XHIOV

XHIOV is a NP 665 (Portugal) cable designation: X = Cross-linked polyethylene (XLPE) insulation; HIO = HIO: radial-field cable, a copper wire screen over each core; V = PVC sheath; XHIOV = XHIOV: medium-voltage cable, copper conductor, XLPE insulation, radial field with a copper wire screen on each core, PVC sheath (HD 620 type 10L-1). 6/10 (12) to 18/30 (36) kV; 90 C conductor, 120 C short duration overload, 250 C short circuit (5 s) (HD 620 S3 10-L 1). HD 620 S3:2023 section 10-L, No. 14 code designation (p. 10-L-11), Type 10L-1; XLPE DIX 13 (1, p. 10-L-3). Owner's copy, read 2026-10-31, seen: standard; NP 665 letters.

1 coding system recognises this code

NP 665 (Portugal)

SymbolMeaning
XCross-linked polyethylene (XLPE) insulation
HIOHIO: radial-field cable, a copper wire screen over each core
VPVC sheath
XHIOVXHIOV: medium-voltage cable, copper conductor, XLPE insulation, radial field with a copper wire screen on each core, PVC sheath (HD 620 type 10L-1). 6/10 (12) to 18/30 (36) kV; 90 C conductor, 120 C short duration overload, 250 C short circuit (5 s) (HD 620 S3 10-L 1). HD 620 S3:2023 section 10-L, No. 14 code designation (p. 10-L-11), Type 10L-1; XLPE DIX 13 (1, p. 10-L-3). Owner's copy, read 2026-10-31, seen: standard; NP 665 letters

Fire behaviour (EU CPR)

A CPR class is declared by the maker in its Declaration of Performance and printed on the sheath (EN 50575 cl 7). This decoder does not assign one. What the CPR classes mean →

Sources: EN 13501-6 draft and FprEN 50575:2014 final draft (drafts, not the published texts); IEC 60332-3-24:2000+A1:2008; EN 13501-3 draft A2.