NA2XS(FL)H 1x95 RM/16 18/30 kV

IEC nominal calculation, not manufacturer data. The thicknesses are the nominal values of the construction standards, added up layer by layer. A manufacturer's cable of the same name can differ by a few millimetres and by 10 to 20 % in weight: always check its datasheet before you specify, order or lay a cable.

By the IEC construction rules, NA2XS(FL)H 1x95 RM/16 18/30 kV comes to an overall diameter of about 37.7 mm and a weight of about 1,440 kg/km.

Open this cable in the designer Change any layer, see it in 3D and to scale, and download it.

This size as a PDF datasheet under your brand, with Pro. See Pro

Request a quote for this cable Sent to makers of this cable family, free.

Main dimensions

ConductorAluminium 95 mm² RM, Ø 11.5 mmIEC 60228 class 2 compacted, middle of min / max
InsulationXLPE 8.0 mmIEC 60502-2:2014 Tables 5-7, nominal insulation thickness
Diameter over insulation28.7 mm
Overall diameter37.7 mm
Weight (approximate)1,440 kg/km

Round conductors (IEC 60228 class 2 compacted; class 1 solid up to 10 mm²).

Layer by layer (inside out)

#LayerMaterialThickness mmØ over mmSourceHow firmly
1Conductor screen (semicon)Semiconducting0.612.7TKF at least 0.5 mm, Nexans under 1 mmtypical value, no rule
2InsulationXLPE8.028.7IEC 60502-2:2014 Tables 5-7, nominal insulation thicknessread in the standard
3Insulation screen (semicon)Semiconducting0.830.3TKF 0.8 mm, Nexans about 1 mmtypical value, no rule
4Swelling tape (water block)Swelling0.330.9typical swelling tape 0.30 mm; a wound tape at most 70 mm widetypical value, no rule
5Wire screenCopper42 wires of 0.70 mm, 16 mm²32.5copper wire screen: wires at least 0.5 mm (0.7 mm, thicker when the section does not fit), 0.1 mm counter-helix tapetypical value, no rule
6Swelling tape (water block)Swelling0.333.1typical swelling tape 0.30 mm; a wound tape at most 70 mm widetypical value, no rule
7Laminate (radial water block)Aluminium0.233.5typical aluminium laminate bonded to the sheathtypical value, no rule
8SheathHalogen-free (LSZH)2.137.7IEC 60502 clause 13 / 14.3, oversheath: 0.035 D + 1.0 mm, D the fictitious diameter (Annex A)read in the standard

Diameters add up the nominal layers. Where IEC 60502 sizes a layer by the fictitious diameter of its Annex A, the calculated diameter is used instead, which can move a value one step. Sources and page numbers: research/mv-dimensions in the site repository.

Materials in this cable: Copper, Aluminium, XLPE, Halogen-free (LSZH), Semiconductive compound

Weight, by part

Conductors260 kg/km
Metal screens and armour200 kg/km
Insulation, semicon, tapes, fillers and sheaths980 kg/km
Total1,440 kg/km

Each layer's cross-section times its density; stranded conductors, laid-up cores and helical wires count 2 % longer than the cable. Densities: copper 8.89 and aluminium 2.703 g/cm³ (the values of IEC 60028 and IEC 60889); XLPE 0.92, PE 0.94, PVC 1.45, semicon 1.12, steel 7.85 g/cm³ (usual compound values).

NA2XS(FL)H 1x95 RM/16 18/30 kV: equivalents in other countries

Shown for 1x95/16 18/30 kV. Each country's rules are applied to this build, keeping the conductor, section, cores, voltage, screen, armour and sheath.

CountryStandardName in that countryVerdictDifferences
International (IEC)IEC 60502Al/XLPE/CWS/LSZH 1x95/16 18/30 kV (to IEC 60502-2)CloseInsulation screen (semicon) 0.6 → 0.8 mm; Sheath 2.5 → 2.1 mm; Overall diameter 38.1 → 37.7 mm
NetherlandsHD 620 S3 10-Jno letters for this buildClosescreen 16 → 25 mm² (HD 620 10-J Table A.1); Insulation screen (semicon) 0.6 → 0.8 mm; Overall diameter 38.1 → 38.5 mm
SwedenHD 620 S3 10-MAXCQJ-TT 1x95/25 18/30 (36) kV (NKT writes a near build without the C (AXLJ))Closescreen 16 → 25 mm² (HD 620 10-M Tables 1A, 2A, 3A); Sheath 2.5 → 2.1 mm; Overall diameter 38.1 → 37.3 mm; this cable as built misses 1 of its rules
NorwayHD 620 S3 10-KTSLI 36 kV 1 x 95 mm2 A (provisional code designation of HD 620 10-K Table 4)Closescreen 16 → 25 mm² (HD 620 10-K Table 1); Insulation screen (semicon) 0.6 → 0.8 mm; Sheath 2.5 → 2.1 mm; Overall diameter 38.1 → 37.7 mm; this cable as built misses 1 of its rules
DenmarkHD 620 S3 10-Dno letters for this buildClosescreen 16 → 25 mm² (HD 620 10-D Table 1); Insulation screen (semicon) 0.6 → 0.8 mm; Sheath 2.5 → 3 mm; Overall diameter 38.1 → 39.5 mm; this cable as built misses 2 of its rules

No equivalent in: BS 6622 (armoured cables only).

Nominal values computed by each standard's rules, not manufacturer data. This is not a statement that two cables are interchangeable: the buyer's specification and the maker's type test decide.

Who makes or stocks this cable?

NA2XS(FL)H

The same section at other voltages

Other sections