6491B

6491B is a BS 6004 / BS 6500 / BS 7211 type numbers (UK) cable designation: 649 = Single-core non-sheathed cable (insulation only), for conduit and trunking; 1 = Number of cores: 1; B = Low smoke, halogen-free (LSZH / LSF) materials; 6491B = 6491B: single-core low smoke halogen-free (LSF) insulated, non-sheathed wire (the UK number of H07Z-U / H07Z-R). 450/750 V from 1.5 mm2 (300/500 V up to 1.0 mm2), 90 C maximum conductor temperature (Anixter p. 1:18). BS 7211 and harmonised H07Z-U / H07Z-R (Anixter p. 1:18); now BS EN 50525-3-41.

1 coding system recognises this code

BS 6004 / BS 6500 / BS 7211 type numbers (UK)

SymbolMeaning
649Single-core non-sheathed cable (insulation only), for conduit and trunking
1Number of cores: 1
BLow smoke, halogen-free (LSZH / LSF) materials
6491B6491B: single-core low smoke halogen-free (LSF) insulated, non-sheathed wire (the UK number of H07Z-U / H07Z-R). 450/750 V from 1.5 mm2 (300/500 V up to 1.0 mm2), 90 C maximum conductor temperature (Anixter p. 1:18). BS 7211 and harmonised H07Z-U / H07Z-R (Anixter p. 1:18); now BS EN 50525-3-41

Fire behaviour (EU CPR)

A CPR class is declared by the maker in its Declaration of Performance and printed on the sheath (EN 50575 cl 7). This decoder does not assign one. What the CPR classes mean →

Sources: EN 13501-6 draft and FprEN 50575:2014 final draft (drafts, not the published texts); IEC 60332-3-24:2000+A1:2008; EN 13501-3 draft A2.

Laying, sizes and datasheet: 6491B

Terms on this page: conduit

Work with 6491B

Related cables

More BS 6004 / BS 6500 / BS 7211 type numbers (UK) designations