title: "A2XS2Y cable: meaning, layers and 3D view"
code: "A2XS2Y"
url: https://thecablecode.com/c/A2XS2Y
language: en
---

# A2XS2Y

**A2XS2Y** is a [DIN VDE 0271/0276 power cables (Germany)](https://thecablecode.com/standards/din-vde-0271-0276) cable designation: A = Aluminium Conductor; 2X = Cross-Linked Polyethylene (XLPE); S = Copper Screen (Wires, Or Wires And Tape); On Multi-Core Cables Over The Laid-Up Cores; 2Y = Polyethylene (PE).

2 coding systems recognise this code

**Standards behind these values:**

- IEC 60502-2:2014 (edition 3.0): Power cables with extruded insulation and their accessories for rated voltages from 1 kV (Um = 1,2 kV) up to 30 kV (Um = 36 kV) - Part 2: Cables for rated voltages from 6 kV (Um = 7,2 kV) up to 30 kV (Um = 36 kV)
- IEC 60228:2023 (edition 4.0): Conductors of insulated cables

## DIN VDE 0271/0276 power cables (Germany)

| Symbol | Meaning |
|---|---|
| `A` | Aluminium Conductor |
| `2X` | Cross-Linked Polyethylene (XLPE) |
| `S` | Copper Screen (Wires, Or Wires And Tape); On Multi-Core Cables Over The Laid-Up Cores |
| `2Y` | Polyethylene (PE) |

[How to read a DIN VDE 0271/0276 power cables (Germany) cable code](https://thecablecode.com/guides/din-vde-0271-0276)

## India (IS 1554 / IS 7098 cable code)

| Symbol | Meaning |
|---|---|
| `A` | Aluminium Conductor |
| `2X` | Cross-Linked Polyethylene (XLPE) |
| `S` | Synthetic Yarn Braid (Rubber Cables); Lapped Fibrous Bedding Or Serving (Paper Cables) |
| `2Y` | Polyethylene Outer Sheath |

[How to read a India (IS 1554 / IS 7098 cable code) cable code](https://thecablecode.com/guides/is-1554)

## A2XS2Y: equivalents in other countries

Shown for 1x95/16 12/20 kV. Each country's rules are applied to this build, keeping the conductor, section, cores, voltage, screen, armour and sheath.

| Country | Standard | Name in that country | Verdict | Differences |
|---|---|---|---|---|
|  | HD 620 S3 10-L | no letters for this build | **Close** | Sheath material PE → PVC |
| Denmark | HD 620 S3 10-D | [PEX-AL](https://thecablecode.com/c/PEX-AL) 1x95+25 12/20 (24) kV | **Close** | screen 16 → 25 mm² (HD 620 10-D Table 1); this cable as built misses 1 of its rules |
| Norway | HD 620 S3 10-K | [TXSE](https://thecablecode.com/c/TXSE) 24 kV 1 x 95 mm2 A (provisional code designation of HD 620 10-K Table 4; X is not explained in the standard) | **Close** | screen 16 → 25 mm² (HD 620 10-K Table 1); Overall diameter 30.7 → 29.9 mm; this cable as built misses 1 of its rules |
| Europe | HD 620 S3 10-N | no letters for this build | **Close** | Insulation 5.5 → 4.8 mm; Sheath 1.9 → 1.8 mm; Overall diameter 30.7 → 29.1 mm |
| Germany | HD 620 S3 10-C (DIN VDE 0276-620) | [NA2XS2Y](https://thecablecode.com/c/NA2XS2Y) 1x95 RM/16 12/20 kV | **Close** | Insulation screen (semicon) 0.8 → 0.6 mm; Sheath 1.9 → 2.5 mm; Overall diameter 30.7 → 31.5 mm; this cable as built misses 3 of its rules |
| United Kingdom | HD 620 S3 10-O | no letters for this build | **Close** | rated 12.7/22 kV (same Um 24 kV); Conductor screen (semicon) 0.6 → 0.7 mm; Insulation screen (semicon) 0.8 → 0.5 mm; Wire screen wire diameter 0.7 → 1.04 mm; this cable as built misses 1 of its rules |
| Sweden | HD 620 S3 10-M | AXCLJ 1x95/25 12/20 (24) kV (NKT writes a near build without the C (AXLJ)) | **Close** | screen 16 → 25 mm² (HD 620 10-M Tables 1A, 2A, 3A); Insulation screen (semicon) 0.8 → 0.6 mm; Overall diameter 30.7 → 29.5 mm; this cable as built misses 2 of its rules |
| Netherlands | HD 620 S3 10-J | [YMeKrvas](https://thecablecode.com/c/YMeKrvas) 12/20 kV 1x95 Al rs +as25 (key read from a maker (Nedkab), the NEN text not seen) | **Close** | screen 16 → 25 mm² (HD 620 10-J Table A.1); Sheath 1.9 → 2.5 mm; Overall diameter 30.7 → 31.9 mm; this cable as built misses 2 of its rules |
| Spain | HD 620 S3 10-E1 | [RHZ1-OL](https://thecablecode.com/c/RHZ1-OL) 12/20 kV 1 x 95 K Al + H16 | **Close** | Conductor screen (semicon) 0.6 → 0.5 mm; Insulation screen (semicon) 0.8 → 0.5 mm; Sheath material PE → LSZH; Sheath 1.9 → 2.7 mm; this cable as built misses 1 of its rules |
| Europe | HD 620 S3 10-P | no letters for this build | **Close** | Wire screen material: not in the equivalent; Sheath material PE → PVC; Sheath 1.9 → 2.7 mm; Tape screen material: only in the equivalent; this cable as built misses 1 of its rules |
| India | IS 7098 (Part 2) | [A2X2Y](https://thecablecode.com/c/A2X2Y) 1x95 12.7/22 kV (the code letters of IS 7098 (Part 2):2011 cl. 21.3) | **Close** | rated 12.7/22 kV (same Um 24 kV); Insulation 5.5 → 6 mm; Wire screen material: not in the equivalent; Sheath 1.9 → 2.2 mm; this cable as built misses 2 of its rules |
| Italy | HD 620 S3 10-I2 | [ARE4H5EX](https://thecablecode.com/c/ARE4H5EX) 12/20 kV 1 x 95 | **Close** | Insulation 5.5 → 4.3 mm; Insulation screen (semicon) 0.8 → 0.6 mm; Wire screen material: not in the equivalent; Sheath 1.9 → 1.32 mm; this cable as built misses 1 of its rules |
|  | HD 620 S3 10-G | no letters for this build | **Close** | Insulation 5.5 → 4.4 mm; Wire screen material: not in the equivalent; Sheath 1.9 → 1.8 mm; Swelling tape (water block) material: only in the equivalent |
| Spain | HD 620 S3 10-E2 | no letters for this build | **Close** | Conductor screen (semicon) 0.6 → 0.5 mm; Insulation 5.5 → 4.9 mm; Insulation screen (semicon) 0.8 → 0.5 mm; Wire screen material: not in the equivalent; this cable as built misses 2 of its rules |
| Italy | HD 620 S3 10-I1 | [ARE4H5EX](https://thecablecode.com/c/ARE4H5EX) 12/20 kV 1 x 95 | **Close** | Insulation 5.5 → 4.31 mm; Insulation screen (semicon) 0.8 → 0.6 mm; Wire screen material: not in the equivalent; Sheath 1.9 → 2 mm; this cable as built misses 2 of its rules |

No equivalent in: BS 6622 (armoured cables only); HD 620 S3 10-I3 (the size, cores or voltage would change).

Nominal values computed by each standard's rules, not manufacturer data. This is not a statement that two cables are interchangeable: the buyer's specification and the maker's type test decide.

- [A2XS2Y cable: meaning, layers and 3D view](https://thecablecode.com/c/A2XS2Y)
- [Design A2XS2Y in the cable designer: layers, diameter and weight](https://thecablecode.com/design/A2XS2Y)
- [More DIN VDE 0271/0276 power cables (Germany) designations](https://thecablecode.com/standards/din-vde-0271-0276)

## Related cables

- [NA2XS2Y](https://thecablecode.com/c/NA2XS2Y)
- [NA2XS2Y rmv](https://thecablecode.com/c/NA2XS2Y%20rmv)
- [A2XS2YT](https://thecablecode.com/c/A2XS2YT)