title: "(N)A2XRY cable: meaning, layers and 3D view"
code: "(N)A2XRY"
url: https://thecablecode.com/c/(N)A2XRY
language: en
---

# (N)A2XRY

**(N)A2XRY** is a [DIN VDE 0271/0276 power cables (Germany)](https://thecablecode.com/standards/din-vde-0271-0276) cable designation: (N) = Similar To VDE Standard; A = Aluminium Conductor; 2X = Cross-Linked Polyethylene (XLPE); R = Round Steel Wire; Y = Polyvinyl Chloride (PVC).

1 coding system recognises this code

**Standards behind these values:**

- IEC 60502-1:2004 (edition 2.0): Power cables with extruded insulation and their accessories for rated voltages from 1 kV (Um = 1,2 kV) up to 30 kV (Um = 36 kV) - Part 1: Cables for rated voltages of 1 kV (Um = 1,2 kV) and 3 kV (Um = 3,6 kV)
- IEC 60502-2:2014 (edition 3.0): Power cables with extruded insulation and their accessories for rated voltages from 1 kV (Um = 1,2 kV) up to 30 kV (Um = 36 kV) - Part 2: Cables for rated voltages from 6 kV (Um = 7,2 kV) up to 30 kV (Um = 36 kV)
- IEC 60228:2023 (edition 4.0): Conductors of insulated cables

## DIN VDE 0271/0276 power cables (Germany)

| Symbol | Meaning |
|---|---|
| `(N)` | Similar To VDE Standard |
| `A` | Aluminium Conductor |
| `2X` | Cross-Linked Polyethylene (XLPE) |
| `R` | Round Steel Wire |
| `Y` | Polyvinyl Chloride (PVC) |

[How to read a DIN VDE 0271/0276 power cables (Germany) cable code](https://thecablecode.com/guides/din-vde-0271-0276)

## (N)A2XRY: equivalents in other countries

Shown for 4x16 0.6/1 kV. Each country's rules are applied to this build, keeping the conductor, section, cores, voltage, screen, armour and sheath.

| Country | Standard | Name in that country | Verdict | Differences |
|---|---|---|---|---|
| Germany | HD 603 5-G (DIN VDE 0276-603) | NA2XYRY 4x16 RM 0,6/1 kV | **Close** | this cable as built misses 1 of its rules |
| South Africa | SANS 1507-4 | no letters for this build | **Close** | Inner covering / bedding 1 → 1.2 mm; Sheath 1.2 → 1.7 mm; Wire armour wire diameter 1.6 → 1.25 mm; Sheath material: not in the equivalent |
| India | IS 7098 (Part 1) | [A2XWY](https://thecablecode.com/c/A2XWY) 4x16 1100 V | **Close** | rated 0.635/1.1 kV (same Um 1.2 kV); routine voltage test 3 kV a.c., 5 min (this cable 3.5 kV; IS 1554 (Part 1) cl. 16.2, IS 7098 (Part 1) cl. 17.2.1, IEC 60502-1 Table 11); Inner covering / bedding 1 → 0.3 mm; Sheath 1.2 → 1.4 mm |
| United Kingdom | BS 5467 | [Al/XLPE/PVC/SWA/PVC](https://thecablecode.com/c/AL/XLPE/PVC/SWA/PVC) 4x16 0,6/1 kV (to BS 5467) | **Close** | built the British way: the armour on an extruded bedding, no separation sheath; conductor RM → RE; Inner covering / bedding 1 → 0.8 mm; Sheath 1.2 → 1.6 mm |

No equivalent in: BS 6724 (asks another sheath compound); BS 7846 (not in its cable tables, asks another sheath compound).

Nominal values computed by each standard's rules, not manufacturer data. This is not a statement that two cables are interchangeable: the buyer's specification and the maker's type test decide.

- [(N)A2XRY cable: meaning, layers and 3D view](https://thecablecode.com/c/(N)A2XRY)
- [Design (N)A2XRY in the cable designer: layers, diameter and weight](https://thecablecode.com/design/(N)A2XRY)
- [More DIN VDE 0271/0276 power cables (Germany) designations](https://thecablecode.com/standards/din-vde-0271-0276)

## Related cables

- [N2XRY](https://thecablecode.com/c/N2XRY)
- [NA2XY](https://thecablecode.com/c/NA2XY)
- [NA2XRH](https://thecablecode.com/c/NA2XRH)
- [NA2XSY](https://thecablecode.com/c/NA2XSY)
- [NA2XR2Y](https://thecablecode.com/c/NA2XR2Y)
- [NA2XCY](https://thecablecode.com/c/NA2XCY)
- [NA2XHY](https://thecablecode.com/c/NA2XHY)
- [NA2XRGY](https://thecablecode.com/c/NA2XRGY)
- [NA2XSRY](https://thecablecode.com/c/NA2XSRY)
- [(N)A2X2Y](https://thecablecode.com/c/(N)A2X2Y)