CVT

CVT is a JIS type names (Japan) cable designation: C = C: cross-linked polyethylene (XLPE) insulation; V = V: PVC (vinyl) sheath; T = T: triplex, three single-core cables twisted together; CVT = CVT: triplex CV, three single-core XLPE / PVC cables twisted together. 600 V, 90 C (SFCC p.12); also 3300 V and 6600 V (SFCC p.16, p.20), 6/10 kV (Taihan). JIS C 3605 (600 V); JCS 4516 (3300 V); JIS C 3606 (6600 V); KS C IEC 60502-2 (Korea, 6/10 kV).

4 coding systems recognise this code

JIS type names (Japan)

SymbolMeaning
CC: cross-linked polyethylene (XLPE) insulation
VV: PVC (vinyl) sheath
TT: triplex, three single-core cables twisted together
CVTCVT: triplex CV, three single-core XLPE / PVC cables twisted together. 600 V, 90 C (SFCC p.12); also 3300 V and 6600 V (SFCC p.16, p.20), 6/10 kV (Taihan). JIS C 3605 (600 V); JCS 4516 (3300 V); JIS C 3606 (6600 V); KS C IEC 60502-2 (Korea, 6/10 kV)

China (GB / JB/T / MT cable model codes)

SymbolMeaning
CShipboard or Marine Cable
VPolyvinyl Chloride (PVC)
TCopper Conductor

How to read a China (GB / JB/T / MT cable model codes) cable code

NBN (Belgian national cable names, ...B types)

SymbolMeaning
CRubber (Caoutchouc), Natural Or Synthetic, Insulation Or Sheath
VPolyvinyl Chloride (PVC)
TTelephone Cable

How to read a NBN (Belgian national cable names, ...B types) cable code

NEN 3207 / KEMA (Netherlands)

SymbolMeaning
CChloroprene Rubber
VPolyvinyl Chloride (PVC)
TFibrous (Textile) Covering

How to read a NEN 3207 / KEMA (Netherlands) cable code

Fire behaviour (EU CPR)

A CPR class is declared by the maker in its Declaration of Performance and printed on the sheath (EN 50575 cl 7). This decoder does not assign one. What the CPR classes mean →

Sources: EN 13501-6 draft and FprEN 50575:2014 final draft (drafts, not the published texts); IEC 60332-3-24:2000+A1:2008; EN 13501-3 draft A2.

CVT as the cable designer builds it, 1x16 0.6/1 kV

Overall diameter 9.1 mm, about 210 kg/km. Nominal values from the standard's tables for this size, computed, not a maker's data.

LayerMaterialThickness, mmOver the layer, mm
InsulationXLPE0.706.3
SheathPVC1.49.1

CVT on a drum

The smallest drum that passes every check, for 9.1 mm and about 210 kg/km as the cable designer builds it. Drums as their makers print them; lengths are estimates within a few per cent of the cable makers' own tables: whole layers, wound diameter 1.05 × OD, 50 mm freeboard under the flange rim.

LengthDrum size (its makers)LayersGross weight
500 mKTG 6 (600 mm flange), plywood KTG drums (Europe), Bayka11 of 13112 kg
1,000 mKTG 8 (800 mm flange), wood KTG drums (Europe), Bayka, KTG15 of 15241–245 kg

Barrel at least 20 × OD = 182 mm for a cable of this kind (Low voltage, single core): KTG table, the cable's datasheet wins. A load rating is the drum maker's own.

Other lengths, drums and weights: the cable drum calculator

Load it on a truck: 1000 m on its drum in the loading planner

Laying, sizes and datasheet: CVT

CVT belongs to the family LV XLPE power cables: the lowest laying temperature, bending radius, pulling, depth, drum handling and the test after laying, every rule with its sources. Laying and handling guide: LV XLPE power cables

Selling this cable? Open it in the designer and get a datasheet with your logo (Pro). Open the cable designer · See Pro

Work with CVT

Related cables

More JIS type names (Japan) designations