# EXVB

**EXVB** is a [NBN type names (Belgium)](https://thecablecode.com/standards/nbn-types) cable designation: E = Energy Cable; X = Cross-linked polyethylene (XLPE) insulation; V = PVC outer sheath; B = Belgium Type; EXVB = EXVB: Belgian unarmoured 0,6/1 kV power cable for outdoor and underground use, copper conductors in XLPE insulation, a PVC inner covering and a reinforced black PVC outer sheath. 0,6/1 kV, 90 C conductor, 250 C short circuit 5 s. NBN HD 603:2007 Part 5 Section A (Standaardbestek 270; Nexans Belgium), CEBEC.

2 coding systems recognise this code

**Standards behind these values:**

- IEC 60502-1:2004 (edition 2.0): Power cables with extruded insulation and their accessories for rated voltages from 1 kV (Um = 1,2 kV) up to 30 kV (Um = 36 kV) - Part 1: Cables for rated voltages of 1 kV (Um = 1,2 kV) and 3 kV (Um = 3,6 kV)
- IEC 60228:2023 (edition 4.0): Conductors of insulated cables

## NBN type names (Belgium)

| Symbol | Meaning |
|---|---|
| `E` | Energy Cable |
| `X` | Cross-linked polyethylene (XLPE) insulation |
| `V` | PVC outer sheath |
| `B` | Belgium Type |
| `EXVB` | EXVB: Belgian unarmoured 0,6/1 kV power cable for outdoor and underground use, copper conductors in XLPE insulation, a PVC inner covering and a reinforced black PVC outer sheath. 0,6/1 kV, 90 C conductor, 250 C short circuit 5 s. NBN HD 603:2007 Part 5 Section A (Standaardbestek 270; Nexans Belgium), CEBEC |

## NBN (Belgian national cable names, ...B types)

| Symbol | Meaning |
|---|---|
| `E` | Energy Cable |
| `X` | Cross-Linked Polyethylene (XLPE) |
| `V` | Polyvinyl Chloride (PVC) |
| `B` | Belgium Type |

[How to read a NBN (Belgian national cable names, ...B types) cable code](https://thecablecode.com/guides/nbn)

## EXVB: equivalents in other countries

Shown for 4x16 0.6/1 kV. Each country's rules are applied to this build, keeping the conductor, section, cores, voltage, screen, armour and sheath.

| Country | Standard | Name in that country | Verdict | Differences |
|---|---|---|---|---|
| Germany | HD 603 5-G (DIN VDE 0276-603) | [N2XY](https://thecablecode.com/c/N2XY) 4x16 RM 0,6/1 kV | **Equivalent** | every value the same |
| South Africa | SANS 1507-4 | no letters for this build | **Close** | Inner covering / bedding 1 → 1.2 mm; Sheath 1.8 → 1.7 mm; Wire armour material: only in the equivalent; Overall diameter 20.81 → 23.51 mm |
| India | IS 7098 (Part 1) | [2XY](https://thecablecode.com/c/2XY) 4x16 1100 V | **Close** | rated 0.635/1.1 kV (same Um 1.2 kV); routine voltage test 3 kV a.c., 5 min (this cable 3.5 kV; IS 1554 (Part 1) cl. 16.2, IS 7098 (Part 1) cl. 17.2.1, IEC 60502-1 Table 11); Inner covering / bedding 1 → 0.3 mm; Overall diameter 20.81 → 19.41 mm |

No equivalent in: BS 5467 (armoured cables only); BS 6724 (armoured cables only, asks another sheath compound); BS 7846 (armoured cables only, asks another sheath compound).

Nominal values computed by each standard's rules, not manufacturer data. This is not a statement that two cables are interchangeable: the buyer's specification and the maker's type test decide.