N2XH 3x1,5 RE 0,6/1 kV

IEC nominal calculation, not manufacturer data. The thicknesses are the nominal values of the construction standards, added up layer by layer. A manufacturer's cable of the same name can differ by a few millimetres and by 10 to 20 % in weight: always check its datasheet before you specify, order or lay a cable.

By the IEC construction rules, N2XH 3x1,5 RE 0,6/1 kV comes to an overall diameter of about 11.6 mm and a weight of about 170 kg/km.

Open this cable in the designer Change any layer, see it in 3D and to scale, and download it.

Main dimensions

ConductorCopper 1.5 mm² RE, Ø 1.4 mmsolid, from the nominal section (IEC 60228 class 1)
InsulationXLPE 0.7 mmIEC 60502-1:2004 Tables 5-7, nominal insulation thickness
Diameter over insulation2.8 mm
Core diameter2.8 mm
Overall diameter11.6 mm
Weight (approximate)170 kg/km

Round conductors (IEC 60228 class 2 compacted; class 1 solid up to 10 mm²).

Layer by layer (inside out)

#LayerMaterialThickness mmØ over mmSourceHow firmly
1InsulationXLPE0.72.8 (on each core)IEC 60502-1:2004 Tables 5-7, nominal insulation thicknessas manufacturers publish it, table not read
2FillerPPfills the space between the cores6.0
3Inner covering / beddingHalogen-free (LSZH)1.08.0IEC 60502 Table 8, extruded inner covering by the fictitious diameter over the laid-up cores (Annex A)read in the standard
4SheathHalogen-free (LSZH)1.811.6IEC 60502 clause 13 / 14.3, oversheath: 0.035 D + 1.0 mm, D the fictitious diameter (Annex A)read in the standard

Diameters add up the nominal layers. Where IEC 60502 sizes a layer by the fictitious diameter of its Annex A, the calculated diameter is used instead, which can move a value one step. Low voltage insulation (IEC 60502-1) is as manufacturers publish it; the table itself was not read. Sources and page numbers: research/mv-dimensions in the site repository.

Weight, by part

Conductors40 kg/km
Metal screens and armour0 kg/km
Insulation, semicon, tapes, fillers and sheaths130 kg/km
Total170 kg/km

Each layer's cross-section times its density; stranded conductors, laid-up cores and helical wires count 2 % longer than the cable. Densities: copper 8.89 and aluminium 2.703 g/cm³ (the values of IEC 60028 and IEC 60889); XLPE 0.92, PE 0.94, PVC 1.45, semicon 1.12, steel 7.85 g/cm³ (usual compound values).

N2XH