# YMvK

**YMvK** is a [NEN / KEMA type names (Netherlands)](https://thecablecode.com/standards/nen-kema-types) cable designation: Y = Cross-linked polyethylene (XLPE) insulation; MvK = PVC Sheathed Cable; YMvK = YMvK: Dutch 0,6/1 kV power and control cable for fixed installation, copper conductors in XLPE insulation, a filler sheath and a grey PVC outer sheath, no armour or screen. 0,6/1 kV, 90 C conductor, 250 C short circuit (Waskönig), test voltage 3,5 kV (TKF). HD 604 Part 4 Section D; KEMA 42 C-1-4-D (Nexans Nederland); KEMA-KEUR, installed to NEN 1010.

2 coding systems recognise this code

**Standards behind these values:**

- IEC 60502-1:2004 (edition 2.0): Power cables with extruded insulation and their accessories for rated voltages from 1 kV (Um = 1,2 kV) up to 30 kV (Um = 36 kV) - Part 1: Cables for rated voltages of 1 kV (Um = 1,2 kV) and 3 kV (Um = 3,6 kV)
- IEC 60228:2023 (edition 4.0): Conductors of insulated cables

## NEN / KEMA type names (Netherlands)

| Symbol | Meaning |
|---|---|
| `Y` | Cross-linked polyethylene (XLPE) insulation |
| `MvK` | PVC Sheathed Cable |
| `YMvK` | YMvK: Dutch 0,6/1 kV power and control cable for fixed installation, copper conductors in XLPE insulation, a filler sheath and a grey PVC outer sheath, no armour or screen. 0,6/1 kV, 90 C conductor, 250 C short circuit (Waskönig), test voltage 3,5 kV (TKF). HD 604 Part 4 Section D; KEMA 42 C-1-4-D (Nexans Nederland); KEMA-KEUR, installed to NEN 1010 |

## NEN 3207 / KEMA (Netherlands)

| Symbol | Meaning |
|---|---|
| `Y` | Cross-Linked Polyethylene (XLPE) |
| `MvK` | PVC Sheathed Cable |

[How to read a NEN 3207 / KEMA (Netherlands) cable code](https://thecablecode.com/guides/kema)

## YMvK: equivalents in other countries

Shown for 3x16 0.6/1 kV. Each country's rules are applied to this build, keeping the conductor, section, cores, voltage, screen, armour and sheath.

| Country | Standard | Name in that country | Verdict | Differences |
|---|---|---|---|---|
| Germany | HD 603 5-G (DIN VDE 0276-603) | [N2XY](https://thecablecode.com/c/N2XY) 3x16 RM 0,6/1 kV | **Equivalent** | every value the same |
| South Africa | SANS 1507-4 | no letters for this build | **Close** | Inner covering / bedding 1 → 0.8 mm; Sheath 1.8 → 1.6 mm; Wire armour material: only in the equivalent; Overall diameter 19.17 → 20.17 mm |
| India | IS 7098 (Part 1) | [2XY](https://thecablecode.com/c/2XY) 3x16 1100 V | **Close** | rated 0.635/1.1 kV (same Um 1.2 kV); routine voltage test 3 kV a.c., 5 min (this cable 3.5 kV; IS 1554 (Part 1) cl. 16.2, IS 7098 (Part 1) cl. 17.2.1, IEC 60502-1 Table 11); Inner covering / bedding 1 → 0.3 mm; Overall diameter 19.17 → 17.77 mm |

No equivalent in: BS 5467 (armoured cables only); BS 6724 (armoured cables only, asks another sheath compound); BS 7846 (armoured cables only, asks another sheath compound).

Nominal values computed by each standard's rules, not manufacturer data. This is not a statement that two cables are interchangeable: the buyer's specification and the maker's type test decide.

- [YMvK cable: meaning, layers and 3D view](https://thecablecode.com/c/YMvK)
- [Design YMvK in the cable designer: layers, diameter and weight](https://thecablecode.com/design/YMvK)
- [More NEN / KEMA type names (Netherlands) designations](https://thecablecode.com/standards/nen-kema-types)

## Related cables

- [VO-YMvK](https://thecablecode.com/c/VO-YMvK)
- [V4G-YMvK](https://thecablecode.com/c/V4G-YMvK)
- [V4G-YMvK sszh](https://thecablecode.com/c/V4G-YMvK%20sszh)
- [VG-YMvK](https://thecablecode.com/c/VG-YMvK)
- [YMvKas](https://thecablecode.com/c/YMvKas)
- [YMvKrv](https://thecablecode.com/c/YMvKrv)
- [YMvKmb](https://thecablecode.com/c/YMvKmb)
- [VG-YMvK ss](https://thecablecode.com/c/VG-YMvK%20ss)
- [VG-YMvK zh](https://thecablecode.com/c/VG-YMvK%20zh)
- [V-YMvKsas](https://thecablecode.com/c/V-YMvKsas)
- [VO-YMvKas](https://thecablecode.com/c/VO-YMvKas)