title: "AXAL cable: meaning, layers and 3D view"
code: "AXAL"
url: https://thecablecode.com/c/AXAL
language: en
---

# AXAL

**AXAL** is a [SS 424 17 01 (Sweden)](https://thecablecode.com/standards/ss-424-17-01) cable designation: A = Aluminium Conductor; X = Cross-Linked Polyethylene (XLPE, PEX); A = Screen Of Aluminium Foil And/Or Aluminium Wire; L = Polyethylene (PE).

3 coding systems recognise this code

**Standards behind these values:**

- IEC 60502-2:2014 (edition 3.0): Power cables with extruded insulation and their accessories for rated voltages from 1 kV (Um = 1,2 kV) up to 30 kV (Um = 36 kV) - Part 2: Cables for rated voltages from 6 kV (Um = 7,2 kV) up to 30 kV (Um = 36 kV)
- HD 620 S3:2023: Distribution cables with extruded insulation for rated voltages from 3,6/6 (7,2) kV up to and including 20,8/36 (42) kV
- IEC 60228:2023 (edition 4.0): Conductors of insulated cables

## SS 424 17 01 (Sweden)

| Symbol | Meaning |
|---|---|
| `A` | Aluminium Conductor |
| `X` | Cross-Linked Polyethylene (XLPE, PEX) |
| `A` | Screen Of Aluminium Foil And/Or Aluminium Wire |
| `L` | Polyethylene (PE) |

[How to read a SS 424 17 01 (Sweden) cable code](https://thecablecode.com/guides/ss-424-17-01)

## China (GB / JB/T / MT cable model codes)

| Symbol | Meaning |
|---|---|
| `A` | Twin Cable |
| `X` | Natural Or Styrene-Butadiene Rubber |
| `A` | Aluminium Foil With Polyethylene Sheath |
| `L` | Aluminium Conductor |

[How to read a China (GB / JB/T / MT cable model codes) cable code](https://thecablecode.com/guides/china)

## CEI-UNEL 35011 (Italy)

| Symbol | Meaning |
|---|---|
| `A` | Aluminium Conductor |
| `X` | Helically Bundled Visible Cores |
| `A` | Aluminium Sheath, Pressed Or Welded, Smooth |
| `L` | Alloyed Lead Sheath For General Use |

[How to read a CEI-UNEL 35011 (Italy) cable code](https://thecablecode.com/guides/cei-unel-35011)

## AXAL: equivalents in other countries

Shown for 3x95/25 12/20 kV. Each country's rules are applied to this build, keeping the conductor, section, cores, voltage, screen, armour and sheath.

| Country | Standard | Name in that country | Verdict | Differences |
|---|---|---|---|---|
| Norway | HD 620 S3 10-K | no letters for this build | **Equivalent** | Insulation screen (semicon) 0.6 → 0.8 mm; Overall diameter 60.73 → 61.59 mm |
| Denmark | HD 620 S3 10-D | [PEX-AL](https://thecablecode.com/c/PEX-AL) 3x95+25 12/20 (24) kV | **Equivalent** | Insulation screen (semicon) 0.6 → 0.8 mm; Overall diameter 60.73 → 63.31 mm |
| International (IEC) | IEC 60502 | [Al/XLPE/CWS/PE](https://thecablecode.com/c/AL/XLPE/CWS/PE) 3x95/25 12/20 kV (to IEC 60502-2) | **Equivalent** | Insulation screen (semicon) 0.6 → 0.8 mm; Overall diameter 60.73 → 63.31 mm |
| Netherlands | HD 620 S3 10-J | [YMeKrvas](https://thecablecode.com/c/YMeKrvas) 12/20 kV 3x95 Al rs +as35 (key read from a maker (Nedkab), the NEN text not seen) | **Close** | screen 25 → 35 mm² (HD 620 10-J Table A.3); Insulation screen (semicon) 0.6 → 0.8 mm; Sheath 3 → 3.2 mm; Overall diameter 60.73 → 63.71 mm; this cable as built misses 2 of its rules |
| India | IS 7098 (Part 2) | [A2X2Y](https://thecablecode.com/c/A2X2Y) 3x95 12.7/22 kV (the code letters of IS 7098 (Part 2):2011 cl. 21.3) | **Close** | rated 12.7/22 kV (same Um 24 kV); Insulation 5.5 → 6 mm; Insulation screen (semicon) 0.6 → 0.8 mm; Inner covering / bedding material semicon → PVC; this cable as built misses 2 of its rules |

No equivalent in: HD 620 S3 10-C (DIN VDE 0276-620) (no three-core cable at this voltage); BS 6622 (armoured cables only, asks a screen on each core); HD 620 S3 10-E1 (the size, cores or voltage would change); HD 620 S3 10-E2 (the size, cores or voltage would change); HD 620 S3 10-I1 (the size, cores or voltage would change); HD 620 S3 10-I2 (the size, cores or voltage would change); HD 620 S3 10-I3 (the size, cores or voltage would change); HD 620 S3 10-G (the size, cores or voltage would change); HD 620 S3 10-L (the size, cores or voltage would change); HD 620 S3 10-N (the size, cores or voltage would change); HD 620 S3 10-O (the size, cores or voltage would change); HD 620 S3 10-P (the size, cores or voltage would change).

Nominal values computed by each standard's rules, not manufacturer data. This is not a statement that two cables are interchangeable: the buyer's specification and the maker's type test decide.

- [AXAL cable: meaning, layers and 3D view](https://thecablecode.com/c/AXAL)
- [Design AXAL in the cable designer: layers, diameter and weight](https://thecablecode.com/design/AXAL)
- [More SS 424 17 01 (Sweden) designations](https://thecablecode.com/standards/ss-424-17-01)

## Related cables

- [AXAH](https://thecablecode.com/c/AXAH)