region, each marked "Sponsored"; a listing never changes what this page says about the cable.