Mineralisolerte kabler (MICC, utførelser etter IEC 60702-1)
International (mineral insulated cables) · 57 typer · Mineralisolerte kabler (MICC, utførelser etter IEC 60702-1): slik leser du kabeltypenavnene
MICC | MICC: mineral insulated copper sheathed cable (light duty 500 V or heavy duty 750 V) (light duty 500 V, heavy duty 750 V; copper sheath 70 C covered or exposed to touch, 105 C bare and out of reach (IEC 60364-5-52:2009 Table 52.1)) |
2L1 | 2L1: mineral insulated copper cable, light duty 500 V, 2 x 1 mm2, 5.1 mm over the copper sheath (6.6 mm with the LSZH covering) (300/500 V; copper sheath 70 C covered or exposed to touch, 105 C bare and out of reach) |
2L1.5 | 2L1.5: mineral insulated copper cable, light duty 500 V, 2 x 1,5 mm2, 5.7 mm over the copper sheath (7.2 mm with the LSZH covering) (300/500 V; copper sheath 70 C covered or exposed to touch, 105 C bare and out of reach) |
2L2.5 | 2L2.5: mineral insulated copper cable, light duty 500 V, 2 x 2,5 mm2, 6.6 mm over the copper sheath (8.1 mm with the LSZH covering) (300/500 V; copper sheath 70 C covered or exposed to touch, 105 C bare and out of reach) |
2L4 | 2L4: mineral insulated copper cable, light duty 500 V, 2 x 4 mm2, 7.7 mm over the copper sheath (9.4 mm with the LSZH covering) (300/500 V; copper sheath 70 C covered or exposed to touch, 105 C bare and out of reach) |
3L1 | 3L1: mineral insulated copper cable, light duty 500 V, 3 x 1 mm2, 5.8 mm over the copper sheath (7.3 mm with the LSZH covering) (300/500 V; copper sheath 70 C covered or exposed to touch, 105 C bare and out of reach) |
3L1.5 | 3L1.5: mineral insulated copper cable, light duty 500 V, 3 x 1,5 mm2, 6.4 mm over the copper sheath (7.9 mm with the LSZH covering) (300/500 V; copper sheath 70 C covered or exposed to touch, 105 C bare and out of reach) |
3L2.5 | 3L2.5: mineral insulated copper cable, light duty 500 V, 3 x 2,5 mm2, 7.3 mm over the copper sheath (9.0 mm with the LSZH covering) (300/500 V; copper sheath 70 C covered or exposed to touch, 105 C bare and out of reach) |
4L1 | 4L1: mineral insulated copper cable, light duty 500 V, 4 x 1 mm2, 6.3 mm over the copper sheath (7.8 mm with the LSZH covering) (300/500 V; copper sheath 70 C covered or exposed to touch, 105 C bare and out of reach) |
4L1.5 | 4L1.5: mineral insulated copper cable, light duty 500 V, 4 x 1,5 mm2, 7.0 mm over the copper sheath (8.5 mm with the LSZH covering) (300/500 V; copper sheath 70 C covered or exposed to touch, 105 C bare and out of reach) |
4L2.5 | 4L2.5: mineral insulated copper cable, light duty 500 V, 4 x 2,5 mm2, 8.1 mm over the copper sheath (9.8 mm with the LSZH covering) (300/500 V; copper sheath 70 C covered or exposed to touch, 105 C bare and out of reach) |
7L1 | 7L1: mineral insulated copper cable, light duty 500 V, 7 x 1 mm2, 7.6 mm over the copper sheath (9.3 mm with the LSZH covering) (300/500 V; copper sheath 70 C covered or exposed to touch, 105 C bare and out of reach) |
7L1.5 | 7L1.5: mineral insulated copper cable, light duty 500 V, 7 x 1,5 mm2, 8.4 mm over the copper sheath (10.1 mm with the LSZH covering) (300/500 V; copper sheath 70 C covered or exposed to touch, 105 C bare and out of reach) |
7L2.5 | 7L2.5: mineral insulated copper cable, light duty 500 V, 7 x 2,5 mm2, 9.7 mm over the copper sheath (11.4 mm with the LSZH covering) (300/500 V; copper sheath 70 C covered or exposed to touch, 105 C bare and out of reach) |
1H1.5 | 1H1.5: mineral insulated copper cable, heavy duty 750 V, 1 x 1,5 mm2, 4.9 mm over the copper sheath (6.2 mm with the LSZH covering) (450/750 V; copper sheath 70 C covered or exposed to touch, 105 C bare and out of reach) |
1H2.5 | 1H2.5: mineral insulated copper cable, heavy duty 750 V, 1 x 2,5 mm2, 5.3 mm over the copper sheath (6.6 mm with the LSZH covering) (450/750 V; copper sheath 70 C covered or exposed to touch, 105 C bare and out of reach) |
1H4 | 1H4: mineral insulated copper cable, heavy duty 750 V, 1 x 4 mm2, 5.9 mm over the copper sheath (7.2 mm with the LSZH covering) (450/750 V; copper sheath 70 C covered or exposed to touch, 105 C bare and out of reach) |
1H6 | 1H6: mineral insulated copper cable, heavy duty 750 V, 1 x 6 mm2, 6.4 mm over the copper sheath (7.7 mm with the LSZH covering) (450/750 V; copper sheath 70 C covered or exposed to touch, 105 C bare and out of reach) |
1H10 | 1H10: mineral insulated copper cable, heavy duty 750 V, 1 x 10 mm2, 7.3 mm over the copper sheath (9.0 mm with the LSZH covering) (450/750 V; copper sheath 70 C covered or exposed to touch, 105 C bare and out of reach) |
1H16 | 1H16: mineral insulated copper cable, heavy duty 750 V, 1 x 16 mm2, 8.3 mm over the copper sheath (10.0 mm with the LSZH covering) (450/750 V; copper sheath 70 C covered or exposed to touch, 105 C bare and out of reach) |
1H25 | 1H25: mineral insulated copper cable, heavy duty 750 V, 1 x 25 mm2, 9.6 mm over the copper sheath (11.3 mm with the LSZH covering) (450/750 V; copper sheath 70 C covered or exposed to touch, 105 C bare and out of reach) |
1H35 | 1H35: mineral insulated copper cable, heavy duty 750 V, 1 x 35 mm2, 10.7 mm over the copper sheath (12.4 mm with the LSZH covering) (450/750 V; copper sheath 70 C covered or exposed to touch, 105 C bare and out of reach) |
1H50 | 1H50: mineral insulated copper cable, heavy duty 750 V, 1 x 50 mm2, 12.1 mm over the copper sheath (13.8 mm with the LSZH covering) (450/750 V; copper sheath 70 C covered or exposed to touch, 105 C bare and out of reach) |
1H70 | 1H70: mineral insulated copper cable, heavy duty 750 V, 1 x 70 mm2, 13.7 mm over the copper sheath (15.4 mm with the LSZH covering) (450/750 V; copper sheath 70 C covered or exposed to touch, 105 C bare and out of reach) |
1H95 | 1H95: mineral insulated copper cable, heavy duty 750 V, 1 x 95 mm2, 15.4 mm over the copper sheath (17.7 mm with the LSZH covering) (450/750 V; copper sheath 70 C covered or exposed to touch, 105 C bare and out of reach) |
1H120 | 1H120: mineral insulated copper cable, heavy duty 750 V, 1 x 120 mm2, 16.8 mm over the copper sheath (19.1 mm with the LSZH covering) (450/750 V; copper sheath 70 C covered or exposed to touch, 105 C bare and out of reach) |
1H150 | 1H150: mineral insulated copper cable, heavy duty 750 V, 1 x 150 mm2, 18.4 mm over the copper sheath (20.7 mm with the LSZH covering) (450/750 V; copper sheath 70 C covered or exposed to touch, 105 C bare and out of reach) |
1H185 | 1H185: mineral insulated copper cable, heavy duty 750 V, 1 x 185 mm2, 20.4 mm over the copper sheath (23.2 mm with the LSZH covering) (450/750 V; copper sheath 70 C covered or exposed to touch, 105 C bare and out of reach) |
1H240 | 1H240: mineral insulated copper cable, heavy duty 750 V, 1 x 240 mm2, 23.3 mm over the copper sheath (26.1 mm with the LSZH covering) (450/750 V; copper sheath 70 C covered or exposed to touch, 105 C bare and out of reach) |
1H300 | 1H300: mineral insulated copper cable, heavy duty 750 V, 1 x 300 mm2, 26.0 mm over the copper sheath (28.8 mm with the LSZH covering) (450/750 V; copper sheath 70 C covered or exposed to touch, 105 C bare and out of reach) |
1H400 | 1H400: mineral insulated copper cable, heavy duty 750 V, 1 x 400 mm2, 30.0 mm over the copper sheath (32.8 mm with the LSZH covering) (450/750 V; copper sheath 70 C covered or exposed to touch, 105 C bare and out of reach) |
2H1.5 | 2H1.5: mineral insulated copper cable, heavy duty 750 V, 2 x 1,5 mm2, 7.9 mm over the copper sheath (9.6 mm with the LSZH covering) (450/750 V; copper sheath 70 C covered or exposed to touch, 105 C bare and out of reach) |
2H2.5 | 2H2.5: mineral insulated copper cable, heavy duty 750 V, 2 x 2,5 mm2, 8.7 mm over the copper sheath (10.4 mm with the LSZH covering) (450/750 V; copper sheath 70 C covered or exposed to touch, 105 C bare and out of reach) |
2H4 | 2H4: mineral insulated copper cable, heavy duty 750 V, 2 x 4 mm2, 9.8 mm over the copper sheath (11.5 mm with the LSZH covering) (450/750 V; copper sheath 70 C covered or exposed to touch, 105 C bare and out of reach) |
2H6 | 2H6: mineral insulated copper cable, heavy duty 750 V, 2 x 6 mm2, 10.9 mm over the copper sheath (12.6 mm with the LSZH covering) (450/750 V; copper sheath 70 C covered or exposed to touch, 105 C bare and out of reach) |
2H10 | 2H10: mineral insulated copper cable, heavy duty 750 V, 2 x 10 mm2, 12.7 mm over the copper sheath (14.4 mm with the LSZH covering) (450/750 V; copper sheath 70 C covered or exposed to touch, 105 C bare and out of reach) |
2H16 | 2H16: mineral insulated copper cable, heavy duty 750 V, 2 x 16 mm2, 14.7 mm over the copper sheath (16.4 mm with the LSZH covering) (450/750 V; copper sheath 70 C covered or exposed to touch, 105 C bare and out of reach) |
2H25 | 2H25: mineral insulated copper cable, heavy duty 750 V, 2 x 25 mm2, 17.1 mm over the copper sheath (19.4 mm with the LSZH covering) (450/750 V; copper sheath 70 C covered or exposed to touch, 105 C bare and out of reach) |
3H1.5 | 3H1.5: mineral insulated copper cable, heavy duty 750 V, 3 x 1,5 mm2, 8.3 mm over the copper sheath (10.0 mm with the LSZH covering) (450/750 V; copper sheath 70 C covered or exposed to touch, 105 C bare and out of reach) |
3H2.5 | 3H2.5: mineral insulated copper cable, heavy duty 750 V, 3 x 2,5 mm2, 9.3 mm over the copper sheath (11.0 mm with the LSZH covering) (450/750 V; copper sheath 70 C covered or exposed to touch, 105 C bare and out of reach) |
3H4 | 3H4: mineral insulated copper cable, heavy duty 750 V, 3 x 4 mm2, 10.4 mm over the copper sheath (12.1 mm with the LSZH covering) (450/750 V; copper sheath 70 C covered or exposed to touch, 105 C bare and out of reach) |
3H6 | 3H6: mineral insulated copper cable, heavy duty 750 V, 3 x 6 mm2, 11.5 mm over the copper sheath (13.2 mm with the LSZH covering) (450/750 V; copper sheath 70 C covered or exposed to touch, 105 C bare and out of reach) |
3H10 | 3H10: mineral insulated copper cable, heavy duty 750 V, 3 x 10 mm2, 13.6 mm over the copper sheath (15.3 mm with the LSZH covering) (450/750 V; copper sheath 70 C covered or exposed to touch, 105 C bare and out of reach) |
3H16 | 3H16: mineral insulated copper cable, heavy duty 750 V, 3 x 16 mm2, 15.6 mm over the copper sheath (17.9 mm with the LSZH covering) (450/750 V; copper sheath 70 C covered or exposed to touch, 105 C bare and out of reach) |
3H25 | 3H25: mineral insulated copper cable, heavy duty 750 V, 3 x 25 mm2, 18.2 mm over the copper sheath (20.5 mm with the LSZH covering) (450/750 V; copper sheath 70 C covered or exposed to touch, 105 C bare and out of reach) |
4H1.5 | 4H1.5: mineral insulated copper cable, heavy duty 750 V, 4 x 1,5 mm2, 9.1 mm over the copper sheath (10.8 mm with the LSZH covering) (450/750 V; copper sheath 70 C covered or exposed to touch, 105 C bare and out of reach) |
4H2.5 | 4H2.5: mineral insulated copper cable, heavy duty 750 V, 4 x 2,5 mm2, 10.1 mm over the copper sheath (11.8 mm with the LSZH covering) (450/750 V; copper sheath 70 C covered or exposed to touch, 105 C bare and out of reach) |
4H4 | 4H4: mineral insulated copper cable, heavy duty 750 V, 4 x 4 mm2, 11.4 mm over the copper sheath (13.1 mm with the LSZH covering) (450/750 V; copper sheath 70 C covered or exposed to touch, 105 C bare and out of reach) |
4H6 | 4H6: mineral insulated copper cable, heavy duty 750 V, 4 x 6 mm2, 12.7 mm over the copper sheath (14.4 mm with the LSZH covering) (450/750 V; copper sheath 70 C covered or exposed to touch, 105 C bare and out of reach) |
4H10 | 4H10: mineral insulated copper cable, heavy duty 750 V, 4 x 10 mm2, 14.8 mm over the copper sheath (16.5 mm with the LSZH covering) (450/750 V; copper sheath 70 C covered or exposed to touch, 105 C bare and out of reach) |
4H16 | 4H16: mineral insulated copper cable, heavy duty 750 V, 4 x 16 mm2, 17.3 mm over the copper sheath (19.6 mm with the LSZH covering) (450/750 V; copper sheath 70 C covered or exposed to touch, 105 C bare and out of reach) |
4H25 | 4H25: mineral insulated copper cable, heavy duty 750 V, 4 x 25 mm2, 20.1 mm over the copper sheath (22.9 mm with the LSZH covering) (450/750 V; copper sheath 70 C covered or exposed to touch, 105 C bare and out of reach) |
7H1.5 | 7H1.5: mineral insulated copper cable, heavy duty 750 V, 7 x 1,5 mm2, 10.8 mm over the copper sheath (12.5 mm with the LSZH covering) (450/750 V; copper sheath 70 C covered or exposed to touch, 105 C bare and out of reach) |
7H2.5 | 7H2.5: mineral insulated copper cable, heavy duty 750 V, 7 x 2,5 mm2, 12.1 mm over the copper sheath (13.8 mm with the LSZH covering) (450/750 V; copper sheath 70 C covered or exposed to touch, 105 C bare and out of reach) |
12H1.5 | 12H1.5: mineral insulated copper cable, heavy duty 750 V, 12 x 1,5 mm2, 14.1 mm over the copper sheath (15.8 mm with the LSZH covering) (450/750 V; copper sheath 70 C covered or exposed to touch, 105 C bare and out of reach) |
12H2.5 | 12H2.5: mineral insulated copper cable, heavy duty 750 V, 12 x 2,5 mm2, 15.6 mm over the copper sheath (17.9 mm with the LSZH covering) (450/750 V; copper sheath 70 C covered or exposed to touch, 105 C bare and out of reach) |