USE-2 dimensions

Nominal calculation, not one manufacturer's datasheet. The conductor is NEC Chapter 9 Table 8; the insulation and nylon walls are the nominal values the makers catalogue, because UL 83, UL 44 and UL 854 were not read. A wire of the same name can differ slightly: check its datasheet before you specify or order.

Each row is one USE-2 size in copper at 600 V: the conductor from NEC Table 8, the walls as the makers catalogue them. Open a row for every layer and its source. What USE-2 means, letter by letter.

North American building wire, 600 V (AWG / kcmil) · 24 sizes

SizeRatingInsulation mmOverall diameter mmWeight (approximate) kg/km
14 AWG600 V1.144.130
12 AWG600 V1.144.640
10 AWG600 V1.145.160
8 AWG600 V1.526.6100
6 AWG600 V1.527.6150
4 AWG600 V1.528.8220
3 AWG600 V1.529.5280
2 AWG600 V1.5210.2340
1 AWG600 V2.0312.2440
1/0 AWG600 V2.0313.3550
2/0 AWG600 V2.0314.4680
3/0 AWG600 V2.0315.6850
4/0 AWG600 V2.0317.11,060
250 kcmil600 V2.4119.01,270
300 kcmil600 V2.4120.31,500
350 kcmil600 V2.4121.61,740
400 kcmil600 V2.4122.81,980
500 kcmil600 V2.4124.92,450
600 kcmil600 V2.7927.62,960
700 kcmil600 V2.7929.33,430
750 kcmil600 V2.7930.23,670
800 kcmil600 V2.7931.03,900
900 kcmil600 V2.7932.54,380
1000 kcmil600 V2.7934.04,850