**N2XSHR(AL)H** is a [DIN VDE 0271/0276 power cables (Germany)](https://thecablecode.com/standards/din-vde-0271-0276) cable designation: N = VDE Standard; 2X = Cross-Linked Polyethylene (XLPE); S = Copper Screen (Wires, Or Wires And Tape); On Multi-Core Cables Over The Laid-Up Cores; H = Halogen-Free Compound (Insulation Or Sheath, E.g. NHXH, N2XSEHRH); Older MV Cables: Field-Limiting Conductive Layers (H-Type, Höchstädter); R(AL) = Round Aluminium Wire Armour; H = Halogen-Free Compound (Insulation Or Sheath, E.g. NHXH, N2XSEHRH); Older MV Cables: Field-Limiting Conductive Layers (H-Type, Höchstädter).

1 coding system recognises this code

**Standards behind these values:**

- IEC 60502-2:2014 (edition 3.0): Power cables with extruded insulation and their accessories for rated voltages from 1 kV (Um = 1,2 kV) up to 30 kV (Um = 36 kV) - Part 2: Cables for rated voltages from 6 kV (Um = 7,2 kV) up to 30 kV (Um = 36 kV)
- IEC 60228:2023 (edition 4.0): Conductors of insulated cables

## DIN VDE 0271/0276 power cables (Germany)

| Symbol | Meaning |
|---|---|
| `N` | VDE Standard |
| `2X` | Cross-Linked Polyethylene (XLPE) |
| `S` | Copper Screen (Wires, Or Wires And Tape); On Multi-Core Cables Over The Laid-Up Cores |
| `H` | Halogen-Free Compound (Insulation Or Sheath, E.g. NHXH, N2XSEHRH); Older MV Cables: Field-Limiting Conductive Layers (H-Type, Höchstädter) |
| `R(AL)` | Round Aluminium Wire Armour |
| `H` | Halogen-Free Compound (Insulation Or Sheath, E.g. NHXH, N2XSEHRH); Older MV Cables: Field-Limiting Conductive Layers (H-Type, Höchstädter) |

[How to read a DIN VDE 0271/0276 power cables (Germany) cable code](https://thecablecode.com/guides/din-vde-0271-0276)

## N2XSHR(AL)H: equivalents in other countries

Shown for 1x95/16 12/20 kV. Each country's rules are applied to this build, keeping the conductor, section, cores, voltage, screen, armour and sheath.

| Country | Standard | Name in that country | Verdict | Differences |
|---|---|---|---|---|
| Germany | HD 620 S3 10-C (DIN VDE 0276-620) | [N2XSHRH](https://thecablecode.com/c/N2XSHRH) 1x95 RM/16 12/20 kV | **Close** | Insulation screen (semicon) 0.8 → 0.6 mm; Sheath 2.1 → 2.5 mm; Overall diameter 37.5 → 37.9 mm; this cable as built misses 3 of its rules |
| Norway | HD 620 S3 10-K | no letters for this build | **Close** | screen 16 → 25 mm² (HD 620 10-K Table 1); Sheath 2.1 → 1.9 mm; Overall diameter 37.5 → 36.3 mm; this cable as built misses 1 of its rules |
| Netherlands | HD 620 S3 10-J | no letters for this build | **Close** | screen 16 → 25 mm² (HD 620 10-J Table A.1); Sheath 1.2 → 1.1 mm; Sheath 2.1 → 2.5 mm; Overall diameter 37.5 → 38.1 mm; this cable as built misses 1 of its rules |
| Sweden | HD 620 S3 10-M | no letters for this build | **Close** | screen 16 → 25 mm² (HD 620 10-M Tables 1A, 2A, 3A); Insulation screen (semicon) 0.8 → 0.6 mm; Sheath 2.1 → 1.9 mm; Overall diameter 37.5 → 35.9 mm; this cable as built misses 2 of its rules |
| Denmark | HD 620 S3 10-D | no letters for this build | **Close** | screen 16 → 25 mm² (HD 620 10-D Table 1); Sheath 2.1 → 3 mm; Overall diameter 37.5 → 39.3 mm; this cable as built misses 2 of its rules |
| United Kingdom | BS 6622 | Cu/XLPE/CWS/LSZH/AWA/LSZH 1x95/16 12,7/22 kV (to BS 6622) | **Close** | rated 12.7/22 kV (same Um 24 kV); armour steel → Al (single-core a.c.); Wire armour material steel → Al |
|  | HD 620 S3 10-L | no letters for this build | **Close** | Sheath material LSZH → PVC; Sheath 1.2 → 1.9 mm; Wire armour material: not in the equivalent; Sheath material: not in the equivalent |
| United Kingdom | HD 620 S3 10-O | no letters for this build | **Close** | rated 12.7/22 kV (same Um 24 kV); Conductor screen (semicon) 0.6 → 0.7 mm; Insulation screen (semicon) 0.8 → 0.5 mm; Wire screen wire diameter 0.7 → 1.04 mm; this cable as built misses 1 of its rules |
| Europe | HD 620 S3 10-N | no letters for this build | **Close** | Insulation 5.5 → 4.8 mm; Sheath material LSZH → PE; Sheath 1.2 → 1.8 mm; Wire armour material: not in the equivalent |
|  | HD 620 S3 10-G | no letters for this build | **Close** | Insulation 5.5 → 4.4 mm; Wire screen material: not in the equivalent; Sheath material LSZH → PE; Sheath 1.2 → 1.8 mm |
| Europe | HD 620 S3 10-P | no letters for this build | **Close** | Wire screen material: not in the equivalent; Sheath material LSZH → PVC; Sheath 1.2 → 2.7 mm; Wire armour material: not in the equivalent; this cable as built misses 1 of its rules |
| India | IS 7098 (Part 2) | 2XWaY 1x95 12.7/22 kV (the code letters of IS 7098 (Part 2):2011 cl. 21.3) | **Close** | rated 12.7/22 kV (same Um 24 kV); Insulation 5.5 → 6 mm; Wire screen material: not in the equivalent; Sheath material LSZH → PVC; this cable as built misses 1 of its rules |

No equivalent in: HD 620 S3 10-E1 (the size, cores or voltage would change); HD 620 S3 10-E2 (the size, cores or voltage would change); HD 620 S3 10-I1 (the size, cores or voltage would change); HD 620 S3 10-I2 (the size, cores or voltage would change); HD 620 S3 10-I3 (the size, cores or voltage would change).

Nominal values computed by each standard's rules, not manufacturer data. This is not a statement that two cables are interchangeable: the buyer's specification and the maker's type test decide.

- [N2XSHR(AL)H cable: meaning, layers and 3D view](https://thecablecode.com/c/N2XSHR(AL)H)
- [Design N2XSHR(AL)H in the cable designer: layers, diameter and weight](https://thecablecode.com/design/N2XSHR(AL)H)
- [More DIN VDE 0271/0276 power cables (Germany) designations](https://thecablecode.com/standards/din-vde-0271-0276)

## Related cables

- [N2XSHRH](https://thecablecode.com/c/N2XSHRH)
- [N2XSYR(AL)Y](https://thecablecode.com/c/N2XSYR(AL)Y)