Enterprise · bid comparison
Compare bidders' schedules
Your required schedule and each bidder's offered one, row by row: a compliance matrix, the deviations each bidder declared and the ones it did not, and the age of its type-test reports.
Your files stay on your computer. Everything is read and compared in your browser: no file is uploaded, stored or sent anywhere.
An invented example: the schedule the designer writes for one 12/20 kV cable (NA2XS(F)2Y 1x240/25) and three fictional bidders, Sample bidder A, B and C. Their values, remarks and laboratories are made up to show each kind of finding.
Summary per bidder
Sample bidder A
Sample bidder B
Sample bidder C
Compliance matrix
| No. | Parameter | REQUIRED | Sample bidder A | Sample bidder B | Sample bidder C |
|---|---|---|---|---|---|
| 1 | Designation | NA2XS(F)2Y 1x240/25 12/20 kV | NA2XS(F)2Y 1x240/25 12/20 kVComplies | NA2XS(F)2Y 1x240/25 12/20 kVComplies | NA2XS(F)2Y 1x240/25 12/20 kVComplies |
| 2 | Base standard | IEC 60502-2:2014 | IEC 60502-2Complies · edition not stated | IEC 60502-2:2014Complies | IEC 60502-2:2014Complies |
| 3 | Rated voltage U0/U (Um) | 12/20 kV (Um 24.0 kV) | 12/20 kV (Um 24.0 kV)Complies | 12/20 kV (Um 24.0 kV)Complies | 12/20 kV (Um 24.0 kV)Complies |
| 4 | Number of cores | 1 | 1Complies | 1Complies | 1Complies |
| 5 | Conductor material | Aluminium | AlComplies | AluminiumComplies | AluminiumComplies |
| 6 | Conductor class (IEC 60228) | 2 | 2Complies | 2Complies | 2Complies |
| 7 | Conductor cross-section | 240 mm² | 240 mm²Complies | 240 mm²Complies | 240 mm²Complies |
| 8 | Max. d.c. resistance of the conductor at 20 °C | 0.125 Ω/km | 0.124 Ω/kmComplies | 0.125 Ω/kmComplies | 0.125 Ω/kmComplies |
| 9 | Conductor diameter (approx.) | 18.4 mm | 18.6 mmDeviates · off the nominal valuedeclaredDeviation: compacted conductor, 18.6 mm | 18.4 mmComplies | 18.4 mmComplies |
| 10 | Insulation material | XLPE | XLPEComplies | XLPEComplies | XLPE, water tree retardantComplies |
| 11 | Insulation nominal thickness | 5.50 mm | 5.50 mmComplies | 5.3 mmDeviates · below the minimumnot declared | 5.50 mmComplies |
| 12 | Metal screen: Wire screen | Copper, 25 mm² | Copper, 25 mm²Complies | Copper, 25 mm²Complies | Copper, 16 mm²Deviates · off the nominal valuedeclaredDeviation: 16 mm² copper screen |
| 13 | Direction of lay: Conductor, outer layer of wires | Z (right-hand); inner layers reversed in turn | Z (right-hand); inner layers reversed in turnComplies | Z (right-hand); inner layers reversed in turnComplies | Z (right-hand); inner layers reversed in turnComplies |
| 14 | Direction of lay: Swelling tape (water block) | S (left-hand); pitch 67 mm (as designed) | S (left-hand); pitch 67 mm (as designed)Complies | S (left-hand); pitch 67 mm (as designed)Complies | S (left-hand); pitch 67 mm (as designed)Complies |
| 15 | Direction of lay: Wire screen | Z (right-hand) | Z (right-hand)Complies | Z (right-hand)Complies | Z (right-hand)Complies |
| 16 | Direction of lay: Counter-helix tape | S (left-hand); pitch 165 mm (as designed) | S (left-hand); pitch 165 mm (as designed)Complies | S (left-hand); pitch 165 mm (as designed)Complies | S (left-hand); pitch 165 mm (as designed)Complies |
| 17 | Direction of lay: Swelling tape (water block) | Z (right-hand); pitch 65 mm (as designed) | Z (right-hand); pitch 65 mm (as designed)Complies | Z (right-hand); pitch 65 mm (as designed)Complies | Z (right-hand); pitch 65 mm (as designed)Complies |
| 18 | Outer sheath material | PE | PEComplies | PEComplies | PEComplies |
| 19 | Outer sheath nominal thickness | 2.10 mm | 2.10 mmComplies | as per IEC 60502-2Not a value · "as per" or "complied" instead of a value | 2.10 mmComplies |
| 20 | Overall diameter (approx.) | 39.2 mm | 39.2 mmComplies | 39.2 mmComplies | 39.2 mmComplies |
| 21 | Approximate weight | 1680 kg/km | 1680 kg/kmComplies | 1680 kg/kmComplies | 1680 kg/kmComplies |
| 22 | Short-circuit current of the conductor, 1 s | 23.10 kA | 23.10 kAComplies | 23.10 kAComplies | 22.60 kADeviates · below the minimumnot declared |
| 23 | Short-circuit current of the screen, 1 s | 2.79 kA | 2.79 kAComplies | Missing | 2.79 kAComplies |
| 24 | Minimum bending radius, installation | 15 × D = 588 mm | 15 × D = 588 mmComplies | 15 × D = 588 mmComplies | 20 × D (deviation)Deviates · above the maximumnot declared |
| 25 | CPR class (EN 13501-6) | not declared | FcaComplies · no value required | not declaredComplies · no value required | not declaredComplies · no value required |
| 26 | Type test report (laboratory, date) | Laboratory and date | Example Lab North, 2024-03-12Complies | Example Lab South, 14.06.2016Deviates · report older than the windownot declared | Factory laboratory, 2023-09-05Deviates · laboratory not on the accepted listnot declared |
| Water blocking tape under the screen | not in the required schedule | YesExtra row |
Deviation register
Per bidder: first the cells that deviate without a word in its remarks or deviation column (the hidden deviations: tenders read take an offer that lists none as fully compliant), then what it declared.
Sample bidder A
- Declared Conductor diameter (approx.): required 18.4 mm, offered 18.6 mm (off the nominal value)
Deviation: compacted conductor, 18.6 mm
Sample bidder B
- Not declared Insulation nominal thickness: required 5.50 mm, offered 5.3 mm (below the minimum)
- Not declared Type test report (laboratory, date): required Laboratory and date, offered Example Lab South, 14.06.2016 (report older than the window)
Sample bidder C
- Not declared Short-circuit current of the conductor, 1 s: required 23.10 kA, offered 22.60 kA (below the minimum)
- Not declared Minimum bending radius, installation: required 15 × D = 588 mm, offered 20 × D (deviation) (above the maximum)
Written in the value cell, not in the remarks or deviation column: not taken into account. - Not declared Type test report (laboratory, date): required Laboratory and date, offered Factory laboratory, 2023-09-05 (laboratory not on the accepted list)
- Declared Metal screen: Wire screen: required Copper, 25 mm², offered Copper, 16 mm² (off the nominal value)
Deviation: 16 mm² copper screen
Type-test reports
| Bidder | As stated | Date | Age (years) | Result |
|---|---|---|---|---|
| Sample bidder A | Example Lab North, 2024-03-12 | 2024-03-12 | 2.6 | Complies |
| Sample bidder B | Example Lab South, 14.06.2016 | 2016-06-14 | 10.4 | report older than the window |
| Sample bidder C | Factory laboratory, 2023-09-05 | 2023-09-05 | 3.2 | laboratory not on the accepted list |