BFDU

BFDU is a Norwegian type designation (NEK 606 offshore and Norwegian land cables) cable designation: B = Fire Resistant Tape + Insulation (Halogen-Free); F = Bedding Or Taping (Halogen-Free); D = Oil Filled Cable Reinforcement (Longitudinal / Transverse); U = Halogen-Free Thermoset Compound (EMA or EVA; SHF2 class).

1 coding system recognises this code

Standard, worked reading and related types

Worked reading of BFDU:

  • BFDU: B = Fire Resistant Tape + Insulation (Halogen-Free); F = Bedding Or Taping (Halogen-Free); D = Oil Filled Cable Reinforcement (Longitudinal / Transverse); U = Halogen-Free Thermoset Compound (EMA or EVA; SHF2 class)

Related cable types: BFD

Norwegian type designation (NEK 606 offshore and Norwegian land cables)

SymbolMeaning
BFire Resistant Tape + Insulation (Halogen-Free)
FBedding Or Taping (Halogen-Free)
DOil Filled Cable Reinforcement (Longitudinal / Transverse)
UHalogen-Free Thermoset Compound (EMA or EVA; SHF2 class)

How to read a Norwegian type designation (NEK 606 offshore and Norwegian land cables) cable code

How to read a Norwegian type designation (NEK 606 offshore and Norwegian land cables) cable code

A Norwegian type designation (NEK 606 offshore and Norwegian land cables) designation (Norway) is a row of letter groups, and each group stands for one part of the cable: conductor, insulation, screen, armour, sheath, or the standard it follows. The decoder knows 95 symbols for this system.

What does B mean in a Norwegian type designation (NEK 606 offshore and Norwegian land cables) cable code? B means Fire Resistant Tape + Insulation (Halogen-Free); or Corrugated Aluminium (optionally with corrosion protection); or Steel Tapes, 2 Off; or Hydrocarbon Resistant Sheath.

What does F mean in a Norwegian type designation (NEK 606 offshore and Norwegian land cables) cable code? F means PE Or PP + Filling Compound; or Bedding Or Taping (Halogen-Free); or Flat Steel Wire Armour; or Semi-Conducting PE.

What does D mean in a Norwegian type designation (NEK 606 offshore and Norwegian land cables) cable code? D means Impregnated Paper Drip Free; or Aluminium + Plastics; or Oil Filled Cable Reinforcement (Longitudinal / Transverse).

What does U mean in a Norwegian type designation (NEK 606 offshore and Norwegian land cables) cable code? U means Halogen-Free Thermoset Compound (EMA or EVA); or Halogen-Free Thermoset Compound (EMA or EVA; SHF2 class); or Round Aluminium Wire.

Fire behaviour (EU CPR)

  • Halogen-free compound (B, F, U). Under the CPR this shows in the additional classes: acidity a1 to a3 (EN 60754-2) and smoke s1 to s3 (EN 50399; s1a and s1b add the 3 m cube test EN 61034-2). The main class, Aca to Fca, depends on the whole construction.

    Typically targeted, as declared by makers for this kind of construction in the examples this site checked (not the class of this cable):

    Listed as sources, alphabetically by maker. No maker pays to appear here.

  • Fire resistant (B): the circuit keeps working in a fire. That is circuit integrity, classified apart from reaction to fire (EN 13501-3: P and PH classes, 15 to 120 min). It gives no reaction-to-fire class; that one is declared on its own.

A CPR class is declared by the maker in its Declaration of Performance and printed on the sheath (EN 50575 cl 7). This decoder does not assign one. What the CPR classes mean →

Sources: EN 13501-6 draft and FprEN 50575:2014 final draft (drafts, not the published texts); IEC 60332-3-24:2000+A1:2008; EN 13501-3 draft A2.

Not equivalent, because

IEC 60331 ≠ BS 6387 (C, W, Z) ≠ BS 8491 ≠ EN 50200 (PH) ≠ DIN 4102-12 (E30, E60, E90) ≠ UL 2196

Not equivalent, because Flame or furnace, temperature, mechanical shock, water and what is tested (a cable alone, or a cable with its supports) all differ: a time or class from one test says nothing about another.

IEC 60331

  • Parts 1 and 2: a flame of at least 830 °C with mechanical shock; part 1 for cables over 20 mm, part 2 up to 20 mm; up to 0.6/1 kV. Sources: IEC 60331-1:2009 and IEC 60331-2:2009 (edition 1.0), cl. 1 p. 7, 7.4 p. 19, 8.1 and 8.2 p. 20, Annex A p. 22 (the 2018 edition is not held) (read in the standard)
  • Parts 11 and 21: fire alone, at least 750 °C. Sources: IEC 60331-11:1999+A1:2009 (edition 1.1), 5.2 p. 7, Annex A p. 13; IEC 60331-21:1999, cl. 7 and 8, pp. 13 to 15 (read in the standard)
  • Pass: the circuit keeps working for the stated time. Sources: IEC 60331-1:2009 and IEC 60331-2:2009 (edition 1.0), cl. 1 p. 7, 7.4 p. 19, 8.1 and 8.2 p. 20, Annex A p. 22 (the 2018 edition is not held) (read in the standard)

BS 6387 (C, W, Z)

  • C: 950 °C for 3 h. W: 650 °C for 15 min, then 15 min with water. Z: 950 °C with a shock every 30 s for 15 min. CWZ: all three passed. Sources: BS 6387:2013, cl. 4, 6, 7, 8 (read in the standard)
  • Cables up to 600/1000 V and 20 mm diameter. Sources: BS 6387:2013, cl. 4, 6, 7, 8 (read in the standard)

BS 8491

EN 50200 (PH)

  • 830 °C with a shock every 5 min, cables up to 20 mm; Annex E adds a water spray. Sources: BS EN 50200:2015, 6.3 (830 °C, +40 / 0), 8.3 (shock every 5 min), clause 1 (cables up to 20 mm), Annex D (PH classes), Annex E (water spray) (read in the standard)
  • Classes PH15, PH30, PH60, PH90, PH120 (EN 13501-3). Sources: EN 13501-3:2005+A1:2009 with draft A2 (cover September 2013), cl 4.3 p. 7; cl 6.3 p. 9; cl 7.2.4.4, 7.2.5.4 pp. 16-17; cl 7.2.6.2 p. 18 (read in a draft); BS EN 50200:2015, 6.3 (830 °C, +40 / 0), 8.3 (shock every 5 min), clause 1 (cables up to 20 mm), Annex D (PH classes), Annex E (water spray) (read in the standard)

DIN 4102-12 (E30, E60, E90)

  • The cable with its supports in a furnace on the standard temperature curve, at up to 400 V; E30, E60 and E90 hold only for the support system tested. Sources: Datwyler (N)HXCH FE180 E90 datasheet (maker's catalogue)

UL 2196

  • A furnace on the ASTM E119 time-temperature curve (NFPA 262 Annex A names it for UL 2196). Sources: NFPA 262:2023 (NFPA free access), Annex A, A.1.1.1 (read in the standard)
  • Ratings up to 2 h, with a hose stream after the fire. Sources: research: equivalents map F5 (UL 2196 not read) (typical practice)

All the comparisons →

Laying, sizes and datasheet: BFDU