AL RH5Z1 OL

AL RH5Z1 OL is a UNE (Spain: UNE 21123 / UNE 20434) cable designation: RH = Cross-Linked Polyethylene (XLPE); 5 = Aluminium Tape Screen (H5, After RH Or DH: XLPE Or EPR Insulation With The Screen; HD 620 S3 10-E2); Z1 = Low Smoke Zero Halogen Compound; OL = Single Layer Longitudinal Water Barrier; AL = Aluminium Conductor.

1 coding system recognises this code

Standard, worked reading and related types

Worked reading of AL RH5Z1 OL:

  • AL RH5Z1 OL: RH = Cross-Linked Polyethylene (XLPE); 5 = Aluminium Tape Screen (H5, After RH Or DH: XLPE Or EPR Insulation With The Screen; HD 620 S3 10-E2); Z1 = Low Smoke Zero Halogen Compound; OL = Single Layer Longitudinal Water Barrier; AL = Aluminium Conductor

Related cable types: RH5Z1-OL

UNE (Spain: UNE 21123 / UNE 20434)

SymbolMeaning
RHCross-Linked Polyethylene (XLPE)
5Aluminium Tape Screen (H5, After RH Or DH: XLPE Or EPR Insulation With The Screen; HD 620 S3 10-E2)
Z1Low Smoke Zero Halogen Compound
OLSingle Layer Longitudinal Water Barrier
ALAluminium Conductor

How to read a UNE (Spain: UNE 21123 / UNE 20434) cable code

How to read a UNE (Spain: UNE 21123 / UNE 20434) cable code

A UNE (Spain: UNE 21123 / UNE 20434) designation (Spain) is a row of letter groups, and each group stands for one part of the cable: conductor, insulation, screen, armour, sheath, or the standard it follows. The decoder knows 56 symbols for this system.

What does RH mean in a UNE (Spain: UNE 21123 / UNE 20434) cable code? RH means Cross-Linked Polyethylene (XLPE).

What does 5 mean in a UNE (Spain: UNE 21123 / UNE 20434) cable code? 5 means Aluminium Tape Screen (H5, After RH Or DH: XLPE Or EPR Insulation With The Screen; HD 620 S3 10-E2).

What does Z1 mean in a UNE (Spain: UNE 21123 / UNE 20434) cable code? Z1 means Low Smoke Zero Halogen Compound.

What does OL mean in a UNE (Spain: UNE 21123 / UNE 20434) cable code? OL means Single Layer Longitudinal Water Barrier.

What does AL mean in a UNE (Spain: UNE 21123 / UNE 20434) cable code? AL means Aluminium Conductor.

Fire behaviour (EU CPR)

  • Halogen-free compound (Z1). Under the CPR this shows in the additional classes: acidity a1 to a3 (EN 60754-2) and smoke s1 to s3 (EN 50399; s1a and s1b add the 3 m cube test EN 61034-2). The main class, Aca to Fca, depends on the whole construction.

    Typically targeted, as declared by makers for this kind of construction in the examples this site checked (not the class of this cable):

    Listed as sources, alphabetically by maker. No maker pays to appear here.

A CPR class is declared by the maker in its Declaration of Performance and printed on the sheath (EN 50575 cl 7). This decoder does not assign one. What the CPR classes mean →

Sources: EN 13501-6 draft and FprEN 50575:2014 final draft (drafts, not the published texts); IEC 60332-3-24:2000+A1:2008; EN 13501-3 draft A2.