AYWY
AYWY is a BIS type names (India) cable designation: A = Aluminium conductor; Y = PVC insulation; W = Round steel wire armour; Y = PVC outer sheath; AYWY = AYWY: aluminium conductors, PVC insulation, inner sheath, galvanised round steel wire armour, PVC outer sheath (IS 1554-1, up to 1100 V). Up to and including 1100 V a.c.; d.c. up to and including 1500 V to earth; 70 C (Type A PVC) or 85 C (Type C, marked HR 85), 160 C short circuit. IS 1554 (Part 1):1988 (reaffirmed 2020), cable code cl. 17.3.
5 coding systems recognise this code
BIS type names (India)
| Symbol | Meaning |
|---|---|
A | Aluminium conductor |
Y | PVC insulation |
W | Round steel wire armour |
Y | PVC outer sheath |
AYWY | AYWY: aluminium conductors, PVC insulation, inner sheath, galvanised round steel wire armour, PVC outer sheath (IS 1554-1, up to 1100 V). Up to and including 1100 V a.c.; d.c. up to and including 1500 V to earth; 70 C (Type A PVC) or 85 C (Type C, marked HR 85), 160 C short circuit. IS 1554 (Part 1):1988 (reaffirmed 2020), cable code cl. 17.3 |
India (IS 1554 / IS 7098 cable code)
| Symbol | Meaning |
|---|---|
A | Aluminium Conductor |
Y | Polyvinyl Chloride (PVC) |
W | Round Steel Wire |
Y | Polyvinyl Chloride (PVC) |
How to read a India (IS 1554 / IS 7098 cable code) cable code
VDE telecom, signal and fibre cables (DIN VDE 0815, 0816, 0813, 0888)
| Symbol | Meaning |
|---|---|
A | Outdoor Cable |
Y | Polyvinyl Chloride (PVC) |
W | Steel Sheath, Corrugated |
Y | Polyvinyl Chloride (PVC) |
How to read a VDE telecom, signal and fibre cables (DIN VDE 0815, 0816, 0813, 0888) cable code
China (GB / JB/T / MT cable model codes)
| Symbol | Meaning |
|---|---|
A | Twin Cable |
YW | Foam-Skin Polyethylene |
Y | Polyethylene (PE) Or Polyolefin |
How to read a China (GB / JB/T / MT cable model codes) cable code
CEI-UNEL 35011 (Italy)
| Symbol | Meaning |
|---|---|
A | Aluminium Conductor |
Y | Textile Or Metallic Carrying Component Between Cores |
W | Divisible Flat Cable (Intermediary Groove) |
Y | Textile Or Metallic Carrying Component Between Cores |
Fire behaviour (EU CPR)
PVC sheath (Y).
Typically targeted, as declared by makers for this kind of construction in the examples this site checked (not the class of this cable):
EcaN1XV-R, Ahlsell (seller)Cca-s3,d1,a3FG16OR16, Nexans (La Triveneta Cavi)EcaU1000 R2V, Nexans (La Triveneta Cavi)EcaN2XSY, Waskönig+Walter (10 kV datasheet)
Listed as sources, alphabetically by maker. No maker pays to appear here.
A CPR class is declared by the maker in its Declaration of Performance and printed on the sheath (EN 50575 cl 7). This decoder does not assign one. What the CPR classes mean →
Sources: EN 13501-6 draft and FprEN 50575:2014 final draft (drafts, not the published texts); IEC 60332-3-24:2000+A1:2008; EN 13501-3 draft A2.
AYWY as the cable designer builds it, 3x16 1100 V
Overall diameter 21.5 mm, about 910 kg/km. Nominal values from the standard's tables for this size, computed, not a maker's data.
| Layer | Material | Thickness, mm | Over the layer, mm |
|---|---|---|---|
| Insulation | PVC | 1.0 | 6.9 |
| Filler | PP | 14.9 | |
| Inner covering / bedding | PVC | 0.30 | 15.5 |
| Wire armour | Steel | 32 × 1.60 | 18.7 |
| Sheath | PVC | 1.4 | 21.5 |
AYWY on a drum
The smallest drum that passes every check, for 21.5 mm and about 910 kg/km as the cable designer builds it. Drums as their makers print them; lengths are estimates within a few per cent of the cable makers' own tables: whole layers, wound diameter 1.05 × OD, 50 mm freeboard under the flange rim.
| Length | Drum size (its makers) | Layers | Gross weight |
|---|---|---|---|
| 500 m | KTG 12 (1250 mm flange), wood KTG drums (Europe), Bayka, KTG | 7 of 11 | 599–620 kg |
| 1,000 m | KTG 14 (1400 mm flange), wood KTG drums (Europe), Bayka, KTG | 12 of 13 | 1,085–1,109 kg |
Barrel at least 15 × OD = 322 mm for a cable of this kind (Low voltage, multi-core): KTG table, the cable's datasheet wins. A load rating is the drum maker's own.
Other lengths, drums and weights: the cable drum calculator
Load it on a truck: 1000 m on its drum in the loading planner
Laying, sizes and datasheet: AYWY
Terms on this page: oversheath (outer sheath) · steel wire armour
Selling this cable? Open it in the designer and get a datasheet with your logo (Pro). Open the cable designer · See Pro