title: "YKSLY cable: meaning, layers and 3D view"
code: "YKSLY"
url: https://thecablecode.com/c/YKSLY
language: en
---

# YKSLY

**YKSLY** is a [PN (Poland)](https://thecablecode.com/standards/pn) cable designation: Y = PVC sheath (variants Yc heat-resistant, Yo oil-resistant, Yn self-extinguishing); KS = Signalling / control cable family (K cable, S signalling); L = Stranded copper conductor; Y = PVC insulation; YKSLY = YKSLY: control / signalling cable, stranded copper cores, PVC / PVC (Y, Yc, Yo or Yn sheath variants), 300/500 V and 0,6/1 kV. 300/500 V (also 0,6/1 kV). Elpar ARCONTROL range (standard number not named by the pages read).

1 coding system recognises this code

**Standards behind these values:**

- IEC 60502-1:2004 (edition 2.0): Power cables with extruded insulation and their accessories for rated voltages from 1 kV (Um = 1,2 kV) up to 30 kV (Um = 36 kV) - Part 1: Cables for rated voltages of 1 kV (Um = 1,2 kV) and 3 kV (Um = 3,6 kV)
- IEC 60228:2023 (edition 4.0): Conductors of insulated cables

## PN (Poland)

| Symbol | Meaning |
|---|---|
| `Y` | PVC sheath (variants Yc heat-resistant, Yo oil-resistant, Yn self-extinguishing) |
| `KS` | Signalling / control cable family (K cable, S signalling) |
| `L` | Stranded copper conductor |
| `Y` | PVC insulation |
| `YKSLY` | YKSLY: control / signalling cable, stranded copper cores, PVC / PVC (Y, Yc, Yo or Yn sheath variants), 300/500 V and 0,6/1 kV. 300/500 V (also 0,6/1 kV). Elpar ARCONTROL range (standard number not named by the pages read) |

## YKSLY: equivalents in other countries

Shown for 1x16 0.6/1 kV. Each country's rules are applied to this build, keeping the conductor, section, cores, voltage, screen, armour and sheath.

| Country | Standard | Name in that country | Verdict | Differences |
|---|---|---|---|---|
| Germany | HD 603 3-G (DIN VDE 0276-603) | [NYY](https://thecablecode.com/c/NYY) 1x16 RM 0,6/1 kV | **Close** | Sheath 1.4 → 1.8 mm; Overall diameter 9.7 → 10.5 mm; this cable as built misses 2 of its rules |
| India | IS 1554 (Part 1) | [YY](https://thecablecode.com/c/YY) 1x16 1100 V (the code letters of IS 1554 (Part 1):1988 cl. 17.3) | **Close** | rated 0.635/1.1 kV (same Um 1.2 kV); routine voltage test 3 kV a.c., 5 min (this cable 3.5 kV; IS 1554 (Part 1) cl. 16.2, IS 7098 (Part 1) cl. 17.2.1, IEC 60502-1 Table 11); Sheath 1.4 → 1.8 mm; Overall diameter 9.7 → 10.5 mm; this cable as built misses 1 of its rules |

Nominal values computed by each standard's rules, not manufacturer data. This is not a statement that two cables are interchangeable: the buyer's specification and the maker's type test decide.

- [YKSLY cable: meaning, layers and 3D view](https://thecablecode.com/c/YKSLY)
- [Design YKSLY in the cable designer: layers, diameter and weight](https://thecablecode.com/design/YKSLY)
- [More PN (Poland) designations](https://thecablecode.com/standards/pn)

## Related cables

- [YSLY](https://thecablecode.com/c/YSLY)
- [YKSY](https://thecablecode.com/c/YKSY)