title: "NA2XY cable: meaning, layers and 3D view"
code: "NA2XY"
url: https://thecablecode.com/c/NA2XY
language: en
---

# NA2XY

**NA2XY** is a [DIN VDE 0271/0276 power cables (Germany)](https://thecablecode.com/standards/din-vde-0271-0276) cable designation: N = VDE Standard; A = Aluminium Conductor; 2X = Cross-Linked Polyethylene (XLPE); Y = Polyvinyl Chloride (PVC).

1 coding system recognises this code

**Standards behind these values:**

- IEC 60502-1:2004 (edition 2.0): Power cables with extruded insulation and their accessories for rated voltages from 1 kV (Um = 1,2 kV) up to 30 kV (Um = 36 kV) - Part 1: Cables for rated voltages of 1 kV (Um = 1,2 kV) and 3 kV (Um = 3,6 kV)
- IEC 60228:2023 (edition 4.0): Conductors of insulated cables

## DIN VDE 0271/0276 power cables (Germany)

| Symbol | Meaning |
|---|---|
| `N` | VDE Standard |
| `A` | Aluminium Conductor |
| `2X` | Cross-Linked Polyethylene (XLPE) |
| `Y` | Polyvinyl Chloride (PVC) |

[How to read a DIN VDE 0271/0276 power cables (Germany) cable code](https://thecablecode.com/guides/din-vde-0271-0276)

## NA2XY: equivalents in other countries

Shown for 3x16 0.6/1 kV. Each country's rules are applied to this build, keeping the conductor, section, cores, voltage, screen, armour and sheath.

| Country | Standard | Name in that country | Verdict | Differences |
|---|---|---|---|---|
| International (IEC) | IEC 60502 | [Al/XLPE/PVC](https://thecablecode.com/c/AL/XLPE/PVC) 3x16 0,6/1 kV (to IEC 60502-1) | **Equivalent** | every value the same |
| South Africa | SANS 1507-4 | no letters for this build | **Close** | Inner covering / bedding material: not in the equivalent; Overall diameter 19.17 → 17.17 mm |
| India | IS 7098 (Part 1) | [A2XY](https://thecablecode.com/c/A2XY) 3x16 1100 V | **Close** | rated 0.635/1.1 kV (same Um 1.2 kV); Inner covering / bedding 1 → 0.3 mm; Overall diameter 19.17 → 17.77 mm |

No equivalent in: BS 5467 (armoured cables only); BS 6724 (armoured cables only, asks another sheath compound); BS 7846 (not in its cable tables, armoured cables only, asks another sheath compound).

Nominal values computed by each standard's rules, not manufacturer data. This is not a statement that two cables are interchangeable: the buyer's specification and the maker's type test decide.

- [NA2XY cable: meaning, layers and 3D view](https://thecablecode.com/c/NA2XY)
- [Design NA2XY in the cable designer: layers, diameter and weight](https://thecablecode.com/design/NA2XY)
- [More DIN VDE 0271/0276 power cables (Germany) designations](https://thecablecode.com/standards/din-vde-0271-0276)

## Related cables

- [NA2XY-O](https://thecablecode.com/c/NA2XY-O)
- [NA2XY-J](https://thecablecode.com/c/NA2XY-J)
- [NA2XYH](https://thecablecode.com/c/NA2XYH)
- [(N)A2XY-J(O)](https://thecablecode.com/c/(N)A2XY-J(O))
- [(N)A2XY 1X300](https://thecablecode.com/c/(N)A2XY%201X300)
- [(N)A2XY 1X240](https://thecablecode.com/c/(N)A2XY%201X240)
- [(N)A2XY 1X240 RM 1.5/1.5 DC kV](https://thecablecode.com/c/(N)A2XY%201X240%20RM%201.5/1.5%20DC%20kV)