AS/NZS (Australia, New Zealand)

Australia, New Zealand · 15 типов · AS/NZS (Australia, New Zealand): как читать названия типов кабелей

TPSTPS: flat building cable, two or three V-90 PVC-insulated copper cores and a green/yellow earth side by side in a PVC sheath (twin and earth) (450/750 V; V-90 insulation, 90 C PVC sheath (Olex))
ORANGE CIRCULAROrange circular: round building cable, V-90 PVC-insulated copper cores and a green/yellow earth laid up round, orange PVC sheath (450/750 V or 0.6/1 kV; V-90 insulation, 90 C PVC sheath (Olex))
V-90V-90 building wire: one copper conductor, V-90 PVC insulation, unsheathed (0.6/1 kV (Prysmian Australia))
X-90X-90 single core: one copper conductor, X-90 XLPE insulation, PVC sheath (single double insulated, SDI) (0.6/1 kV, 90 C normal operation (Electra, Prysmian))
V-75V-75 building wire: one copper conductor, V-75 PVC insulation (0.6/1 kV (CMI))
Type 209Type 209: AS/NZS 1802 composite-screened cable for general use, three EPR power cores with a tinned copper and polyester composite screen (earth), one central extensible pilot, heavy-duty elastomer sheath (1.1/1.1 kV to 11/11 kV (Prysmian p.10))
Type 210Type 210: AS/NZS 1802 composite-screened cable for hand-held equipment, 1.1 kV, three EPR power cores with composite screens, central pilot, HD-85-PCP sheath (1.1/1.1 kV (Prysmian p.12; some authorities limit it to 250/250 V))
Type 240Type 240: AS/NZS 1802 composite-screened cable with three pilot conductors, for long feeder runs (1.1/1.1 kV to 11/11 kV (Prysmian p.14))
Type 241Type 241: AS/NZS 1802 semiconductive-screened cable, three EPR power cores on a black semiconductive screen, three earth cores, one central extensible pilot; Type 241SF the super-flexible build (1.1/1.1 kV to 11/11 kV (Prysmian p.16, p.18); Caledonian 'Type 241 1.1 to 11KV', 'Type 241 Superflex 1.1 to 6.6KV')
Type 245Type 245: AS/NZS 1802 super-flexible cable for longwall shearer cable chains, semiconductive-screened power cores, three earths and three extensible pilots (1.1/1.1 kV to 3.3/3.3 kV (Prysmian 'Type 245SF', Tratos); Caledonian 'Type 245 1.1 to 6.6KV')
Type 275Type 275: AS/NZS 1802 shuttle car cable, 1.1 kV, unscreened EPR power cores, three semiconductive-covered earths in the interstices, one central pilot, semiconductive filling and a reinforced HD-85-PCP sheath (1.1/1.1 kV (Prysmian p.22; Caledonian 'Type 275 1.1/1.1KV'))
Type 409Type 409: AS/NZS 2802 class 2 composite-screened open-cut trailing cable with a central pilot, Kevlar braid reinforced sheath (1.1/1.1 kV to 22/22 kV (Prysmian p.26; Caledonian 'Type 409 1.1 to 22KV'))
Type 440Type 440: AS/NZS 2802 class 2 composite-screened open-cut cable with three pilot cores in the interstices (1.1/1.1 kV to 22/22 kV (Prysmian p.28; Caledonian 'Type 440 1.1 to 22KV'))
Type 441Type 441: AS/NZS 2802 semiconductive-screened open-cut cable, three earth cores and one pilot (1.1 kV (class 2) and 3.3/3.3 to 22/22 kV (class 1) (Prysmian p.30, p.32))
Type 450Type 450: AS/NZS 2802 class 1 composite-screened reeling cable, 3.3 to 33 kV, two earths and one pilot, extra-heavy-duty Kevlar reinforced sheath (3.3/3.3 kV to 33/33 kV (Prysmian p.34))