NOIKLX
NOIKLX is a HD 620-10D (Denmark) cable designation: NO = NKT family prefix of its halogen-free cables (the LK lommebog table lists every NO name under 'Halogenfri kabler'); the words behind N and O are not given in that table or on any NKT sheet found; I = Installation ('InstallationsKabel Let PEX', LK lommebog p. 98, nkt cables betegnelser); K = Cable ('InstallationsKabel', same row); L = Light ('Let': light installation cable, 300/500 V); X = Cross-linked polyethylene (PEX) insulation ('Let PEX' in the LK lommebog row; X read by position as the PEX letter); 90 = Maximum conductor temperature 90 C ('Max. ledertemperatur 90 C'); NOIKLX = NOIKLX: NKT light installation cable (Let installationskabel), copper, PEX insulation, filler sheath, halogen-free sheath, 300/500 V, 90 C. 300/500 V (0,3/0,5 kV), test 2 kV, 90 C conductor, 250 C short circuit. NKT factory standard 008 (NKT NOIKLX 90 sheet); letters per the LK lommebog 2012 table 'nkt cables betegnelser' (p. 98).
1 coding system recognises this code
HD 620-10D (Denmark)
| Symbol | Meaning |
|---|---|
NO | NKT family prefix of its halogen-free cables (the LK lommebog table lists every NO name under 'Halogenfri kabler'); the words behind N and O are not given in that table or on any NKT sheet found |
I | Installation ('InstallationsKabel Let PEX', LK lommebog p. 98, nkt cables betegnelser) |
K | Cable ('InstallationsKabel', same row) |
L | Light ('Let': light installation cable, 300/500 V) |
X | Cross-linked polyethylene (PEX) insulation ('Let PEX' in the LK lommebog row; X read by position as the PEX letter) |
90 | Maximum conductor temperature 90 C ('Max. ledertemperatur 90 C') |
NOIKLX | NOIKLX: NKT light installation cable (Let installationskabel), copper, PEX insulation, filler sheath, halogen-free sheath, 300/500 V, 90 C. 300/500 V (0,3/0,5 kV), test 2 kV, 90 C conductor, 250 C short circuit. NKT factory standard 008 (NKT NOIKLX 90 sheet); letters per the LK lommebog 2012 table 'nkt cables betegnelser' (p. 98) |
Fire behaviour (EU CPR)
Halogen-free compound (NOIKLX). Under the CPR this shows in the additional classes: acidity a1 to a3 (EN 60754-2) and smoke s1 to s3 (EN 50399; s1a and s1b add the 3 m cube test EN 61034-2). The main class, Aca to Fca, depends on the whole construction.
Typically targeted, as declared by makers for this kind of construction in the examples this site checked (not the class of this cable):
B2ca-s1,d0,a11-CXKH-R-J, Kablo VrchlabíCca-s1b,d1,a1FG16(O)M16, Nexans (La Triveneta Cavi)B2ca-s1a,d1,a1FG18(O)M16, Nexans (La Triveneta Cavi)DcaFXQJ, Nexans NorwayCca-s1,d1,a1H07Z1-K, Nexans SpainB2caAXQJ-RMF, Prysmian Sweden (12/20 kV)Cca-s1b,d1,a1RZ1FZ1-K (AS), Top CableCca-s1a,d1,a1RZ1-K (AS), Top Cable (B2ca-s1a,d1,a1 for some sizes)
Listed as sources, alphabetically by maker. No maker pays to appear here.
A CPR class is declared by the maker in its Declaration of Performance and printed on the sheath (EN 50575 cl 7). This decoder does not assign one. What the CPR classes mean →
Sources: EN 13501-6 draft and FprEN 50575:2014 final draft (drafts, not the published texts); IEC 60332-3-24:2000+A1:2008; EN 13501-3 draft A2.
NOIKLX: equivalents in other countries
Shown for 3x95 0.6/1 kV. Each country's rules are applied to this build, keeping the conductor, section, cores, voltage, screen, armour and sheath.
| Country | Standard | Name in that country | Verdict | Differences |
|---|---|---|---|---|
| Germany | HD 603 5-G (DIN VDE 0276-603) | N2XH 3x95 RM 0,6/1 kV | Equivalent | every value the same |
No equivalent in: BS 5467 (armoured cables only, asks another sheath compound); BS 6724 (armoured cables only); BS 7846 (armoured cables only).
Nominal values computed by each standard's rules, not manufacturer data. This is not a statement that two cables are interchangeable: the buyer's specification and the maker's type test decide.
NOIKLX as the cable designer builds it, 3x95 0.6/1 kV
Overall diameter 35.9 mm, about 3,360 kg/km. Nominal values from the standard's tables for this size, computed, not a maker's data.
| Layer | Material | Thickness, mm | Over the layer, mm |
|---|---|---|---|
| Insulation | XLPE | 1.1 | 13.7 |
| Filler | PP | 29.5 | |
| Inner covering / bedding | Halogen-free (LSZH) | 1.2 | 31.9 |
| Sheath | Halogen-free (LSZH) | 2.0 | 35.9 |
NOIKLX on a drum
The smallest drum that passes every check, for 35.9 mm and about 3,360 kg/km as the cable designer builds it. Drums as their makers print them; lengths are estimates within a few per cent of the cable makers' own tables: whole layers, wound diameter 1.05 × OD, 50 mm freeboard under the flange rim.
| Length | Drum size (its makers) | Layers | Gross weight |
|---|---|---|---|
| 500 m | KTG 16 (1600 mm flange), wood KTG drums (Europe), Bayka, KTG | 7 of 9 | 1,956–1,989 kg |
| 1,000 m | KTG 20 (2000 mm flange), wood KTG drums (Europe), Bayka, KTG | 8 of 8 | 3,839–3,960 kg |
Barrel at least 15 × OD = 539 mm for a cable of this kind (Low voltage, multi-core): KTG table, the cable's datasheet wins. A load rating is the drum maker's own.
Other lengths, drums and weights: the cable drum calculator
Load it on a truck: 1000 m on its drum in the loading planner
Laying, sizes and datasheet: NOIKLX
NOIKLX belongs to the family LV XLPE power cables: the lowest laying temperature, bending radius, pulling, depth, drum handling and the test after laying, every rule with its sources. Laying and handling guide: LV XLPE power cables