Slik leser du en typebetegnelse: guider per betegnelsessystem · NEC / UL (USA) · USA
NEC / UL (USA): slik leser du kabeltypenavnene
Hvert navn i NEC / UL (USA) står for en hel kabeltype: THW har for eksempel sin egen konstruksjon, standard og egne merkedata. Dekoderen kjenner 133 typer i dette systemet. Nedenfor: hvordan navnene er bygd opp, hver type med sine merkedata og kildene tabellen nevner.
Slik er et navn bygd opp
Typetabellen deler hvert navn opp i deler og angir hva hver del betyr. Noen navn tatt fra hverandre:
THW
| T | Thermoplastic (PVC) insulation |
| H | Heat resistant, 75 C (one H) |
| W | Approved for wet locations |
Thermoplastic heat- and moisture-resistant building wire, 75 C
THHN
| T | Thermoplastic (PVC) insulation |
| HH | High heat resistant, 90 C (one H means 75 C) |
| N | Nylon outer covering |
Thermoplastic high heat-resistant nylon-coated building wire
SOOW
| S | Service cord, 600 V, extra-hard usage |
| OO | Oil-resistant insulation (inner) and jacket (outer) |
| W | Weather- and water-resistant |
Standard thermoset flexible cord, oil-resistant, weather-resistant
CMP
| C | Communications cable |
| M | Multipurpose rating (reading by usage, UNVERIFIED) |
| P | Plenum |
Communications cable, plenum rated (low smoke; FEP insulation on 4-pair data cable, low-smoke PVC on 2-conductor cable)
Alle deler som brukes i navnene
| Del | Betydning | Brukes i |
|---|---|---|
| W | Weather- and water-resistant | SOW SOOW SJOW SJOOW SJTW SJTOW SJTOOW STW STOW STOOW SEOW SEOOW SJEOOW |
| S | Service cord, 600 V, extra-hard usage | SO SOO SOW SOOW ST STW STO STOW STOOW SEOW SEOOW |
| T | Thermoplastic (PVC) insulation | TW THW THHW THWN THHN THWN-2 TFFN TFN TFF TF |
| T | Thermoplastic (PVC) insulation and jacket | SJT SJTW SJTO SJTOW SJTOOW ST STW STO STOW STOOW |
| O | Oil-resistant outer jacket | SO SOW SJO SJOW SJTO SJTOW STO STOW SEOW |
| SJ | Junior service cord, 300 V, lighter duty | SJO SJOW SJOOW SJT SJTW SJTO SJTOW SJTOOW SJEOOW |
| C | Communications cable | CM CMP CMR CMG CMX CMP-LP CMR-LP CMG-LP CM-LP |
| M | Multipurpose rating (reading by usage, UNVERIFIED) | CM CMP CMR CMG CMX CMP-LP CMR-LP CMG-LP CM-LP |
| W | Approved for wet locations | THW THHW THWN THWN-2 XHHW XHHW-2 RHW RHW-2 |
| R | Riser | CMR CL2R CL3R OFNR OFCR CATVR CMR-LP NPLFR |
| CL | Class 2 or 3 power-limited circuit cable | CL2 CL2R CL2P CL2X CL3 CL3R CL3P CL3X |
| OF | Optical fibre | OFN OFNG OFNR OFNP OFC OFCR OFCP OFCG |
| OO | Oil-resistant insulation (inner) and jacket (outer) | SOO SOOW SJOOW SJTOOW STOOW SEOOW SJEOOW |
| P | Plenum | CMP OFNP OFCP CATVP CMP-LP NPLFP |
| AWM | Appliance wiring material, UL 758: a style number, not an NEC wiring type | AWM 1007 AWM 1015 AWM 2464 AWM 2517 AWM 2919 AWM 20276 |
| N | Nylon outer covering | THWN THHN THWN-2 TFFN TFN |
| S | Service cord | SPT-1 SPT-2 SPT-3 SPT SVT |
| T | Thermoplastic (PVC) | SPT-1 SPT-2 SPT-3 SPT SVT |
| -2 | 90 C in both wet and dry locations | THWN-2 XHHW-2 RHW-2 USE-2 |
| HH | High heat resistant, 90 C | XHH XHHW XHHW-2 RHH |
| P | Parallel (zip) construction | SPT-1 SPT-2 SPT-3 SPT |
| 2 | Class 2 circuit | CL2 CL2R CL2P CL2X |
| 3 | Class 3 circuit | CL3 CL3R CL3P CL3X |
| N | Nonconductive (dielectric) | OFN OFNG OFNR OFNP |
| C | Conductive (metallic member, UNVERIFIED) | OFC OFCR OFCP OFCG |
| LP | Limited power: rated current per conductor printed, for power over Ethernet (NEC 2023) | CMP-LP CMR-LP CMG-LP CM-LP |
| X | Thermoset (cross-linked polyethylene) insulation | XHH XHHW XHHW-2 |
| R | Thermoset (originally rubber) insulation | RHH RHW RHW-2 |
| TC | Tray cable | TC-ER TC-ER-HL TC-ER-JP |
| ER | Exposed run (NEC 336.10(7)): passes the UL 1277 impact and crush tests; a grounding conductor unless three or more circuit conductors none over 6 AWG (UL 1277 ed. 6, 8.7, 30.1(p)) | TC-ER TC-ER-HL TC-ER-JP |
| E | Thermoplastic elastomer (TPE) insulation and jacket (reading from Seoprene pages; E alone UNVERIFIED) | SEOW SEOOW SJEOOW |
| X | Limited use (VW-1 vertical flame test) | CMX CL2X CL3X |
| CATV | Community antenna television (coaxial) cable, NEC 820 | CATVR CATVP CATVX |
| H | Heat resistant, 75 C (one H) | THW THWN |
| H | Heat resistant | THWN-2 RHW-2 |
| U | Underground, direct burial | USE USE-2 |
| SE | Service entrance | USE USE-2 |
| FF | Flexible fixture (stranded) wire | TFFN TFF |
| F | Fixture wire | TFN TF |
| -B | Conductors rated 90 C | NM-B UF-B |
| SE | Service-entrance cable | SER SEU |
| ITC | Instrumentation tray cable | ITC-ER ITC-HL |
| ER | Exposed run | ITC-ER PLTC-ER |
| PLTC | Power-limited tray cable | PLTC-ER PLTC-HL |
| MV | Medium voltage | MV-90 MV-105 |
| G | Grounded portable power cable (UNVERIFIED) | TYPE G G-GC |
| P | Plenum (NFPA 262 tunnel test) | CL2P CL3P |
| FPL | Fire alarm, power limited | FPLR FPLP |
| G | General purpose | OFNG CMG-LP |
| NPLF | Non-power-limited fire alarm cable (NEC 760 Part II) | NPLFR NPLFP |
| HL | Hazardous location: welded corrugated aluminium sheath under the jacket | ITC-HL PLTC-HL |
| SHD | Shielded, heavy duty: each phase core under a flexible copper braid shield (Prysmian: Shielded Round) | SHD-GC SHD-CGC |
| GC | Ground-check conductor, yellow polypropylene insulated, for fail-safe ground monitoring | SHD-GC MP-GC |
| W | Moisture resistant, wet locations | TW |
| HH | High heat resistant, 90 C range (two H) | THHW |
| HH | High heat resistant, 90 C (one H means 75 C) | THHN |
| H | Heat resistant, 75 C | RHW |
| NM | Non-metallic sheathed cable | NM-B |
| UF | Underground feeder, direct burial | UF-B |
| R | Round cable with separate neutral and ground (reading by usage, UNVERIFIED) | SER |
| U | Flat (oval) cable with a concentric bare neutral (reading by usage, UNVERIFIED) | SEU |
| AC | Armored cable, interlocked armour | AC |
| 90 | Conductors rated 90 C (AC-90 / ACHH) | AC |
| MC | Metal-clad cable | MC-HL |
| -HL | Hazardous locations, Class I, II, III Div 1 and 2 and Class I Zones 1 and 2 | MC-HL |
| HL | Hazardous locations: a TC-ER cable that also meets UL 2225 (UL 1277 ed. 6, 30.1(t)) | TC-ER-HL |
| -90 | Conductor temperature rating 90 C (emergency 130 C, short circuit 250 C) | MV-90 |
| -105 | Conductor temperature rating 105 C (emergency 140 C, short circuit 250 C) | MV-105 |
| XLPE | Cross-linked polyethylene insulation; the number before it is the wall in mils (AEIC CS9-06 Appendix E Table E-1, by voltage class) | AEIC-CS9 |
| -1 | Insulation thickness class 1 (UNVERIFIED) | SPT-1 |
| -2 | Insulation thickness class 2 (0.045 in on the AWC page) | SPT-2 |
| -3 | Insulation thickness class 3 (UNVERIFIED) | SPT-3 |
| V | Vacuum cleaner / appliance (UNVERIFIED) | SVT |
| SVT | Service vacuum thermoplastic cord | SVTO |
| O | Oil-resistant jacket | SVTO |
| H | Heater cord (UNVERIFIED) | HPN |
| P | Parallel construction (UNVERIFIED) | HPN |
| N | Neoprene insulation (UNVERIFIED) | HPN |
| W | Portable power cable type W (weather and water resistant) | TYPE W |
| GC | Ground-check conductor (UNVERIFIED) | G-GC |
| PV | Photovoltaic wire | PV WIRE |
| G | General purpose (FT4 vertical flame test) | CMG |
| R | Riser (UL 1666) | FPLR |
| P | Plenum (UL 910, low smoke) | FPLP |
| 1007 | Style 1007: 300 V a.c., 80 C, 32 to 16 AWG, PVC insulation | AWM 1007 |
| 1015 | Style 1015: 600 V a.c. or 750 V d.c., 80 / 90 / 105 C, 30 AWG to 2000 kcmil, PVC insulation | AWM 1015 |
| 2464 | Style 2464: 300 V a.c., 80 C, multi-conductor with a jacket | AWM 2464 |
| 2517 | Style 2517: 300 V a.c., 105 C, multi-conductor with a jacket | AWM 2517 |
| 2919 | Style 2919: 30 V a.c., 80 C, multi-conductor with a jacket | AWM 2919 |
| 20276 | Style 20276: 30 V a.c., 60 or 80 C, multi-conductor with a jacket | AWM 20276 |
| JP | Joist pull: passed the UL 1277 joist-pull test (NEC 336.10) | TC-ER-JP |
| X | Limited use | CATVX |
| G | General purpose (UL 1685 vertical tray), not for risers or plenums | OFCG |
| CM | Communications cable (NEC 800) | CMUC |
| UC | Under carpet | CMUC |
| CGC | Extensible centre ground-check conductor, stranded to stretch without carrying tensile load | SHD-CGC |
| MP | Mine power feeder cable for permanent installation (Prysmian: Mine Power Feeder) | MP-GC |
Hva typetabellen sier om navnene
Sitert fra typetabellens merknader, med typene de hører til.
- Usually dual-marked THHN/THWN-2 (and MTW when stranded): the reader treats each name as one listing of the same wire. (THHN)
- Romex is Southwire's brand, used as the type name. (NM-B)
- BX is the trade name for AC. (AC)
- C-L-X is Southwire/Okonite's trade name for this build. (MC-HL)
- Written "12/3": 12 AWG, 3 conductors counting the green ground. (S, SO, SOO, SOW, SOOW, SJ +14)
Alle typer i NEC / UL (USA)
| Type | Beskrivelse | Merkedata |
|---|---|---|
TW | Thermoplastic moisture-resistant building wire, 60 C | 600 V, 60 C dry and wet |
THW | Thermoplastic heat- and moisture-resistant building wire, 75 C | 600 V, 75 C dry and wet |
THHW | Thermoplastic high heat-resistant, moisture-resistant building wire | 600 V, 90 C dry, 75 C wet |
THWN | Thermoplastic heat- and water-resistant nylon-coated building wire, 75 C | 600 V, 75 C wet and dry |
THHN | Thermoplastic high heat-resistant nylon-coated building wire | 600 V, 90 C dry and damp locations |
THWN-2 | Thermoplastic heat- and water-resistant nylon-coated building wire, 90 C wet or dry | 600 V, 90 C wet and dry locations |
MTW | Machine tool wire, oil-resistant PVC, 90 C | 600 V, 90 C dry, 60 C wet or oil |
XHH | Thermoset (XLPE) high heat-resistant building wire, dry and damp locations | 600 V, 90 C dry and damp |
XHHW | Thermoset (XLPE) high heat-resistant building wire, wet locations at 75 C | 600 V, 90 C dry, 75 C wet |
XHHW-2 | Thermoset (XLPE) high heat-resistant building wire, 90 C wet or dry | 600 V, 90 C wet and dry |
RHH | Thermoset (rubber-type) high heat-resistant building wire, dry and damp | 600 V, 90 C dry and damp |
RHW | Thermoset (rubber-type) heat- and moisture-resistant building wire, 75 C | 600 V, 75 C dry and wet |
RHW-2 | Thermoset (rubber-type) heat- and moisture-resistant building wire, 90 C wet or dry | 600 V (2 kV on some listings), 90 C wet and dry |
USE | Underground service-entrance conductor (single wire), 75 C | 600 V, 75 C |
USE-2 | Underground service-entrance conductor, 90 C wet or dry | 600 V, 90 C wet and dry |
TBS | Thermoplastic-insulated, braid-covered switchboard wire | 600 V, 90 C |
SIS | Switchboard and control wire, cross-linked polyethylene, 90 C | 600 V, 90 C |
TFFN | Thermoplastic flexible fixture wire, nylon-coated | 600 V, 90 C |
TFN | Thermoplastic fixture wire, nylon-coated (solid conductor) | 600 V, 90 C |
TFF | Thermoplastic flexible fixture wire, no nylon | 600 V, 60 C (UNVERIFIED) |
TF | Thermoplastic fixture wire, no nylon | 600 V, 60 C |
NM-B | Non-metallic sheathed cable, type B (90 C conductors), for dry indoor wiring | 600 V, 90 C conductors (ampacity at the 60 C column) |
UF-B | Underground feeder cable, type B, sunlight-resistant gray jacket, direct burial | 600 V, 90 C conductors (ampacity at the 60 C column) |
SE | Service-entrance cable (general term, SER round or SEU flat) | 600 V, 75 or 90 C |
SER | Service-entrance cable, style R (round), with a bare ground, gray jacket | 600 V, 90 C (XLPE) or 75 C (PVC) |
SEU | Service-entrance cable, style U (flat), with a concentric bare neutral, gray jacket | 600 V, 90 C (XLPE) or 75 C (PVC) |
URD | Underground residential distribution cable, twisted aluminium conductors, direct burial | 600 V, 90 C XLPE |
MOBILE HOME FEEDER | Mobile home feeder: three aluminium alloy conductors and an insulated ground, XLPE insulated (USE-2 / RHH / RHW-2), direct burial | 600 V, 90 C wet or dry |
AC | Armored cable (BX): insulated conductors with a 16 AWG aluminium bond wire in interlocked steel armour, no outer jacket | 600 V, 90 C conductors (AC-90 / ACHH) |
MC | Metal-clad cable: insulated conductors and a green ground in interlocked metal armour | 600 V, 90 C conductors |
MC-HL | Metal-clad cable for hazardous locations: continuous corrugated aluminium sheath and PVC jacket | 600 V or 1000 V, 90 C (XHHW-2) |
TC | Tray cable: multiconductor power or control cable for cable trays | 600 V, 90 C dry, 75 C wet |
TC-ER | Tray cable, exposed run: may run outside tray or conduit up to 6 ft, supported and secured | 600 V, 90 C dry, 75 C wet |
TC-ER-HL | Tray cable, exposed run, hazardous locations | 600 V, 90 C dry, 75 C wet |
ITC | Instrumentation tray cable, shielded pairs, for circuits up to 150 V and 5 A | 300 V |
ITC-ER | Instrumentation tray cable, exposed run | 300 V |
PLTC | Power-limited tray cable, shielded pairs, 300 V | 300 V |
PLTC-ER | Power-limited tray cable, exposed run | 300 V |
MV-90 | Medium-voltage shielded power cable, 90 C | 2 kV to 35 kV, 90 C |
MV-105 | Medium-voltage shielded power cable, 105 C | 2 kV to 35 kV, 105 C |
AEIC-CS9 | High voltage XLPE power cable, single conductor, 69 to 345 kV, as the makers print its legend (size, metal, wall in mils, class) | 69, 115, 138, 161, 230 and 345 kV, 90 C |
S | Standard thermoset flexible cord | 600 V, 90 C |
SO | Standard thermoset flexible cord, oil-resistant | 600 V, 90 C |
SOO | Standard thermoset flexible cord, oil-resistant | 600 V, 90 C |
SOW | Standard thermoset flexible cord, oil-resistant, weather-resistant | 600 V, 90 C |
SOOW | Standard thermoset flexible cord, oil-resistant, weather-resistant | 600 V, 90 C |
SJ | Junior thermoset flexible cord | 300 V, 90 C |
SJO | Junior thermoset flexible cord, oil-resistant | 300 V, 90 C |
SJOW | Junior thermoset flexible cord, oil-resistant, weather-resistant | 300 V, 90 C |
SJOOW | Junior thermoset flexible cord, oil-resistant, weather-resistant | 300 V, 90 C |
SJT | Junior thermoplastic flexible cord | 300 V, 60 to 105 C |
SJTW | Junior thermoplastic flexible cord, weather-resistant | 300 V, 60 to 105 C |
SJTO | Junior thermoplastic flexible cord, oil-resistant | 300 V, 60 to 105 C |
SJTOW | Junior thermoplastic flexible cord, oil-resistant, weather-resistant | 300 V, 60 to 105 C |
SJTOOW | Junior thermoplastic flexible cord, oil-resistant, weather-resistant | 300 V, 60 to 105 C |
ST | Standard thermoplastic flexible cord | 600 V, 60 to 105 C |
STW | Standard thermoplastic flexible cord, weather-resistant | 600 V, 60 to 105 C |
STO | Standard thermoplastic flexible cord, oil-resistant | 600 V, 60 to 105 C |
STOW | Standard thermoplastic flexible cord, oil-resistant, weather-resistant | 600 V, 60 to 105 C |
STOOW | Standard thermoplastic flexible cord, oil-resistant, weather-resistant | 600 V, 60 to 105 C |
SEOW | Standard elastomer flexible cord, oil-resistant, weather-resistant | 600 V, 105 C |
SEOOW | Standard elastomer flexible cord, oil-resistant, weather-resistant | 600 V, 105 C |
SJEOOW | Junior elastomer flexible cord, oil-resistant, weather-resistant | 300 V, 105 C |
SPT-1 | Parallel thermoplastic lamp cord, insulation class 1 | 300 V, 60 to 105 C (UNVERIFIED) |
SPT-2 | Parallel thermoplastic lamp cord, insulation class 2 | 300 V, 60 to 105 C (UNVERIFIED) |
SPT-3 | Parallel thermoplastic lamp cord, insulation class 3 | 300 V, 60 to 105 C (UNVERIFIED) |
SPT | SPT: parallel thermoplastic (zip) cord, two or three conductors moulded side by side in PVC, no jacket; the insulation class (SPT-1, SPT-2 or SPT-3) not given | 300 V; 60 C or 105 C by listing (Southwire, Cerrowire, AWC) |
SVT | Vacuum-cleaner (service) thermoplastic cord, PVC jacket, 300 V | 300 V, 60 to 105 C |
SVTO | Vacuum-cleaner thermoplastic cord with an oil-resistant PVC jacket, 300 V | 300 V, 60 to 105 C |
HPN | Heater cord, parallel, neoprene (UNVERIFIED expansion) | 300 V, 90 C (UNVERIFIED) |
TYPE W | Portable power cable, 2 kV, tinned copper, EPDM insulation, extra-hard usage | 2000 V, 90 C |
TYPE G | Portable power cable with grounding conductors, 2 kV, mining and industrial (UNVERIFIED) | 2000 V, 90 C (UNVERIFIED) |
G-GC | Portable power cable with grounding and a ground-check conductor (UNVERIFIED) | 2000 V, 90 C (UNVERIFIED) |
DLO | Diesel locomotive cable: tinned flexible copper, EPR insulation, CPE jacket, single conductor | 2000 V, 90 C |
PV WIRE | Photovoltaic wire: stranded copper, XLP insulation, sunlight resistant | 600 V or 1000 V or 2000 V, 90 C wet or dry |
CM | Communications cable, general purpose | 300 V, 75 C |
CMP | Communications cable, plenum rated (low smoke; FEP insulation on 4-pair data cable, low-smoke PVC on 2-conductor cable) | 300 V, 60 to 150 C by product (75 C most common) |
CMR | Communications cable, riser rated (vertical shafts, UL 1666) | 300 V, 60 or 75 C by product |
CMG | Communications cable, general purpose (FT4 vertical flame test) | 300 V, 60 C |
CMX | Communications cable, limited use (residential and in raceway, outdoor-rated types) | 300 V, 60 to 75 C |
CL2 | Class 2 remote-control and signalling cable | Class 2 power-limited, no voltage rating (UL 13 1.2) |
THERMOSTAT WIRE | Thermostat wire: Class 2 control cable, solid bare copper conductors in a PVC jacket | 150 V, Class 2 power-limited (as two makers print it) |
LANDSCAPE WIRE | Low voltage landscape lighting wire: underground low-energy circuit cable, two stranded copper conductors in one flat PVC layer | 150 V (UL), 30 V (CSA LVLL); -20 to 60 C; direct burial |
CL2R | Class 2 remote-control and signalling cable, riser | Class 2 power-limited, no voltage rating (UL 13 1.2) |
CL2P | Class 2 remote-control and signalling cable, plenum | Class 2 power-limited, no voltage rating (UL 13 1.2) |
CL2X | Class 2 remote-control and signalling cable, limited use | Class 2 power-limited, no voltage rating (UL 13 1.2) |
CL3 | Class 3 remote-control and signalling cable | 300 V, Class 3 power-limited (UL 13 1.2: rated 300 V, not so marked) |
CL3R | Class 3 remote-control and signalling cable, riser | 300 V, Class 3 power-limited (UL 13 1.2: rated 300 V, not so marked) |
CL3P | Class 3 remote-control and signalling cable, plenum | 300 V, Class 3 power-limited (UL 13 1.2: rated 300 V, not so marked) |
CL3X | Class 3 remote-control and signalling cable, limited use | 300 V, Class 3 power-limited (UL 13 1.2: rated 300 V, not so marked) |
FPL | Fire-alarm power-limited cable | 300 V, 75 C |
FPLR | Fire-alarm power-limited cable, riser (UL 1666) | 300 V, 75 C |
FPLP | Fire-alarm power-limited cable, plenum (UL 910, low smoke) | 300 V, 75 C |
OFN | Optical fibre cable, nonconductive general | Dielectric |
OFNG | Optical fibre cable, nonconductive, general purpose | Dielectric |
OFNR | Optical fibre cable, nonconductive, riser | Dielectric |
OFNP | Optical fibre cable, nonconductive, plenum | Dielectric |
OFC | Optical fibre cable, conductive general | Fibre with metallic strength member |
OFCR | Optical fibre cable, conductive, riser | Fibre with metallic strength member |
OFCP | Optical fibre cable, conductive, plenum | Fibre with metallic strength member |
CAT5E | Category 5e unshielded or shielded twisted-pair data cable, 4 pairs, 24 AWG | up to 100 MHz, 1 Gbit/s |
CAT6 | Category 6 twisted-pair data cable, 4 pairs, 23 AWG | up to 250 MHz |
CAT6A | Category 6A augmented twisted-pair data cable, 4 pairs | up to 500 MHz (UNVERIFIED) |
AWM 1007 | UL AWM style 1007: single-conductor PVC appliance wiring material (hook-up wire) | 300 V a.c., 80 C, 32 to 16 AWG |
AWM 1015 | UL AWM style 1015: single-conductor PVC appliance wiring material (hook-up wire) | 600 V a.c. or 750 V d.c., 80 / 90 / 105 C, 30 AWG to 2000 kcmil |
AWM 2464 | UL AWM style 2464: multi-conductor equipment cable, singles or twisted pairs, often foil and braid screened | 300 V a.c., 80 C |
AWM 2517 | UL AWM style 2517: multi-conductor equipment cable, singles or twisted pairs, often foil and braid screened | 300 V a.c., 105 C |
AWM 2919 | UL AWM style 2919: multi-conductor equipment cable, singles or twisted pairs, often foil and braid screened | 30 V a.c., 80 C |
AWM 20276 | UL AWM style 20276: multi-conductor equipment cable, singles or twisted pairs, often foil and braid screened | 30 V a.c., 60 or 80 C |
VFD | Variable frequency drive cable, Type TC-ER: three XLPE cores, three symmetrical grounds, overall screen | 1000 V or 2000 V, 90 C wet and dry |
TC-ER-JP | Tray cable, exposed run, joist-pull tested (may be pulled through joists in one- and two-family dwellings) | 600 V, 90 C dry, 75 C wet |
CATV | Community antenna television coaxial cable, general use | 75 ohm coaxial (RG-6 / RG-59 builds) |
CATVR | Community antenna television coaxial cable, riser (UL 1666) | 75 ohm coaxial (RG-6 / RG-59 builds) |
CATVP | Community antenna television coaxial cable, plenum (NFPA 262) | 75 ohm coaxial (RG-6 / RG-59 builds) |
CATVX | Community antenna television coaxial cable, limited use (dwellings, raceway) | 75 ohm coaxial (RG-6 / RG-59 builds) |
CMP-LP | Communications cable, plenum rated (low smoke, FEP insulation), limited power (LP): marked with the current per conductor for PoE | 300 V, 75 C |
CMR-LP | Communications cable, riser rated (vertical shafts, UL 1666), limited power (LP): marked with the current per conductor for PoE | 300 V, 75 C |
CMG-LP | Communications cable, general purpose (same listing level as CM), limited power (LP): marked with the current per conductor for PoE | 300 V, 60 to 75 C |
CM-LP | Communications cable, general purpose, limited power (LP): marked with the current per conductor for PoE | 300 V, 60 to 75 C |
OFCG | Optical fibre cable, conductive, general purpose | Fibre with metallic strength member |
NPLF | Non-power-limited fire alarm cable, general | 600 V (typical) |
NPLFR | Non-power-limited fire alarm cable, riser | 600 V (typical) |
NPLFP | Non-power-limited fire alarm cable, plenum | 600 V (typical) |
ITC-HL | Instrumentation tray cable, shielded pairs, for circuits up to 150 V and 5 A, hazardous location: continuously welded corrugated aluminium sheath and a PVC jacket | 300 V |
PLTC-HL | Power-limited tray cable, shielded pairs, 300 V, hazardous location: continuously welded corrugated aluminium sheath and a PVC jacket | 300 V |
CMUC | Communications under-carpet cable: flat conductors for use under carpet squares | communications |
SHD-GC | SHD-GC: shielded round portable mine power cable, three EPR phase cores each under a tinned copper / textile braid shield, two grounding conductors and a yellow ground-check conductor, reinforced CPE jacket | 2000 V to 35000 V classes, 90 C (Prysmian); 5 kV, 8 kV, 15 kV (Priority Wire) |
SHD-CGC | SHD-CGC: SHD-GC with an extensible (centre) ground-check conductor and three grounding conductors, 2000 to 5000 V | 2000 V and 5000 V, 90 C (Prysmian) |
MP-GC | MP-GC: mine power feeder cable with ground check, three shielded EPR (or XLP) cores with copper tape shields, two grounding conductors and a ground-check conductor, CPE (or PVC) jacket, 5 to 35 kV, for permanent installation | 5000 V to 35000 V, 90 C, 100 % insulation level (Prysmian, Tele-Fonika) |
ALPETH | ALPETH: aerial telephone cable with an aluminium shield and a polyethylene jacket | telephone |
ALVYN | ALVYN: indoor riser-rated telephone cable with an aluminium shield and a vinyl (PVC) jacket | telephone |
ASP | ASP: filled direct-burial telephone cable for rodent areas, corrugated aluminium shield, corrugated steel tape, flooding compound, polyethylene jacket | telephone |
PIC | PIC: plastic-insulated telephone cable (a general term for any type) | telephone |
Merkinger ved siden av navnet
Ord og merkinger som dekoderen leser ved siden av et typenavn i dette systemet: hver av dem legger til en egenskap på typen den står ved siden av.
| Merking | Betydning | Skrives som |
|---|---|---|
| 100% | Insulation level 100 %: ground faults cleared within one minute (ICEA) | 100% 100 % 100% INSULATION 100 PERCENT |
| 133% | Insulation level 133 %: ground faults cleared within one hour (ICEA) | 133% 133 % 133% INSULATION 133 PERCENT |
| 173% | Insulation level 173 %: ground faults may last longer than one hour (ICEA) | 173% 173 % 173% INSULATION |
| JCN | Jacketed concentric neutral: copper wire neutral under an overall jacket | JCN |
Vanlige spørsmål
Hva er kabelen THW?
THW: Thermoplastic heat- and moisture-resistant building wire, 75 C. Merkedata: 600 V, 75 C dry and wet. Standard: UL 83; NEC Article 310. Navnet leses: T (Thermoplastic (PVC) insulation) + H (Heat resistant, 75 C (one H)) + W (Approved for wet locations).
Hva er kabelen AEIC-CS9?
AEIC-CS9: High voltage XLPE power cable, single conductor, 69 to 345 kV, as the makers print its legend (size, metal, wall in mils, class). Merkedata: 69, 115, 138, 161, 230 and 345 kV, 90 C. Standard: AEIC CS9-06 (1st edition, 2006); ICEA S-108-720.
Hva er forskjellen mellom THHN og TFFN?
THHN: Thermoplastic high heat-resistant nylon-coated building wire, 600 V, 90 C dry and damp locations. TFFN: Thermoplastic flexible fixture wire, nylon-coated, 600 V, 90 C. Navnene skiller seg i: THHN: HH (High heat resistant, 90 C (one H means 75 C)); TFFN: FF (Flexible fixture (stranded) wire).
NEC / UL (USA): hva betyr T i et kabelnavn?
T har mer enn én betydning, avhengig av typen: Thermoplastic (PVC) insulation (TW, THW, THHW, THWN +6); Thermoplastic (PVC) insulation and jacket (SJT, SJTW, SJTO, SJTOW +6); Thermoplastic (PVC) (SPT-1, SPT-2, SPT-3, SPT +1).
NEC / UL (USA): hva betyr 100% ved siden av et kabelnavn?
100%: Insulation level 100 %: ground faults cleared within one minute (ICEA). Skrives som 100%, 100 %, 100% INSULATION, 100 PERCENT.
Hva er kabelen THHN?
THHN: Thermoplastic high heat-resistant nylon-coated building wire. Merkedata: 600 V, 90 C dry and damp locations. Standard: UL 83; NEC Article 310. Navnet leses: T (Thermoplastic (PVC) insulation) + HH (High heat resistant, 90 C (one H means 75 C)) + N (Nylon outer covering).
Typetabellens kilder
Standarder som nevnes i tabellen
- UL 83
- NEC Article 310
- UL 1063
- NEC Article 670
- UL 44
- UL 854
- NEC Article 338
- NEC Table 310.104(A)
- UL 66
- NEC Article 402
- UL 719
- NEC Article 334
- UL 493
- NEC Article 340
- ICEA / NEMA WC 70
- UL 854 (USE-2)
- UL 4
- NEC Article 320
- UL 1569
- NEC Article 330
- UL 2225 (UNVERIFIED)
- NEC Articles 330 and 501 to 505
- UL 1277
- NEC Article 336
- UL 2250
- NEC Article 727
- UL 13
- NEC Article 725
- UL 1072
- NEC Article 311
- AEIC CS9-06 (1st edition, 2006)
- ICEA S-108-720
- UL 62
- NEC Article 400, Table 400.4
- NEC Table 400.4
- UL Subject 1680
- CSA C22.2 No. 96
- NEC Article 400 (also 520, 525, 530)
- UL 1650
- NEC Article 400
- UL RHH/RHW-2 (600 V and 2000 V)
- ICEA S-95-658 / NEMA WC 70
- AAR RP-586 and RP-588
- CSA RW90 and RW90-TC
- UL 4703
- NEC Article 690
- UL 444
- NEC Article 800
- NEC 800.179(A)
- NEC 800.179(B)
- UL 444 / CSA C22.2 No. 214
- UL 13 (power-limited circuit cable)
- NEC Article 725, Class 2
- UL 1493 (underground low-energy circuit cable for outdoor lighting)
- CSA LVLL
- UL 1424
- NEC Article 760
- UL 1651
- NEC Article 770
- ANSI/TIA-568 Category 5e
- ANSI/TIA-568 Category 6
- ANSI/TIA-568 Category 6A
- UL 758 (AWM style page)
- UL 1277 TC-ER
- UL 1655
- NEC Article 820 (820.179)
- UL 1425
- NEC Article 760 Part II
- ICEA S-75-381 / NEMA WC 58
- MSHA accepted
- MSHA P-7K-102045-2
- MSHA
- REA / RUS telephone cable practice (General Cable glossary)
- General Cable glossary
Dokumenter og sider opplysningene er hentet fra
- toolgrit.com/guides/cable-type-decoder-guide
- iaeimagazine.org/electrical-inspections/article-310-conductors-for-gene…
- southwire.com/wire-cable/building-wire/simpull-sup-sup-thhn-thwn-2-copp…
- southwire.com/wire-cable/building-wire/simpull-xhhw-2-sup-sup-rw90-copp…
- southwire.com/wire-cable/building-wire/rhh-rhw-2-use-2-copper-silicone-…
- nassaunationalcable.com/products/4-0-awg-aluminum-xlp-use-2-rhh-rhw-2-d…
- nassaunationalcable.com/en-ca/products/switchboard-wire-strand-tinned-c…
- nassaunationalcable.com/en-ca/products/16-26-tffn-conductor
- awcwire.com/product/tffn-16-26
- awcwire.com/product/tfn-16-1
- cabletechsupport.southwire.com/cablespec/download_spec
- mp-pdfv13.ae-admin.com/omnicable/files/AutoSpec_TFFN_TFN_90_C_600_Volt.…
- central-america.prysmian.com/sites/default/files/atoms/files/PG_Catalog…
- phelpsdodge.com.ph
- nassaunationalcable.com/en-ca/products/12-2-w-grnd-nm-b-600v-solid-yell…
- southwire.com/wire-cable/building-wire/romex-brand-simpull-type-nm-b-ca…
- nassaunationalcable.com/products/12-2-uf-b-solid-copper-underground-fee…
- southwire.com/wire-cable/building-wire/ser-aluminum-service-entrance/p/…
- nassaunationalcable.com/products/500-4-4-4-6-copper-ser-service-entranc…
- southwire.com/wire-cable/building-wire/seu-aluminum-service-entrance/p/…
- nassaunationalcable.com/products/250-6-6-6-bare-concentric-ground-servi…
- nassaunationalcable.com/products/4-4-4-vassar-triplex-aluminum-conducto…
- cabletechsupport.southwire.com/tile/50/spec/10054
- na.prysmian.com/sites/na.prysmian.com/files/media/documents/STABILOY Br…
- nassaunationalcable.com/en-ca/products/ac-90-interlocked-galvanized-ste…
- ecmweb.com/national-electrical-code/code-basics/article/55270510/nec-re…
- nassaunationalcable.com/en-ca/products/12-2c-solid-copper-mc-lite-thhn-…
- southwire.com/wire-cable/metal-clad-cable/armorlite-type-mc/p/57875405
- nassaunationalcable.com/products/546-31-3403-c-l-x-type-mc-hl-xhhw-2-14…
- southwire.com/wire-cable/power-control/unshielded-multiconductor-600v-2…
- distributorwire.com/blogs/what-is-tray-cable-a-complete-guide-for-elect…
- ecmweb.com/national-electrical-code/article/20900170/type-tc-vs-type-tc…
- nassaunationalcable.com/products/12-awg-4c-shielded-vntc-tray-cable-tc-…
- nassaunationalcable.com/products/16-awg-2p-pltc-instrumentation-tray-ca…
- nassaunationalcable.com/products/2-awg-3c-aluminum-mv-105-tape-shielded…
- okonite.com/media/catalog/product/files/2-13.pdf
- cabletechsupport.southwire.com/cablespec/download_spec
- cabletechsupport.southwire.com/cablespec/download_spec
- okonite.com/media/catalog/product/files/2-9.pdf
- cabletechsupport.southwire.com/cablespec/download_spec
- na.prysmian.com/sites/na.prysmian.com/files/media/documents/Uniblend® P…
- southwire.com/wire-cable/high-voltage-underground-69kv-and-up-/high-vol…
- southwire.com/wire-cable/high-voltage-underground-69kv-and-up-/high-vol…
- southwire.com/wire-cable/high-voltage-underground-69kv-and-up-/high-vol…
- forum.digikey.com/t/ul-common-cord-style-designations/29509
- nassaunationalcable.com/en-ca/products/12-3-soow-yellow-portable-cord-6…
- southwire.com/wire-cable/flexible-cord/600v-royal-soow-cord-control-wit…
- nassaunationalcable.com/products/12-4-300v-black
- awcwire.com/power-cable-and-portable-cord/sjt-and-svt/sjt
- nassaunationalcable.com/collections/sjtow-stow-portable-cord
- condelmex.com/product-page/cordon-flexible-uso-extrarudo-tipo-seow-90-c…
- southwire.com/wire-cable/flexible-cord/300v-seoprene-plus-sjeoow-cord-w…
- awcwire.com/product/spt-2-18_2
- awcwire.com/product/spt-3-18_2
- cerrowire.com/wp-content/uploads/2023/04/CW-Lamp-Wire_sheet_60C_230629.…
- media.iewc.com/SpecificationSheets/SPT-1-SPT-2-SPT-3-Lamp-Cord.pdf
- awcwire.com/power-cable-and-portable-cord/sjt-and-svt/svt/svt-18_2
- nassaunationalcable.com/products/4-0-4-type-w-multi-conductor-2kv-porta…
- nassaunationalcable.com/products/10-awg-ul-csa-55amp-black-portable-dlo…
- nassaunationalcable.com/products/10-awg-7-strands-copper-building-solar…
- cabletechsupport.southwire.com/cablespec/download_spec
- kristechwire.com/files/2026/05/KTW-STD-00005D-PV-Wire.pdf
- ecmweb.com/national-electrical-code/code-basics/article/20890128/articl…
- nassaunationalcable.com/en-ca/products/16-awg-2c-audacious-sound-riser-…
- nassaunationalcable.com/en-ca/products/24-awg-4-pair-cmx-shielded-cat5e…
- awcwire.com/general-cable-carol-brand-communication-and-control-cable/c…
- zoro.com/static/cms/enhanced_pdf/Prem Magnetics Inc dba Remington Indus…
- nassaunationalcable.com/en-ca/products/24-awg-4-pair-cmp-shielded-cat5e…
- southwire.com/wire-cable/genesis-cable/category-6-cable-plenum/p/636111…
- cabletechsupport.southwire.com/tile/31/spec/13076
- nassaunationalcable.com/products/4-pair-23-awg-riser-cat6-premise-solid…
- southwire.com/wire-cable/low-voltage-cable/multi-conductor-cl3r-fplr-cm…
- na.prysmian.com/sites/na.prysmian.com/files/media/documents/GenSPEED® 6…
- s3.amazonaws.com/s3.supplyhouse.com/product_files/Southwire-552020507-S…
- images.thdstatic.com/catalog/pdfImages/36/36984981-2640-4d88-a1c5-13317…
- cdn.shopify.com/s/files/1/0517/1760/3528/files/SPEC70827-ULEC-LVLL.pdf
- images.homedepot-static.com/catalog/pdfImages/da/da60b80a-3fea-45f1-939…
- windycitywire.com/blogs/fplp-vs-fplr-cable-what-s-the-difference-and-wh…
- southwire.com/wire-cable/low-voltage-cable/fire-alarm-fplp-solid-shield…
- nassaunationalcable.com/products/corning-012t81-33180-24-12-fiber-om3-r…
- iq.ul.com/awm/stylepage.aspx
- iq.ul.com/awm/stylepage.aspx
- iq.ul.com/awm/stylepage.aspx
- iq.ul.com/awm/stylepage.aspx
- iq.ul.com/awm/stylepage.aspx
- iq.ul.com/awm/stylepage.aspx
- southwire.com/wire-cable/power-control/flexible-cu-2000v-xlpe-insulatio…
- belden.com/products/cable/vfd-cable/29536
- ecmweb.com/national-electrical-code/qa/article/20903240/code-qa-permitt…
- standards.globalspec.com/std/14549402/ul-1655
- ecmweb.com/national-electrical-code/code-basics/article/20885527/articl…
- cablinginstall.com/standards/article/14276764/revisions-to-cable-requir…
- datasheets.globalspec.com/ds/uls/ul-444/0307f0ac-d5f2-4b28-a0bc-4e18727…
- corning.com/catalog/coc/documents/application-engineering-notes/AEN071.…
- standards.globalspec.com/std/14549991/ul-1651
- datasheets.globalspec.com/ds/ULS/ul-1425/aa6f7398-826b-4226-85f3-22d13c…
- wiringharnessnews.com/wire-wisdom-anixter-march-april-2019-armored-cabl…
- shawflex.com/wp-content/uploads/2023/05/UL-Type-PLTC_ITC-Armored-Instru…
- nassaunationalcable.com/products/16-24-pair-instrumentation-mc-hl
- na.prysmian.com/sites/na.prysmian.com/files/media/documents/INS-0044-R1…
- prioritywire.com/specs/Type SHD-GC 5KV.pdf
- Tele-Fonika Kable export catalogue 2008, mining cable table
- tele-fonika.us/storage/file/core_files/2025/3/25/78a936722b8b9839bb7cfa…
- General Cable 'Abbreviations and Acronyms', Technical Information p.209
- amercable.com/storage/2025/02/MV-105-1_25.pdf
- w3prep.intertek.com/siteassets/resources/sun/2023/ul-1072-sun-rev-3-16-…
- ecmweb.com/design/medium-voltage-cable-insulation-ratings
- standards.globalspec.com/std/14542463/ul-1072
Hentet fra dette nettstedets typetabell, med kildene ovenfor. Kontroller produsentens datablad før du spesifiserer en kabel.
Veiledning for forlegning og håndtering: Nordamerikanske kabler