BK
BK is a SS 424 17 01 (Sweden) cable designation: B = Low Smoke, Zero Halogen Thermoplastic Polyolefin; K = Polyvinyl Chloride (PVC).
3 coding systems recognise this code
Standard, worked reading and related types
Standards behind these values: IEC 60502-1:2004 (edition 2.0): Power cables with extruded insulation and their accessories for rated voltages from 1 kV (Um = 1,2 kV) up to 30 kV (Um = 36 kV) - Part 1: Cables for rated voltages of 1 kV (Um = 1,2 kV) and 3 kV (Um = 3,6 kV); IEC 60228:2023 (edition 4.0): Conductors of insulated cables. How the values are sourced
Worked reading of BK 3x95 0.6/1 kV:
BK: B = Low Smoke, Zero Halogen Thermoplastic Polyolefin; K = Polyvinyl Chloride (PVC)3x95 0.6/1 kV: 3 cores, each copper 95 mm²; rated voltage 0.6/1 kV
SS 424 17 01 (Sweden)
| Symbol | Meaning |
|---|---|
B | Low Smoke, Zero Halogen Thermoplastic Polyolefin |
K | Polyvinyl Chloride (PVC) |
TS 621 / TSE (Turkey)
| Symbol | Meaning |
|---|---|
B | Cable Resistant To Heavy Mechanical Load For Moving Installation |
K | Corrosion Resistant |
Norwegian type designation (NEK 606 offshore and Norwegian land cables)
| Symbol | Meaning |
|---|---|
B | Fire Resistant Tape + Insulation (Halogen-Free) |
K | Lead |
How to read a Norwegian type designation (NEK 606 offshore and Norwegian land cables) cable code
How to read a SS 424 17 01 (Sweden) cable code
A SS 424 17 01 (Sweden) designation (Sweden) is a row of letter groups, and each group stands for one part of the cable: conductor, insulation, screen, armour, sheath, or the standard it follows. The decoder knows 90 symbols for this system.
What does B mean in a SS 424 17 01 (Sweden) cable code? B means Low Smoke, Zero Halogen Thermoplastic Polyolefin; or Lead Sheath; Or Flame-Retardant Halogen-Free Thermoplastic Polyolefin Sheath (Used Until 2005); or Connecting (Hook-Up) Wire; Vehicle Cable; Lead Sheath; or Aluminium Alloy Conductor.
What does K mean in a SS 424 17 01 (Sweden) cable code? K means Polyvinyl Chloride (PVC).
Fire behaviour (EU CPR)
Halogen-free compound (B). Under the CPR this shows in the additional classes: acidity a1 to a3 (EN 60754-2) and smoke s1 to s3 (EN 50399; s1a and s1b add the 3 m cube test EN 61034-2). The main class, Aca to Fca, depends on the whole construction.
Typically targeted, as declared by makers for this kind of construction in the examples this site checked (not the class of this cable):
B2ca-s1a,d0,a11-CXKH-R-J, Kablo VrchlabíCca-s1b,d1,a1FG16(O)M16, Nexans (La Triveneta Cavi)B2ca-s1a,d1,a1FG18(O)M16, Nexans (La Triveneta Cavi)DcaFXQJ, Nexans NorwayCca-s1b,d1,a1H07Z1-K, Nexans SpainB2ca-s1,d2,a1AXQJ-RMF, Prysmian Sweden (12/20 kV)B2ca-s1a,d1,a1RZ1-K (AS), Top CableCca-s1b,d1,a1RZ1FZ1-K (AS), Top Cable
Listed as sources, alphabetically by maker. No maker pays to appear here.
A CPR class is declared by the maker in its Declaration of Performance and printed on the sheath (EN 50575 cl 7). This decoder does not assign one. What the CPR classes mean →
Sources: EN 13501-6 draft and FprEN 50575:2014 final draft (drafts, not the published texts); IEC 60332-3-24:2000+A1:2008; EN 13501-3 draft A2.
BK as the cable designer builds it, 3x95 0.6/1 kV
Overall diameter 35.9 mm, about 3,420 kg/km. Nominal values from the standard's tables for this size, computed, not a maker's data.
| Layer | Material | Thickness, mm | Over the layer, mm |
|---|---|---|---|
| Insulation | Halogen-free (LSZH) | 1.1 | 13.7 |
| Filler | PP | 29.5 | |
| Inner covering / bedding | PVC | 1.2 | 31.9 |
| Sheath | PVC | 2.0 | 35.9 |
BK on a drum
The smallest drum that passes every check, for 35.9 mm and about 3,420 kg/km as the cable designer builds it. Drums as their makers print them; lengths are estimates: whole layers wound nested (each turn in the groove of the layer below), wound diameter 1.05 × OD, 50 mm freeboard under the flange rim. Cable makers' own tables print less, as they count aligned layers.
| Length | Drum size (its makers) | Layers | Gross weight |
|---|---|---|---|
| 500 m | KTG 16 (1600 mm flange), wood KTG drums (Europe), Bayka, KTG | 7 of 10 | 1,986–2,019 kg |
| 1,000 m | KTG 20 (2000 mm flange), wood KTG drums (Europe), Bayka, KTG | 8 of 9 | 3,899–4,020 kg |
Barrel at least 15 × OD = 539 mm for a cable of this kind (Low voltage, multi-core): KTG table, the cable's datasheet wins. A load rating is the drum maker's own. A steel drum whose maker prints none is checked against the DIN 46391-4 guide load instead: 28 kN per m³ of gross winding volume.
Other lengths, drums and weights: the cable drum calculator
Load it on a truck: 1000 m on its drum in the loading planner
Laying, sizes and datasheet: BK