title: "AXLJ-TTCL TSLF cable: meaning, layers and 3D view"
code: "AXLJ-TTCL TSLF"
url: https://thecablecode.com/c/AXLJ-TTCL%20TSLF
language: en
---

# AXLJ-TTCL TSLF

**AXLJ-TTCL TSLF** is a [Norsk typebetegnelse (Norway)](https://thecablecode.com/standards/norway-type) cable designation: T = 1st letter, insulation: cross-linked polyethylene, PEX ('Tverrbundet polyetylen'); S = 2nd letter: bedding or taping plus concentric conductor ('Fyllkappe/baandering + konsentrisk leder'), used when the 3rd letter is taken; L = 3rd letter: aluminium laminate ('Aluminiumlaminat'); F = 4th letter, outer sheath: semiconducting PE ('Halvledende PE'); TSLF = TSLF: single-core medium-voltage cable, aluminium conductor, XLPE insulation, copper wire screen, aluminium laminate bonded to a PE sheath with an outer semiconducting layer (three cores laid up as 3x1x...). 12/20 (24) kV and 18/30 (36) kV on the pages read (also 12 kV and up to 145 kV in the handbook). Norwegian type designation as tabled in the Nexans Kabelboka (part 2, 'Norske typebetegnelser for kabler'); construction HD 620.10K.

2 coding systems recognise this code

**Standards behind these values:**

- HD 620 S3:2023: Distribution cables with extruded insulation for rated voltages from 3,6/6 (7,2) kV up to and including 20,8/36 (42) kV
- IEC 60228:2023 (edition 4.0): Conductors of insulated cables

## Norsk typebetegnelse (Norway)

| Symbol | Meaning |
|---|---|
| `T` | 1st letter, insulation: cross-linked polyethylene, PEX ('Tverrbundet polyetylen') |
| `S` | 2nd letter: bedding or taping plus concentric conductor ('Fyllkappe/baandering + konsentrisk leder'), used when the 3rd letter is taken |
| `L` | 3rd letter: aluminium laminate ('Aluminiumlaminat') |
| `F` | 4th letter, outer sheath: semiconducting PE ('Halvledende PE') |
| `TSLF` | TSLF: single-core medium-voltage cable, aluminium conductor, XLPE insulation, copper wire screen, aluminium laminate bonded to a PE sheath with an outer semiconducting layer (three cores laid up as 3x1x...). 12/20 (24) kV and 18/30 (36) kV on the pages read (also 12 kV and up to 145 kV in the handbook). Norwegian type designation as tabled in the Nexans Kabelboka (part 2, 'Norske typebetegnelser for kabler'); construction HD 620.10K |

## China (GB / JB/T / MT cable model codes)

| Symbol | Meaning |
|---|---|
| `A` | Twin Cable |
| `X` | Natural Or Styrene-Butadiene Rubber |
| `L` | Aluminium Conductor |
| `J` | Stranded Conductor |
| `T` | Copper Conductor |
| `T` | Copper Conductor |
| `C` | Heavy Duty (Characteristic Letter, As In YC) |
| `L` | Aluminium Conductor |
| `T` | Copper Conductor |
| `S` | Silicone Rubber |
| `L` | Aluminium Conductor |
| `F` | Chloroprene Rubber |

[How to read a China (GB / JB/T / MT cable model codes) cable code](https://thecablecode.com/guides/china)

## AXLJ-TTCL TSLF: equivalents in other countries

Shown for 1x240/25 12/20 kV. Each country's rules are applied to this build, keeping the conductor, section, cores, voltage, screen, armour and sheath.

| Country | Standard | Name in that country | Verdict | Differences |
|---|---|---|---|---|
| International (IEC) | IEC 60502 | [Al/XLPE/CWS/PE](https://thecablecode.com/c/AL/XLPE/CWS/PE) 1x240/25 12/20 kV (to IEC 60502-2) | **Equivalent** | Sheath 2.2 → 2.1 mm; Overall diameter 39 → 39.6 mm |
| Netherlands | HD 620 S3 10-J | YMeKrvasdlwd 12/20 kV 1x240 Al rs +as25 (key read from a maker (Nedkab), the NEN text not seen) | **Close** | Sheath 2.2 → 2.5 mm; Overall diameter 39 → 40.4 mm; this cable as built misses 1 of its rules |
| Germany | HD 620 S3 10-C (DIN VDE 0276-620) | [NA2XS(FL)2Y](https://thecablecode.com/c/NA2XS(FL)2Y) 1x240 RM/25 12/20 kV | **Close** | Insulation screen (semicon) 0.8 → 0.6 mm; Sheath 2.2 → 2.5 mm; Overall diameter 39 → 40 mm; this cable as built misses 2 of its rules |
| Denmark | HD 620 S3 10-D | [PEX-AL](https://thecablecode.com/c/PEX-AL) 1x240+35 12/20 (24) kV (the letters do not say the laminate and the water block) | **Close** | screen 25 → 35 mm² (HD 620 10-D Table 1); Overall diameter 39 → 39.8 mm; this cable as built misses 1 of its rules |
| Sweden | HD 620 S3 10-M | [AXCLJ-TT](https://thecablecode.com/c/AXCLJ-TT) 1x240/35 12/20 (24) kV (NKT writes a near build without the C (AXLJ)) | **Close** | screen 25 → 35 mm² (HD 620 10-M Tables 1A, 2A, 3A); Insulation screen (semicon) 0.8 → 0.6 mm; Overall diameter 39 → 38.6 mm; this cable as built misses 2 of its rules |
|  | HD 620 S3 10-L | no letters for this build | **Close** | Swelling tape (water block) material: not in the equivalent; Swelling tape (water block) material: not in the equivalent; Laminate (radial water block) material: not in the equivalent; Sheath material PE → PVC |
| Spain | HD 620 S3 10-E1 | [RHZ1-OL](https://thecablecode.com/c/RHZ1-OL) 12/20 kV 1 x 240 K Al + H16 | **Close** | Conductor screen (semicon) 0.6 → 0.5 mm; Insulation screen (semicon) 0.8 → 0.5 mm; Wire screen section 25 → 16 mm²; Swelling tape (water block) material: not in the equivalent; this cable as built misses 1 of its rules |
| Europe | HD 620 S3 10-N | no letters for this build | **Close** | Insulation 5.5 → 4.8 mm; Swelling tape (water block) material: not in the equivalent; Swelling tape (water block) material: not in the equivalent; Laminate (radial water block) material: not in the equivalent |
| United Kingdom | HD 620 S3 10-O | no letters for this build | **Close** | rated 12.7/22 kV (same Um 24 kV); Conductor screen (semicon) 0.6 → 0.7 mm; Insulation screen (semicon) 0.8 → 0.5 mm; Swelling tape (water block) material: not in the equivalent; this cable as built misses 1 of its rules |
|  | HD 620 S3 10-G | no letters for this build | **Close** | Insulation 5.5 → 4.3 mm; Wire screen material: not in the equivalent; Laminate (radial water block) material: not in the equivalent; Sheath 2.2 → 2 mm |
| Spain | HD 620 S3 10-E2 | no letters for this build | **Close** | Conductor screen (semicon) 0.6 → 0.5 mm; Insulation 5.5 → 4.9 mm; Insulation screen (semicon) 0.8 → 0.5 mm; Wire screen material: not in the equivalent; this cable as built misses 2 of its rules |
| Italy | HD 620 S3 10-I1 | [ARE4H5EX](https://thecablecode.com/c/ARE4H5EX) 12/20 kV 1 x 240 | **Close** | Insulation 5.5 → 4.31 mm; Insulation screen (semicon) 0.8 → 0.6 mm; Wire screen material: not in the equivalent; Swelling tape (water block) material: not in the equivalent; this cable as built misses 2 of its rules |
| Europe | HD 620 S3 10-P | no letters for this build | **Close** | Swelling tape (water block) material: not in the equivalent; Wire screen material: not in the equivalent; Swelling tape (water block) material: not in the equivalent; Laminate (radial water block) material: not in the equivalent; this cable as built misses 1 of its rules |
| India | IS 7098 (Part 2) | [A2X2Y](https://thecablecode.com/c/A2X2Y) 1x240 12.7/22 kV (the code letters of IS 7098 (Part 2):2011 cl. 21.3) | **Close** | rated 12.7/22 kV (same Um 24 kV); Insulation 5.5 → 6 mm; Swelling tape (water block) material: not in the equivalent; Wire screen material: not in the equivalent; this cable as built misses 1 of its rules |

No equivalent in: BS 6622 (armoured cables only); HD 620 S3 10-I2 (the size, cores or voltage would change); HD 620 S3 10-I3 (the size, cores or voltage would change).

Nominal values computed by each standard's rules, not manufacturer data. This is not a statement that two cables are interchangeable: the buyer's specification and the maker's type test decide.

- [AXLJ-TTCL TSLF cable: meaning, layers and 3D view](https://thecablecode.com/c/AXLJ-TTCL%20TSLF)
- [Design AXLJ-TTCL TSLF in the cable designer: layers, diameter and weight](https://thecablecode.com/design/AXLJ-TTCL%20TSLF)
- [More Norsk typebetegnelse (Norway) designations](https://thecablecode.com/standards/norway-type)

## Related cables

- [TSLF](https://thecablecode.com/c/TSLF)