title: "NHXMH cable: meaning, layers and 3D view"
code: "NHXMH"
url: https://thecablecode.com/c/NHXMH
language: en
---

# NHXMH

**NHXMH** is a [DIN VDE type names (Germany)](https://thecablecode.com/standards/de-trade-names) cable designation: N = German national (VDE) type; HX = Crosslinked polyethylene insulation 2XI1 (DIN VDE 0276-604), halogen-free: 0,5 mm at 1,5 and 2,5 mm², 0,6 at 4 and 6, 0,7 at 10 and 16, 0,9 at 25 and 35 mm² (DIN VDE 0250-214 Table 1); MH = Sheath of the halogen-free thermoplastic HM2 (Annex A, 70 °C), 1,4 to 1,8 mm, over a halogen-free common covering, 0,4 to 1,4 mm (it may be left off a single core) (DIN VDE 0250-214 5.6, 5.7, Table 1); NHXMH = NHXMH: halogen-free installation cable with improved behaviour in a fire, the type of DIN VDE 0250-214. U0/U 300/500 V (clause 4); laying after DIN VDE 0298-3 (clause 7). DIN VDE 0250-214:2002-04 (1 core 1,5 to 16 mm², 2 to 5 cores 1,5 to 35 mm², 7 cores 1,5 and 2,5 mm², 5.1; bare copper, solid class 1 to 10 mm², stranded class 2 from 16 mm², 5.2; mean overall diameter limits, Table 1, e.g. 3 x 1,5 mm²: 8,0 to 9,6 mm; tests, Table 2: 2 kV a.c. for 5 min, flame DIN EN 50266-2-4, corrosivity DIN EN 50267-2-2, smoke density DIN EN 50268-2).

2 coding systems recognise this code

**Standards behind these values:**

- IEC 60228:2023 (edition 4.0): Conductors of insulated cables

## DIN VDE type names (Germany)

| Symbol | Meaning |
|---|---|
| `N` | German national (VDE) type |
| `HX` | Crosslinked polyethylene insulation 2XI1 (DIN VDE 0276-604), halogen-free: 0,5 mm at 1,5 and 2,5 mm², 0,6 at 4 and 6, 0,7 at 10 and 16, 0,9 at 25 and 35 mm² (DIN VDE 0250-214 Table 1) |
| `MH` | Sheath of the halogen-free thermoplastic HM2 (Annex A, 70 °C), 1,4 to 1,8 mm, over a halogen-free common covering, 0,4 to 1,4 mm (it may be left off a single core) (DIN VDE 0250-214 5.6, 5.7, Table 1) |
| `NHXMH` | NHXMH: halogen-free installation cable with improved behaviour in a fire, the type of DIN VDE 0250-214. U0/U 300/500 V (clause 4); laying after DIN VDE 0298-3 (clause 7). DIN VDE 0250-214:2002-04 (1 core 1,5 to 16 mm², 2 to 5 cores 1,5 to 35 mm², 7 cores 1,5 and 2,5 mm², 5.1; bare copper, solid class 1 to 10 mm², stranded class 2 from 16 mm², 5.2; mean overall diameter limits, Table 1, e.g. 3 x 1,5 mm²: 8,0 to 9,6 mm; tests, Table 2: 2 kV a.c. for 5 min, flame DIN EN 50266-2-4, corrosivity DIN EN 50267-2-2, smoke density DIN EN 50268-2) |

## DIN VDE 0250 cords, control and special cables (Germany)

| Symbol | Meaning |
|---|---|
| `N` | VDE Standard |
| `HX` | Cross-Linked Halogen-Free Polymer Compound |
| `MH` | Connecting Cable, Moderate Mechanical Load |

[How to read a DIN VDE 0250 cords, control and special cables (Germany) cable code](https://thecablecode.com/guides/old-vde-0250)

## NHXMH: equivalents in other countries

Shown for 4x1.5 300/500 V. Each country's rules are applied to this build, keeping the conductor, section, cores, voltage, screen, armour and sheath.

| Country | Standard | Name in that country | Verdict | Differences |
|---|---|---|---|---|
| China | GB/T 9330 | WDZ-KYJY 4x1.5 450/750 V | **Close** | rated higher: 450/750 V (this cable 300/500 V); Insulation 0.5 → 0.6 mm; Inner covering / bedding material: not in the equivalent; Sheath 1.4 → 1.2 mm |

Nominal values computed by each standard's rules, not manufacturer data. This is not a statement that two cables are interchangeable: the buyer's specification and the maker's type test decide.

- [NHXMH cable: meaning, layers and 3D view](https://thecablecode.com/c/NHXMH)
- [Design NHXMH in the cable designer: layers, diameter and weight](https://thecablecode.com/design/NHXMH)
- [More DIN VDE type names (Germany) designations](https://thecablecode.com/standards/de-trade-names)

## Related cables

- [NHXMH-J](https://thecablecode.com/c/NHXMH-J)
- [NHXMH/Q](https://thecablecode.com/c/NHXMH/Q)
- [NHXMH FE180](https://thecablecode.com/c/NHXMH%20FE180)
- [3x2,5 NHXMH](https://thecablecode.com/c/3x2%2C5%20NHXMH)