title: "YAXC8V-R cable: meaning, layers and 3D view"
code: "YAXC8V-R"
url: https://thecablecode.com/c/YAXC8V-R
language: en
---

# YAXC8V-R

**YAXC8V-R** is a [TS 621 / TSE (Turkey)](https://thecablecode.com/standards/ts-621) cable designation: Y = Underground Heavy-Duty Cable For Fixed Installation (Y Cable Family, TS 212); A = Aluminium Conductor; X = Cross-Linked Polyethylene (XLPE) Insulation; C8 = Copper Wire Screen Over Each Core; V = Polyvinyl Chloride (PVC); -R = Round Stranded Conductor (Class 2).

2 coding systems recognise this code

**Standards behind these values:**

- IEC 60502-2:2014 (edition 3.0): Power cables with extruded insulation and their accessories for rated voltages from 1 kV (Um = 1,2 kV) up to 30 kV (Um = 36 kV) - Part 2: Cables for rated voltages from 6 kV (Um = 7,2 kV) up to 30 kV (Um = 36 kV)
- IEC 60228:2023 (edition 4.0): Conductors of insulated cables

## TS 621 / TSE (Turkey)

| Symbol | Meaning |
|---|---|
| `Y` | Underground Heavy-Duty Cable For Fixed Installation (Y Cable Family, TS 212) |
| `A` | Aluminium Conductor |
| `X` | Cross-Linked Polyethylene (XLPE) Insulation |
| `C8` | Copper Wire Screen Over Each Core |
| `V` | Polyvinyl Chloride (PVC) |
| `-R` | Round Stranded Conductor (Class 2) |

[How to read a TS 621 / TSE (Turkey) cable code](https://thecablecode.com/guides/ts-621)

## HAR: HD 361 harmonised designation (CENELEC)

| Symbol | Meaning |
|---|---|
| `Y` | Turkish TS Type For Medium And Heavy Operating Conditions (e.g. YXC7V-R) |
| `A` | Concentric Aluminium Conductor |
| `X` | Cross-Linked Polyethylene (XLPE) |
| `C8` | Copper Screen, Over Individual Core |
| `V` | Polyvinyl Chloride (PVC) |
| `-R` | Multi-Wire, Round-Section, Class 2 |

[How to read a HAR: HD 361 harmonised designation (CENELEC) cable code](https://thecablecode.com/guides/har)

## YAXC8V-R: equivalents in other countries

Shown for 1x95/16 12/20 kV. Each country's rules are applied to this build, keeping the conductor, section, cores, voltage, screen, armour and sheath.

| Country | Standard | Name in that country | Verdict | Differences |
|---|---|---|---|---|
|  | HD 620 S3 10-L | no letters for this build | **Equivalent** | every value the same |
| Denmark | HD 620 S3 10-D | no letters for this build | **Close** | screen 16 → 25 mm² (HD 620 10-D Table 1); this cable as built misses 1 of its rules |
| Norway | HD 620 S3 10-K | [TXSP](https://thecablecode.com/c/TXSP) 24 kV 1 x 95 mm2 A (provisional code designation of HD 620 10-K Table 4; X is not explained in the standard) | **Close** | screen 16 → 25 mm² (HD 620 10-K Table 1); Overall diameter 30.7 → 29.9 mm; this cable as built misses 1 of its rules |
| Germany | HD 620 S3 10-C (DIN VDE 0276-620) | [NA2XSY](https://thecablecode.com/c/NA2XSY) 1x95 RM/16 12/20 kV | **Close** | Insulation screen (semicon) 0.8 → 0.6 mm; Sheath 1.9 → 2.5 mm; Overall diameter 30.7 → 31.5 mm; this cable as built misses 3 of its rules |
| Sweden | HD 620 S3 10-M | AXCKJ 1x95/25 12/20 (24) kV (NKT writes a near build without the C (AXLJ)) | **Close** | screen 16 → 25 mm² (HD 620 10-M Tables 1A, 2A, 3A); Insulation screen (semicon) 0.8 → 0.6 mm; Overall diameter 30.7 → 29.5 mm; this cable as built misses 2 of its rules |
| Netherlands | HD 620 S3 10-J | YMvKrvas 12/20 kV 1x95 Al rs +as25 (key read from a maker (Nedkab), the NEN text not seen) | **Close** | screen 16 → 25 mm² (HD 620 10-J Table A.1); Sheath 1.9 → 2.5 mm; Overall diameter 30.7 → 31.9 mm; this cable as built misses 2 of its rules |
| Europe | HD 620 S3 10-N | no letters for this build | **Close** | Insulation 5.5 → 4.8 mm; Sheath material PVC → PE; Sheath 1.9 → 1.8 mm; Overall diameter 30.7 → 29.1 mm |
| Europe | HD 620 S3 10-P | no letters for this build | **Close** | Wire screen material: not in the equivalent; Sheath 1.9 → 2.7 mm; Tape screen material: only in the equivalent; Overall diameter 30.7 → 30.9 mm; this cable as built misses 1 of its rules |
| United Kingdom | HD 620 S3 10-O | no letters for this build | **Close** | rated 12.7/22 kV (same Um 24 kV); Conductor screen (semicon) 0.6 → 0.7 mm; Insulation screen (semicon) 0.8 → 0.5 mm; Wire screen wire diameter 0.7 → 1.04 mm; this cable as built misses 1 of its rules |
| Spain | HD 620 S3 10-E1 | [RHZ1-OL](https://thecablecode.com/c/RHZ1-OL) 12/20 kV 1 x 95 K Al + H16 | **Close** | Conductor screen (semicon) 0.6 → 0.5 mm; Insulation screen (semicon) 0.8 → 0.5 mm; Sheath material PVC → LSZH; Sheath 1.9 → 2.7 mm; this cable as built misses 1 of its rules |
| India | IS 7098 (Part 2) | [A2XY](https://thecablecode.com/c/A2XY) 1x95 12.7/22 kV | **Close** | rated 12.7/22 kV (same Um 24 kV); Insulation 5.5 → 6 mm; Wire screen material: not in the equivalent; Sheath 1.9 → 2.2 mm; this cable as built misses 2 of its rules |
| Spain | HD 620 S3 10-E2 | no letters for this build | **Close** | Conductor screen (semicon) 0.6 → 0.5 mm; Insulation 5.5 → 4.9 mm; Insulation screen (semicon) 0.8 → 0.5 mm; Wire screen material: not in the equivalent; this cable as built misses 2 of its rules |
| Italy | HD 620 S3 10-I1 | [ARE4H5EX](https://thecablecode.com/c/ARE4H5EX) 12/20 kV 1 x 95 | **Close** | Insulation 5.5 → 4.31 mm; Insulation screen (semicon) 0.8 → 0.6 mm; Wire screen material: not in the equivalent; Sheath material PVC → PE; this cable as built misses 2 of its rules |
| Italy | HD 620 S3 10-I2 | [ARE4H5EX](https://thecablecode.com/c/ARE4H5EX) 12/20 kV 1 x 95 | **Close** | Insulation 5.5 → 4.3 mm; Insulation screen (semicon) 0.8 → 0.6 mm; Wire screen material: not in the equivalent; Sheath material PVC → PE; this cable as built misses 1 of its rules |
|  | HD 620 S3 10-G | no letters for this build | **Close** | Insulation 5.5 → 4.4 mm; Wire screen material: not in the equivalent; Sheath material PVC → PE; Sheath 1.9 → 1.8 mm |

No equivalent in: BS 6622 (armoured cables only); HD 620 S3 10-I3 (the size, cores or voltage would change).

Nominal values computed by each standard's rules, not manufacturer data. This is not a statement that two cables are interchangeable: the buyer's specification and the maker's type test decide.

- [YAXC8V-R cable: meaning, layers and 3D view](https://thecablecode.com/c/YAXC8V-R)
- [Design YAXC8V-R in the cable designer: layers, diameter and weight](https://thecablecode.com/design/YAXC8V-R)
- [More TS 621 / TSE (Turkey) designations](https://thecablecode.com/standards/ts-621)

## Related cables

- [YAXC7V-R](https://thecablecode.com/c/YAXC7V-R)
- [YXC8V-R](https://thecablecode.com/c/YXC8V-R)
- [YXC7V-R](https://thecablecode.com/c/YXC7V-R)
- [YAXV-R](https://thecablecode.com/c/YAXV-R)
- [YXC4V-R](https://thecablecode.com/c/YXC4V-R)
- [YXC2V-R](https://thecablecode.com/c/YXC2V-R)
- [YXC3V-R](https://thecablecode.com/c/YXC3V-R)
- [YXC5V-R](https://thecablecode.com/c/YXC5V-R)
- [YXC6V-R](https://thecablecode.com/c/YXC6V-R)
- [YXCV-R](https://thecablecode.com/c/YXCV-R)